Download Bryant 4-WAY MULTIPOISE TWO-STAGE CONDENSING GAS FURNACE 352AAV Instruction manual
Transcript
352AAV Deluxe 4--Way Multipoise Fixed--Capacity Condensing Gas Furnace Service and Maintenance Instructions for Sizes 060--120, Series A NOTE: Read the entire instruction manual before starting the installation. ! ELECTRICAL HAZARD TABLE OF CONTENTS PAGE WARNING SHOCK, FIRE, OR EXPLOSION Failure to follow safety warnings exactly could result in dangerous operation, personal injury, death, or property damage. SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 2 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 -- Before servicing, disconnect all electrical power to furnace. --When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly. -- Verify proper operation after servicing. ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS . . . 2 CARE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . 3 Cleaning and/or Replacing Air Filter . . . . . . . . . . . . . . . . . . . . 3 Blower Motor and Wheel Maintenance . . . . . . . . . . . . . . . . . . 4 Cleaning Burners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 ! Cleaning Heat Exchangers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Primary Heat Exchangers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 WARNING ELECTRICAL SHOCK, FIRE, OR EXPLOSION HAZARD Secondary Heat Exchangers . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Flushing Collector Box and Drainage System . . . . . . . . . . . . . 8 Failure to follow this warning could result in possible damage to this equipment, personal injury, or death. Servicing Hot Surface Igniter . . . . . . . . . . . . . . . . . . . . . . . . . 10 Electrical Controls and Wiring . . . . . . . . . . . . . . . . . . . . . . . . 11 The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recommended in the User’s Manual. Checking Heat Tape Operation (If Applicable) . . . . . . . . . . . 11 Winterizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Status Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Component Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 ! WARNING FIRE OR EXPLOSION HAZARD ama Failure to follow this warning could property damage, personal injury, or death. Never store anything on, near, or in contact with the furnace, such as: 1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners, or other cleaning tools. 2. Soap powders, bleaches, waxes or other cleaning compounds, plastic or plastic containers, gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids, or other volatile fluids. 3. Paint thinners and other painting compounds, paper bags, or other paper products. ISO 9001:2000 CERTIFIED REGISTERED 1 352AAV SAFETY CONSIDERATIONS Recognize safety information. This is the safety--alert symbol . When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified service agency personnel should install, repair, or service heating equipment. Untrained personnel can perform basic maintenance functions described in User’s Information Manual such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply. Follow all safety codes including the National Fuel Gas Code (NFGC) NFPA 54--2006/ANSI Z223.1--2006 in the USA, CSA B149.1--05 National Standard of Canada, Natural Gas and Propane Installation Codes (NSCNGPIC) in Canada, and the Installation Standards, Warm Air Heating and Air Conditioning Systems (NFPA 90B) ANSI/NFPA 90B. Wear safety glasses and work gloves. Have a fire extinguisher available during start--up and adjustment procedures and service calls. ! A05085 Fig. 1 -- Multipoise Furnace in Upflow Orientation AIRFLOW UPFLOW CAUTION UNIT DAMAGE HAZARD HORIZONTAL LEFT Failure to follow this caution may result in damage to furnace. Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. HORIZONTAL RIGHT DOWNFLOW AIRFLOW AIRFLOW AIRFLOW GENERAL A93041 Fig. 2 -- Multipoise Orientation This furnace can be installed as a direct vent (2--pipe) or non--direct vent (1--pipe) condensing gas furnace. These instructions are written as if the furnace is installed in an upflow application. An upflow furnace application is where the blower is located below the combustion and controls section of the furnace, and conditioned air is discharged upward. Since this furnace can be installed in any of the 4 positions shown in Fig. 2, you may need to revise your orientation to component location accordingly. ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS ! CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may damage furnace components. Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential. 2 CARE AND MAINTENANCE For continuing high performance and to minimize possible furnace failure, it is essential that maintenance be performed annually. Consult your local dealer for maintenance and maintenance contract availability. ! WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Turn off the gas and electrical supplies to the unit before performing any maintenance or service. Follow the operating instructions on the label attached to the furnace. The minimum maintenance that should be performed on this equipment is as follows: 1. Check and clean or replace air filter each month as needed. 2. Check blower motor and wheel for cleanliness annually. 3. Check electrical connections for tightness and controls for proper operation each heating season. Service as necessary. 4. Check for proper condensate drainage. Clean as necessary. 5. Check for blockages in combustion--air and vent pipes annually. 