Download Bryant 355M-40-4 Operating instructions
Transcript
TABLE 8—AIR CONDITIONING (A/C) AIRFLOW SETUP SWITCH POSITION AIR CONDITIONER (TONS) Default 1-1/2 2 2-1/2 3 3-1/2 4 5 CFM AIRFLOW 1200 or 2000 600 800 1000 1200 1400 1600 2000 A/C SETUP SWITCH POSITION A/C-1 A/C-2 A/C-3 OFF OFF OFF ON OFF ON OFF ON OFF ON OFF ON ON OFF OFF ON ON OFF OFF OFF ON ON ON ON ALLOWABLE FURNACE MODEL SETUP 042040 3 Tons 1200 CFM X X X X X — — 042060 3 Tons 1200 CFM X X X X X — — 042080 3 Tons 1200 CFM X X X X X — — 060080 5 Tons 2000 CFM — X X X X X X 060100 5 Tons 2000 CFM — X X X X X X 060120 5 Tons 2000 CFM — X X X X X X X—Indicates allowable selection. TABLE 9—CONTINUOUS FAN (CF) AIRFLOW SETUP SWITCH POSITION CONTINUOUS FAN (CFM) Default 600 800 1000 1200 1400 1600 2000 CF SETUP SWITCH POSITION CF-1 CF-2 CF-3 OFF OFF OFF ON OFF OFF OFF ON OFF ON ON OFF OFF OFF ON ON OFF ON OFF ON ON ON ON ON ALLOWABLE FURNACE MODEL SETUP 042040 565* X X X X X — — 042060 515* X X X X X — — 042080 690* X X X X X — — 060080 690* — X X X X X X 060100 860* — X X X X X X 060120 1035* — X X X X X X * Add 15% additional CFM when Bypass Humidifier switch SW-3 on control board is used. X—Indicates allowable selection. 3. See Table 10 for setup switch description. (See Fig. 24 and 45.) 1 4. Replace main furnace door and blower access panel. NOTE: If a bypass humidifier is used, setup switch SW-3 (BPH) should be in ON position. This prevents nuisance limit trips caused by the increased temperature in return air resulting from bypass. NOTE: If modulating dampers are used, setup switch SW-5 (MZ) should be in ON position. This allows furnace control center to compensate for modulating dampers. The control re-calibrates for new system static conditions once every minute while operating in low-heat or continuous fan modes. OFF III. PRIME CONDENSATE TRAP WITH WATER A95198 Fig. 45—Example of Setup Switch in OFF Position CAUTION: Condensate trap must be PRIMED or proper draining may not occur. The condensate trap has 2 internal chambers which can ONLY be primed by pouring water into the inducer drain side of condensate trap. 1. Remove main furnace door and blower access panel. 2. Locate CF setup switches on control center. (See Fig. 25.) 3. Determine desired continuous fan airflow. 4. Use Table 9 or wiring schematic to determine proper setup position of CF switches. (See Fig. 24 and 45.) NOTE: The CF switches are factory set to provide continuous fan airflow equal to low-heat mode. 1. Remove upper inducer housing drain connection cap. (See Fig. 46.) 2. Connect field-supplied 1/2-in. ID tube to upper inducer housing drain connection. 5. Replace main furnace door and blower access panel. 3. Insert field-supplied funnel into tube. C. Setup Switches (SW) The control center has 8 setup switches that may be set to meet the application requirements. Position these setup switches for the appropriate requirement. 4. Pour 1 quart of water into funnel/tube. Water should run through inducer housing, overfill condensate trap, and flow into open field drain. (See Fig. 47.) 5. Remove funnel and tube from inducer housing and replace drain connection cap and clamp. 1. Remove main furnace door and blower access panel. 2. Locate setup switches on control center. (See Fig. 25.) —35—