Download Daikin BRC7E65 Specifications
Transcript
Si38-606 Troubleshooting by Indication on the Remote Controller 2.11 “C9” Indoor Unit: Malfunction of Thermistor (R1T) for Suction Air Remote Controller Display C9 Applicable Models AII indoor unit models Method of Malfunction Detection Malfunction detection is carried out by temperature detected by suction air temperature thermistor. Malfunction Decision Conditions When the suction air temperature thermistor becomes disconnected or shorted while the unit is running. Supposed Causes Defect of indoor unit thermistor (R1T) for air inlet Defect of indoor unit PC board Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred. Connector is connected to X13A or X19A of the indoor unit PC board. NO Connect the thermistor and turn on again. YES Resistance is normal when measured after disconnecting the thermistor NO (R1T) from the indoor unit PC board. (7.2kΩ~ 112kΩ) YES Replace the thermistor (R1T). Replace the indoor unit PC board. (V2786) ∗: Refer to thermistor resistance / temperature characteristics table on P232. Troubleshooting 131