6. Check burners for cleanliness annually. ! Step 1 — Cleaning and/or Replacing Air Filter The air filter arrangement may vary depending on the application or orientation. See Table 1 or 2 for filter size and type. ! WARNING FIRE, CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal injury, death or property damage. Never operate unit without a filter or with the blower access panel removed. Operating a unit without a filter or with the blower access door removed could cause damage to the furnace blower motor. Dust and lint on internal parts of furnace can cause a loss of efficiency. NOTE: If the filter has an airflow direction arrow, the arrow must point toward the blower. To clean or replace filters, proceed as follows: If filter is installed in filter cabinet adjacent to furnace: 1. Turn off electrical supply to furnace. 2. Remove filter cabinet door. 3. Slide filter out of cabinet. 4. Furnaces with a washable filter, clean filter by spraying cold tap water through filter in opposite direction of airflow. Rinse filter and let dry. Oiling or coating of the filter is not recommended. 5. If equipped with factory specified disposable media filter, replace only with a factory specified media filter of the same size. 6. Slide filter into cabinet. 7. Replace filter cabinet door. 8. Turn on electrical supply to furnace. If filter is installed in furnace blower compartment: 1. Turn off electrical supply to furnace. 2. Remove main furnace door and blower access panel. 3. Release filter retainer wire. (See Fig. 3 or 4.) NOTE: Filters shown in Fig. 3 and 4 can be in furnace blower compartment or in filter cabinet, but not in both. 4. Slide filter out of furnace. 5. Furnaces with washable filter(s) should clean filter by spraying cold tap water through filter in opposite direction of airflow. 6. Rinse filter and let dry. Oiling or coating filter is not recommended. 7. Slide filter into furnace. 8. Recapture filter retaining wire. 9. Replace blower access panel and main furnace door. 10. Turn on electrical supply to furnace. CAUTION CUT HAZARD Failure to follow this caution may result in personal injury. Be careful of sharp metal edges, etc. Use care and wear protective clothing, gloves, and safety glasses when removing parts. 3 352AAV 1. Disconnect all power to the furnace. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND. 2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged. 3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch ungrounded objects, etc.). 4. If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before touching control or wires. 5. Use this procedure for installed and uninstalled (ungrounded) furnaces. 6. Before removing a new control from its container, discharge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects. 7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage. Table 1 – Furnace Air Filter Table FURNACE CASING WIDTH IN (MM) 17--- 1/2 (445) 21 (533 ) 24--- 1/2 (610) FILTER QUANTITY AND SIZE * SIDE RETURN* BOTTOM RETURN* IN (MM) IN (MM) (1) 16 x 25 x 3/4 (1) 16 x 25 x 3/4 (406 x 635 x 19) (406 x 635 x 19) (1) 16 x 25 x 3/4 (1) 20 x 25 x 3/4 (406 x 635 x 19) (508 x 635 x 19) (1) 16 x 25 x 3/4 (1) 24 x 25 x 3/4 (406 x 635 x 19) (610 x 635 x 19) FILTER TYPE* 3/4” (19 mm) thick washable 3/4” (19 mm) thick washable 3/4” (19 mm) thick washable Table 2 – Air Filter Located in Filter Cabinet 352AAV FILTER CABINET HEIGHT --- IN (MM) FILTER SIZE --- IN (MM) (1) 16 x 25 x 3/4* (406 x 635 x 19) or (1) 16 x 25 x 4--- 5/16 (406 x 635 x 110) (1) 20 x 25 x 3/4* (508 x 635 x 19) or (1) 20 x 25 x 4--- 5/16 (508 x 635 x 110) (1) 24 x 25 x 3/4*or (610 x 635 x 19) or (1) 24 x 25 x 4--- 5/16 (610 x 635 x 110) 16 (406) 20 (508) 24 (610) FILTER TYPE Washable Washable Washable * Filters with a side return--air may have a different filter size. Measure the filter to obtain the correct size. Step 2 — Blower Motor and Wheel Maintenance To ensure long life, economy, and high efficiency, clean accumulated dirt and grease from blower wheel and motor annually. The inducer and blower motors are pre--lubricated and require no additional lubrication. These motors can be identified by the absence of oil ports on each end of the motor. The following items should be performed by a qualified service technician. Clean blower motor and wheel as follows: 1. Turn off electrical supply to furnace. 2. Remove main furnace door and blower access panel. FILTER FILTER SUPPORT FILTER RETAINER WASHABLE FILTER OR DISPOSABLE MEDIA FILTER IN FILTER CABINET A08588 Fig. 3 -- Bottom Filter Arrangement 3. Disconnect blower motor wires from furnace control. Field thermostat connections may need to be disconnected depending on their length and routing. 4. Remove control box mounting screws and position control box, transformer, and door switch assembly to right side of furnace casing. 5. If condensate trap is located in left-- or right--hand side of furnace casing, proceed to item 6, otherwise remove trap and tubing as described below (See Fig. 5): a. Disconnect field drain connection from condensate trap. b. Disconnect drain and relief port tubes from condensate trap. c. Remove condensate trap from blower shelf. 6. Remove screws securing blower assembly to blower shelf and slide blower assembly out of furnace. Detach ground wire and disconnect blower motor harness plugs from blower motor. NOTE: Blower wheel is fragile. Use care. 7. Clean blower wheel and motor by using a vacuum with soft brush attachment. Be careful not to disturb balance weights (clips) on blower wheel vanes. Do not bend wheel or blades as balance will be affected. 8. If greasy residue is present on blower wheel, remove wheel from the blower housing and wash it with an appropriate degreaser. To remove wheel: a. Mark blower wheel location on shaft before disassembly to ensure proper reassembly. b. Loosen setscrew holding blower wheel on motor shaft. NOTE: Mark blower mounting arms and blower housing so each arm is positioned at the same hole location during reassembly. c. Mark blower wheel orientation and cutoff plate location to ensure proper reassembly. d. Remove screws securing cutoff plate and remove cutoff plate from housing. e. Remove bolts holding motor mounts to blower housing and slide motor and mounts out of housing. Disconnect capacitor and ground wire attached to blower housing before removing motor. Motor mounts do not need to be removed from motor. f. Remove blower wheel from housing. 4 ! FILTER IN FURNACE CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in noise or furnace component failure. FILTER RETAINER WASHABLE FILTER OR DISPOSABLE MEDIA FILTER IN FILTER CABINET A08589 Fig. 4 -- Filter Installed for Side Inlet PLUG CAP COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED) COLLECTOR BOX TUBE (PINK) COLLECTOR BOX TUBE (GREEN) INDUCER HOUSING (MOLDED) DRAIN TUBE (BEHIND COLLECTOR BOX DRAIN TUBE) COLLECTOR BOX DRAIN TUBE (BLUE) g. Clean wheel per instructions on degreaser cleaner. Do not get degreaser in motor. 9. Reassemble motor and blower wheel by reversing items 8b through 8f. Ensure wheel is positioned for proper rotation. Tighten setscrew to between 140--160 in.--lb torque. NOTE: Be sure to attach ground wire to blower housing. 10. Reinstall blower assembly in furnace. 11. Reinstall control box, transformer, and door switch assembly on blower shelf. 12. Reinstall condensate trap and tubing if previously removed. a. Reinstall condensate trap in hole in blower shelf. b. Connect condensate trap drain tubes. See Fig. 5 or tubing diagram on main furnace door for proper tube location. (1.) Connect 1 tube (blue or blue and white striped) from collector box. (2.) Connect 1 tube (violet or unmarked) from inducer housing. (3.) Connect 1 tube (relief port, green or pink) from collector box. NOTE: Ensure tubes are not kinked or pinched, as this will affect operation. c. Connect field drain to condensate trap. 13. Reconnect wires. Refer to furnace wiring diagram and connect thermostat leads if previously disconnected. (See Fig. 16.) NOTE: Refer to Table 3 for motor speed lead reconnection if leads were not identified before disconnection. ! CAUTION UNIT DAMAGE HAZARD CONDENSATE TRAP Failure to adjust the heating speed may shorten heat exchanger life. Heating air speed selection MUST be adjusted to provide proper temperature rise as specified on the rating plate. FIELD-INSTALLED FACTORY-SUPPLIED DRAIN TUBE COUPLING (LEFT DRAIN OPTION) Table 3 – Speed Selection FIELD-INSTALLED FACTORY-SUPPLIED DRAIN TUBE FIELD-INSTALLED FACTORY-SUPPLIED 1⁄2-IN. CPVC STREET ELBOWS (2) FOR LEFT DRAIN OPTION FIELD-INSTALLED FACTORY-SUPPLIED DRAIN TUBE COUPLING (RIGHT DRAIN OPTION) A01030 Fig. 5 -- Factory--Shipped Upflow Tube Configuration (Shown with Blower Access Panel Removed) COLOR SPEED White Black Yellow Orange{ Common High Medium High Medium Blue Medium Low Red Low* *Continuous blower speed. {Available on 5 ---speed blowers only. 5 FACTORY ATTACHED TO Com Cool Spare High--- Gas Heat Spare/High--- Gas Heat Low--- Gas Heat 352AAV The blower wheel should not be dropped or bent as balance will be affected. ! CELL PANEL WARNING MANIFOLD MOUNTING SCREWS ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Blower access door switch opens 115--v power to furnace control. No component operation can occur. Caution must be taken when manually closing this switch for service purposes. 352AAV GASKET 14. Turn on electrical supply. Manually close blower access door switch. Use a piece of tape to hold switch closed. Check for proper rotation and speed changes by performing a component self--test as shown at the bottom of Service label. (See Fig. 20.) 15. If furnace is operating properly, remove tape to release blower access door switch, replace blower access door, and replace main furnace door. MANIFOLD GAS VALVE REGULATOR FITTING GAS CONTROL VALVE Step 3 — Cleaning Burners A02312 The following items should be performed by a qualified service technician. If the burners develop an accumulation of light dirt or dust, they may be cleaned by using the following procedure: 1. Turn off gas and electrical supplies to furnace. 2. Remove main furnace door. 3. Remove burner box cover. 4. Using backup wrench, disconnect gas supply pipe from furnace gas control valve. ! Fig. 6 -- Burner Box Assembly CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in damage to furnace. Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. 5. Remove wires from gas valve. Note location for reassembly. 6. Remove burner box pressure tube from gas valve regulator fitting. 7. Unplug igniter from harness. 8. Remove igniter leads from slot in manifold grommet. 9. Remove screws that secure manifold to burner box. (See Fig. 6.) NOTE: Do not remove burner box from cell panel. 10. Remove manifold, orifices, and gas valve as 1 assembly. 11. Remove screws attaching burner assembly in burner box. NOTE: Use care when removing and reinstalling burners not to strike the hot surface igniter. 12. Remove burner assembly from burner box. NOTE: All burners are attached to burner bracket and can be removed as 1 assembly. 13. Clean burners with soft brush and vacuum. 14. Reinstall manifold, orifice, and gas valve assembly in burner box. Ensure manifold seal grommet is installed properly and burners fit over orifices. 15. Reinsert the igniter wires in the slot in the manifold grommet, dressing the wires to ensure there is no tension on the igniter itself. (See Fig. 7.) IGNITER WIRES MUST BE PLACED IN THIS SLOT A05074 Fig. 7 -- Igniter Wire Placement ! WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in electrical shock, personal injury, or death. Igniter wires must be securely placed in slot in manifold grommet or else they could become pinched or severed and electrically shorted. 16. Reconnect wires to gas valve and igniter. Refer to furnace wiring diagram for proper wire location. 17. Reinstall burner box pressure tube to gas valve regulator fitting. 18. Reinstall gas supply pipe to furnace gas control valve using backup wrench on gas valve to prevent rotation and improper orientation. 6 NOTE: Use propane gas resistant pipe dope to prevent gas leaks. DO NOT use Teflon tape. ! PRIMARY HX INLET OPENINGS WARNING FIRE, EXPLOSION, UNIT DAMAGE HAZARD Failure to follow this warning could result in property damage, personal injury, or death. Gas valve switch MUST be facing forward or tilted upward. ! WARNING FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury, death, or property damage. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. 21. Check for gas leaks. 22. Replace main furnace door. Step 4 — Cleaning Heat Exchangers The following items should be performed by a qualified service technician. Primary Heat Exchangers If the heat exchangers get an accumulation of light dirt or dust on the inside, they may be cleaned by the following procedure: NOTE: If heat exchangers get a heavy accumulation of soot and carbon, both the primary and secondary heat exchangers should be replaced rather than trying to clean them thoroughly due to their intricate design. A build--up of soot and carbon indicates that a problem exists which needs to be corrected, such as improper adjustment of manifold pressure, insufficient or poor quality combustion air, improper vent termination, incorrect size or damaged manifold orifices(s), improper gas, or a restricted heat exchanger (primary or secondary). Action must be taken to correct the problem. 1. Turn off gas and electrical supplies to furnace. 2. Remove main furnace door. ! CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in furnace component damage. Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and hazardous operation. 3. Disconnect wires or connectors to flame rollout switch, gas valve, igniter, and flame sensor. 4. Disconnect combustion-air intake pipe from intake housing. 5. Remove the pressure switch tube from intake housing. 6. Remove screws attaching intake housing to burner box, and rotate intake housing away from burner box for removal. 7. Using backup wrench, disconnect gas supply pipe from furnace gas control valve. 8. Disconnect pressure tubing from gas valve. Fig. 8 -- Cleaning Inlet Openings of Primary A96305 Heat Exchangers 9. Remove 2 screws attaching top filler panel and rotate upwards to gain access to screws attaching burner box to cell panel. 10. Remove screws attaching burner box to cell panel. (See Fig. 6). NOTE: Burner box, cover, manifold, gas valve, and burner assembly should be removed as one assembly. 11. Clean heat exchanger openings with a vacuum and a soft brush. (See Fig. 8.) NOTE: After cleaning, inspect the heat exchanger to ensure they are free of all foreign objects that may restrict flow of combustion products. 12. Reverse items 4 through 10 for reassembly. ! CAUTION UNIT MAY NOT OPERATE Failure to attach this ground wire to an adequate casing ground may cause the furnace control to lock out. The ground wire from the gas valve MUST be attached to the burner box attachment screw. NOTE: Be sure burner box gasket is installed between burner box and cell panel. (See Fig. 6.) If gasket is damaged, replace it. NOTE: Inspect combustion--air intake housing. If foamed gasket was removed, check for any damage. If gasket is damaged in any way, it must be repaired. To repair, remove damaged gasket section, apply sealant releasing agent such as PAM cooking spray or equivalent (must not contain corn nor canola oil, halogenated hydrocarbons nor aromatic content, to prevent inadequate seal from occurring) to burner box and apply a small bead of G.E. RTV 162, G.E. RTV 6702, or Dow--Corning RTV 738 sealant to edge of combustion--air intake housing. (See Fig. 9.) 13. Refer to furnace wiring diagram and reconnect wires to flame rollout switch, gas valve, igniter, and flame sensor. 14. Reconnect pressure switch tubes to gas valve and intake housing. Refer to tube routing label on main furnace door or Fig. 10 for proper tube location. Be sure tubes are not kinked. 15. Turn on gas and electrical supplies to furnace. 7 352AAV 19. Replace burner box cover. 20. Turn on gas and electrical supplies to furnace. 16. Check furnace operation through 2 complete heat operating cycles. Look through sight glass in burner enclosure to check burners. Burner flames should be clear blue, almost transparent. (See Fig. 11.) ! WARNING FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury, death, or property damage. 352AAV Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. 17. Check for gas leaks. 18. Replace main furnace door. Secondary Heat Exchangers NOTE: The condensing side (inside) of the secondary heat exchangers CANNOT be serviced or inspected. A small number of bottom outlet openings can be inspected by removing the inducer assembly. See Flushing Collector Box and Drainage System section for details on removing inducer assembly. 10. Reassemble inducer assembly by reversing items 5-7. Tighten vent coupling clamp screw(s) to 15 in.-lb of torque. NOTE: If seal between the inducer housing and the collector box is damaged in any way, it must be repaired. To repair, apply sealant releasing agent such as PAM cooking spray or equivalent (must not contain corn nor canola oil, halogenated hydrocarbons nor aromatic content, to prevent inadequate seal from occurring) to inducer housing. Apply a small bead of G.E. RTV 162, G.E. RTV 6702, or Dow--Corning RTV 738 sealant to groove in collector box. (See Fig. 12.) 11. Refer to furnace wiring diagram and reconnect wires to inducer motor and pressure switches or connectors. 12. Reconnect pressure tubes to pressure switches. See diagram on main furnace door for proper location of tubes. Be sure tubes are not kinked. (See Fig. 10.) 13. Turn on gas and electrical supplies to furnace. 14. Check furnace operation through 2 complete heat operating cycles. Check area below inducer housing, vent pipe, and condensate trap to ensure no condensate leaks occur. If leaks are found, correct the problem. ! ELECTRICAL OPERATION HAZARD Step 5 — Flushing Collector Box and Drainage System 1. Turn off gas and electrical supplies to furnace. 2. Remove main furnace door. 3. Disconnect inducer motor and pressure switch wires or connectors. 4. Disconnect pressure switch tubes. 5. Disconnect vent pipe from inducer housing outlet by loosening coupling clamp on inducer outlet. 6. Disconnect drain tube from inducer housing. (See Fig. 10.) NOTE: Ensure the drain tube disconnected from the inducer housing is higher than the collector box opening or water will flow out of tube. 7. Remove inducer housing assembly by removing 4 bolts attaching assembly to cell panel. 8. Flush inside of collector box with water until discharge from condensate trap is clean and runs freely. 9. Inspect inside area of collector box for any pieces of foreign materials and remove them if present. ! WARNING Failure to follow the safety warnings exactly could result in serious injury, death, or property damage. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. 15. Check for gas leaks. 16. Replace main furnace door. RTV PAM CAUTION Fig. 9 -- Combustion-- Air Intake Housing Gasket Repair UNIT DAMAGE HAZARD Failure to follow this caution may result in furnace component damage. DO NOT use wire brush or other sharp object to inspect or dislodge materials in secondary heat exchangers as cutting the secondary heat exchanger protective coating may occur. Flush with water only. 8 A93087 TUBE ROUTING Furnace is shipped from factory in upflow configuration. Pressure tube and drain tube routing MUST match the diagrams below. Tube location when used in UPFLOW application (Blower access panel removed) CAP CAP COLLECTOR BOX TUBE (PINK) PLUG COLLECTOR BOX TUBE (GREEN) COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED) INDUCER HOUSING (MOLDED) DRAIN TUBE (BEHIND COLLECTOR BOX DRAIN TUBE) CONDENSATE TRAP COLLECTOR BOX DRAIN TUBE (BLUE) COLLECTOR BOX TUBE (GREEN) CONDENSATE TRAP INDUCER HOUSING DRAIN TUBE (VIOLET) Tube location when used in DOWNFLOW application PLUG CAP COLLECTOR BOX DRAIN TUBE (BLUE) COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED) COLLECTOR BOX TUBE (GREEN) COLLECTOR BOX TUBE (PINK) PLUG COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED) COLLECTOR BOX TUBE (GREEN) INDUCER HOUSING DRAIN TUBE (VIOLET) COLLECTOR BOX EXTENSION TUBE COLLECTOR BOX EXTENSION TUBE CONDENSATE TRAP Tube location when used on HORIZONTAL - LEFT application COLLECTOR BOX TUBE (GREEN) BURNER ENCLOSURE PRESSURE REFERENCE TUBE ASSEMBLY COLLECTOR BOX DRAIN TUBE (BLUE) COLLECTOR BOX DRAIN TUBE (BLUE) CONDENSATE TRAP DRAIN TUBE COUPLING COLLECTOR BOX EXTENSION DRAIN TUBE COLLECTOR BOX TUBE (PINK) RELOCATE TUBE BETWEEN BLOWER SHELF AND INDUCER HOUSING FOR 060 AND 080 HEATING INPUT FURNACES COLLECTOR BOX EXTENSION TUBE COLLECTOR BOX TUBE (PINK) AUXILIARY "J" BOX RELOCATED HERE PLUG INDUCER HOUSING DRAIN TUBE (VIOLET) COLLECTOR BOX EXTENSION TUBE GAS VALVE Tube location when used on HORIZONTAL - RIGHT application COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED) PLUG CAP CONDENSATE TRAP DRAIN TUBES ROUTED IN FRONT OF GAS VALVE INDUCER HOUSING DRAIN TUBE (VIOLET) AUXILIARY "J" BOX COLLECTOR BOX EXTENSION TUBE BURNER ENCLOSURE PRESSU REFERENCE TUBE ASSEMBL DRAIN TUBE COUPLING COLLECTOR BOX TUBE (PINK) BURNER ENCLOSURE PRESSURE REFERENCE TUBE ASSEMBLY COLLECTOR BOX EXTENSION DRAIN TUBE Condensate Trap on RIGHT Side T COLLECTOR BOX DRAIN TUBE (BLUE) PLUGGED END CAP NOTE: COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED) COLLECTOR BOX DRAIN TUBE (BLUE) FIELD-INSTALLED FACTORY-SUPPLIED 1/2-IN. CPVC STREET ELBOWS (2) FOR LEFT DRAIN OPTION FIELD-INSTALLED FACTORY-SUPPLIED DRAIN TUBE BURNER ENCLOSURE PRESSURE REFERENCE TUBE ASSEMBLY PLUG COLLECTOR BOX TUBE (PINK) FIELD-INSTALLED FACTORY- SUPPLIED DRAIN TUBE COUPLING (RIGHT DRAIN OPTION) FIELD-INSTALLED FACTORY-SUPPLIED DRAIN TUBE COUPLING (LEFT DRAIN OPTION) Condensate Trap on LEFT Side Condensate Trap on LEFT Side Optional BURNER ENCLOSURE PRESSURE REFERENCE TUBE ASSEMBLY 352AAV Condensate Trap; Factory Installed in Blower Shelf CAP BURNER ENCLOSURE PRESSURE REFERENCE TUBE ASSEMBLY COLLECTOR BOX EXTENSION TUBE COLLECTOR BOX TUBE (GREEN) COLLECTOR BOX DRAIN TUBE (BLUE AND WHITE STRIPED) CONDENSATE TRAP INDUCER HOUSING DRAIN TUBE (VIOLET) 1. All tubing must be connected securely and routed to avoid kinks and traps. 2. Pressure tubing must always slope away from pressure switch to collector box connection as shown. 3. HORIZONTAL-LEFT installations require the collector box pressure tube to be relocated between the inducer housing and the blower shelf to prevent a trap. Refer to the Installation Instructions for further details. ;; ;; Fig. 10 -- Furnace Pressure and Draining Tube Diagram 326476-201 REV. B (lit-bottom) A01052 BURNER FLAME BURNER MANIFOLD Fig. 11 -- Burner Flame 9 A89020 ! CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in premature failure of the igniter. PAM The igniter is fragile. DO NOT allow it to hit the side of the burner box parts while removing or replacing it. RTV 352AAV e. If replacement is required, replace igniter on igniter bracket and then install assembly to burner box to avoid damage to the igniter. 6. To replace igniter and bracket assembly, reverse items 5a through 5d. 7. Reconnect igniter wire connection and insert the igniter wires in the slot in the manifold grommet, dressing the igniter wires to ensure there is no tension on the igniter itself. (See Fig. 7.) ! A93081 ELECTRICAL SHOCK HAZARD Fig. 12 -- Gasket on Collector Box Failure to follow this warning could result in electrical shock, personal injury, or death. Step 6 — Servicing Hot Surface Igniter Igniter wires must be securely placed in slot in manifold grommet or else they could become pinched or severed and electrically shorted. The igniter does NOT require annual inspection. Check igniter resistance before removal. 1. Turn off gas and electrical supplies to furnace. 2. Remove main furnace door. 3. Disconnect igniter wire connection. 4. Check igniter resistance. Igniter resistance is affect by temperature. Only check resistance when the igniter is at room temperature. d. Using an ohm meter, check resistance across both igniter leads in connector. e. Cold reading should be between 40 ohms and 70 ohms. 5. Remove igniter assembly. ! WARNING 8. Reinstall burner box cover. 9. Turn on gas and electrical supplies to furnace. 10. Verify igniter operation by initiating furnace control board self-test feature or by cycling thermostat. 11. Replace main furnace door. CAUTION BURN HAZARD Failure to follow this caution may result in minor personal injury. A05075 Allow igniter to cool before removal. Normal operating temperatures exceed 2000°F. Fig. 13 -- Igniter Bracket a. Remove burner box cover. b. Remove igniter wires from slot in manifold grommet. (See Fig. 7.) c. Using a 1/4 in. driver, remove the single screw securing the igniter bracket to the burner box bracket (See Fig. 13.) and carefully withdraw the igniter and bracket assembly through the front of the burner box without striking the igniter on surrounding parts. Note that the igniter bracket has a handle that extends to the front of the burner box to aid in handling (See Fig. 13.). d. Inspect igniter for signs of damage or failure. 10 2-5/32˝ (55 mm) Fig. 14 -- Igniter A04181 Step 7 — Electrical Controls and Wiring ! In applications where the ambient temperature around the furnace is 32°F (0_C) or lower, freeze protection measures are required. If this application is where heat tape has been applied, check to ensure it will operate when low temperatures are present. NOTE: Heat tape, when used, should be wrapped around the condensate drain trap and drain line. There is no need to use heat tape within the furnace casing. Most heat tapes are temperature activated, and it is not practical to verity the actual heating of the tape. Check the following: 1. Check for signs of physical damage to heat tape such as nicks, cuts, abrasions, gnawing by animals, etc. 2. Check for discolored heat tape insulation. If any damage or discolored insulation is evident, replace heat tape. 3. Check that heat tape power supply circuit is on. Step 9 — Winterizing ! WARNING UNIT DAMAGE HAZARD ELECTRICAL SHOCK HAZARD Failure to follow this caution may result in furnace component damage. Failure to follow this warning could result in personal injury or death. Freezing condensate left in the furnace may damage the furnace. There may be more than 1 electrical supply to the unit. Check accessories and cooling unit for additional electrical supplies. The electrical ground and polarity for 115-v wiring must be maintained properly. Refer to Fig. 15a or 15b for field wiring information and to Fig. 21 for unit wiring information. NOTE: If the polarity is not correct or the furnace is not grounded, the STATUS LED on the furnace control board will flash rapidly and prevent the furnace from operating. The control system also requires an earth ground for proper operation of the furnace control board and flame sensor. The 24-v circuit contains an automotive-type, 3-amp fuse located on the control. (See Fig. 16.) Any direct shorts of the 24-v wiring during installation, service, or maintenance will cause this fuse to blow. If fuse replacement is required, use ONLY a 3 amp fuse. The control LED will display status code 24 when fuse needs to be replaced. With power to the unit disconnected, check all electrical connections for tightness. Tighten all screws on electrical connections. If any smoky or burned connections are found, disassemble the connection, clean all parts, strip wire, and reassemble properly and securely. Reconnect electrical supply to unit and observe unit through 1 complete operating cycle for proper operation. ! CAUTION If the furnace will be off for an extended period of time in a structure where the temperature will drop to 32°F (0_C)or below, winterize as follows: 1. Turn off electrical supply to furnace. 2. Remove main furnace door. 3. Disconnect cap from unused drain tap on inducer housing. (See Fig. 18.) 4. Connect field-supplied 1/2-in. I.D. tube to upper inducer housing drain connection. ! CAUTION UNIT DAMAGE HAZARD Failure of plastic components may occur. Do not use ethylene glycol (Prestone II antifreeze/coolant or equivalent automotive type). CAUTION UNIT AND PROPERTY DAMAGE HAZARD Failure to follow this caution may result in furnace component failures or water property damage. If this furnace is to be operated in an unconditioned space where the ambient temperatures may be 32_F (0_C) or lower, freeze protection measures must be taken. (See Fig. 17). See CONDENSATE DRAIN PROTECTION section of Installation, Start--up, and Operating Instructions. 11 352AAV Step 8 — Checking Heat Tape Operation (If Applicable) FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-V WIRING 1-STAGE THERMOSTAT TERMINALS W FIVE WIRE Y R G C FIELD-SUPPLIED FUSED DISCONNECT TWO-WIRE HEATINGONLY BLK BLK WHT WHT 208/230- OR 460-V THREE PHASE W2 GND GND COM 208/230-V SINGLE PHASE W/W1 GND 352AAV GND Y/Y2 115-V FUSED DISCONNECT SWITCH (WHEN REQUIRED) JUNCTION BOX CONTROL BOX GND R GND CONDENSING UNIT G 24-V TERMINAL BLOCK FURNACE NOTES: 1. Connect Y-terminal as shown for proper operation. 2. Some thermostats require a "C" terminal connection as shown. 3. If any of the original wire, as supplied, must be replaced, use same type or equivalent wire. A99071 Fig. 15 -- Field Wiring FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-V WIRING 2-STAGE THERMOSTAT TERMINALS SEVEN WIRE W2 W1 Y2 R G Y1 C FIELD-SUPPLIED FUSED DISCONNECT THREE-WIRE HEATINGONLY W2 BLK BLK WHT 208/230- OR 460-V THREE PHASE GND GND COM WHT 208/230-V SINGLE PHASE W/W1 GND GND C Y/Y2 115-V FUSED JUNCTION DISCONNECT BOX SWITCH CONTROL (WHEN REQUIRED) BOX Y1 Y2 R G 24-V TERMINAL BLOCK FURNACE GND GND 2-SPEED CONDENSING UNIT NOTES: 1. Connect Y-terminal as shown for proper operation. 2. Some thermostats require a "C" terminal connection as shown. 3. If any of the original wire, as supplied, must be replaced, use same type or equivalent wire. Fig. 16 -- Field Wiring 12 A99072 SETUP SWITCHES LOW-HEAT ONLY AND BLOWER OFF-DELAY TWINNING AND/OR COMPONENT TEST TERMINAL TRANSFORMER 24-VAC CONNECTIONS 0.5-AMP024 VAC R LE SEC-2 PL3 NEUTRAL-L2 PL1 OD E EAC-2 D SEC-1 352AAV PL1 - LOW VOLTAGE MAIN HARNESS CONNECTOR FUSE 3-AMP US C 3-AMP FUSE PLT HUM ACRDJ TEST/TWIN STAT LED OPERATION & DIAGNOSTIC LIGHT 1 2 3 LHT OFF DLY Y1 DHUM G COM WW1 Y/Y2 24V HUMIDIFIER TERMINAL (24-VAC 0.5 AMP MAX.) ON OFF W2 24-V-THERMOSTAT TERMINALS ACRDJ - AIR CONDITIONING RELAY DISABLE JUMPER PL3 1 1 BLW 115-VAC (L2) NEUTRAL CONNECTIONS BHI/LOR BHT/CLR BLWR HI HEAT IDM COOL IHI/LOR SPARE-2 PR-1 PL2 EAC-1 1 SPARE-2 L1 1-AMP@115 VAC COOL SPARE-1 SPARE-1 BLOWER SPEED SELECTION TERMINALS HSIR IDR LO HEAT HI HEAT LO HEAT HSI HI LO 115-VAC (L1) LINE VOLTAGE CONNECTION PL2 - HOT SURFACE IGNITER & INDUCER MOTOR CONNECTOR EAC-1 TERMINAL (115-VAC 1.0 AMP MAX.) A02017 Fig. 17 -- Two-- Stage Control 8. Propylene glycol need not be removed before restarting furnace. WIRING DIAGRAM See Fig. 21 for Wiring Diagram. TROUBLESHOOTING Use the Troubleshooting Guide, the status code LED on the control and the Component Test to isolate furnace operation problems. Status Codes Fig. 18 -- Winterizing the Furnace A07911 5. Insert funnel in tube and pour up to 1 quart of antifreeze, propylene glycol (RV, swimming pool antifreeze, or equivalent) into funnel until it is visible at point where condensate enters open drain. (See Fig. 19.) 6. Reconnect drain cap to inducer housing. 7. Replace main furnace door. For an explanation of status codes, refer to service label located on back of main furnace door or Fig. 20. The stored status codes will NOT be erased from the control memory, if 115-or 24-v power is interrupted. The control will store up to 7 Status Codes. NOTE: Removing the blower access door will open the blower access door switch and terminate 115--v power to the control. To read current status code, remove main furnace door. The status code LED can be viewed through the sight glass on the blower access door. NOTE: NO thermostat signals may be present at control and all blower off delays must be completed to view previous codes. To retrieve previous codes, remove one of the red main limit or flame rollout switch wires 1 to 4 sec until the LED light goes out, the reconnect it. (Do not leave red wire disconnected for longer periods of time as the control will assume an overtemperature condition exists and will respond with blower operation.) This places the control in the status recall mode and displays the first code stored in memory. 13 Record the code and repeat the disconnect and reconnect of the red wire, recording each code until code 11 is displayed indicating no additional codes. After the last code is displayed or after 2 minutes in the code recall mode the control will return to normal standby mode. Component Test 352AAV NOTE: The furnace control component test allows all components to run for a short time; except the gas valve and humidifier terminal HUM are not energized for safety reasons. The EAC--1 terminal is energized when blower is energized. This feature helps diagnose a system problem in case of a component failure. The component test feature will not operate if any thermostat signal is present at control and not until all time delays are completed. To Begin Component Self-Test: ! WARNING ELECTRICAL SHOCK OPERATE HAZARD AND UNIT MAY NOT Failure to follow this warning could result in electrical shock, personal injury, or death. Fig. 19 -- Inducer Housing Drain Tube Cap Blower access panel door switch opens 115-v power to control board. No component operation can occur. Caution must be taken when manually closing this switch for service purposes. A99118 1. 2. 3. 4. A99119 Fig. 20 -- Funnel in Drain Tube and Antifreeze Running Through Trap Remove blower access door. Disconnect thermostat R lead from furnace control. Manually close blower door switch. For approximately 2 sec, short (jumper) the COM-24 v terminal on control to the TEST/TWIN 3/16-in. quick-connect terminal on control until LED turns off. Remove jumper from terminals. (See Fig.16.) NOTE: If TEST/TWIN and COM--24v terminals are jumpered longer than 2 sec, LED will flash rapidly and ignore status code retrieval request. Component test sequence for 2-stage furnace is as follows: a. LED will display previous status code 4 times. b. Inducer motor starts on high--speed and continues to run until Step g of component test sequence. c. Hot surface igniter is energized for 15 sec, then off. d. Blower motor operates on LO--HEAT speed for 10 sec. e. Blower motor operates on HI--HEAT speed for 10 sec. f. Blower motor operates on COOL speed for 10 sec. g. Inducer motor goes to low--speed for 10 sec, then stops. 5. Reconnect R lead to furnace control, remove tape from blower door switch, and re-install blower door. 6. Operate furnace per instruction on outer door. 7. Verify furnace shut down by lowering thermostat setting below room temperature. 8. Verify that furnace restarts by raising thermostat setting above room temperature. 14 SERVICE If status code recall is needed, briefly remove then reconnect one main limit wire to display last stored status code. Repeat remove-and-reconnect four more times for previous four status codes, after which the five codes repeat. Status code 11 will display when less than four previous status codes exist. On RED LED controls do not remove power or blower door before initiating status code recall. LED CODE STATUS 352AAV CONTINUOUS OFF - Check for 115VAC at L1 & L2, & 24VAC at SEC-1 & SEC-2. CONTINUOUS ON - Control has 24VAC power. RAPID FLA SHING - Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions. EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES. 11 NO PREVIOUS CODE - Stored status codes are erased automatically after 72 hours. On RED LED boards stored status codes can also be erased when power (115 VAC or 24 VAC) to control is interrupted. 12 BL OWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for the selected blower off-delay time, if unit is powered up during a call for heat (R-W/W1 closed) or (R-W/W1) opens during blower on-delay. 13 LIMIT CIRCUIT LOCKOUT - Lockout occurs if a limit or flame rollout switch is open longer than 3 minutes. - Control will auto reset after three hours. - Refer to #33. 14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34. 21 GAS HEATING LOCKOUT - Control will NOT auto reset. Check for: - Mis-wired gas valve - Defective control (valve relay) 22 ABNO RMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is de-energized. Inducer will run until fault is cleared. Check for: - Leaky gas valve - Stuck-open gas valve 23 PRESSURE SWITCH DID NOT OPEN Check for: - Obstructed pressure tubing - Pressure switch stuck closed 24 SECONDARY VOLTAGE FUSE IS OPEN Check for: - Short circuit in secondary voltage (24VAC) wiring. 31 HIGH-HEAT PRESSURE SWITCH OR RELAY DID NOT CLOSE OR REOPENED Control relay may be defective, refer to status code #32 32 LOW-HEAT PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than five minutes, inducer shuts off for 15 minutes before retry. If opens during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Excessive wind - Restricted vent - Defective inducer motor - Low inlet gas pressure (if LGPS used) - Defective pressure switch - Low inducer voltage (115 VAC) - Inadequate combustion air supply - Proper vent sizing - Disconnected or obstructed pressure tubing 33 LIMIT CIRCUIT FAULT - Indicates a limit or flame rollout, switch is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts off. Flame rollout switch requires manual reset. Check for: - Dirty filter or restricted duct system - Proper vent sizing - Restricted vent - Loose blower wheel - Excessive wind - Defective blower motor or capacitor - Defective switch or connections - Inadequate combustion air supply (Flame Roll-out Switch open). 34 IGNITION PROVING FAILURE - Control will try three more times before lock out #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal) - Manual valve shut-off - Control ground continuity - Gas valve defective or gas valve turned off - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Defective Hot Surface Ignitor - Flame sensor must not be grounded - Green/Yellow wire MUST be connected to furnace sheet metal 43 LOW-HEAT PRESSURE SWITCH OPEN WHILE HIGH-HEAT PRESSURE SWITCH IS CLOSED - Check for: - Disconnected or obstructed pressure tubing - Mis-wired pressure switches - Low-heat pressure switch stuck open - Low inlet gas pressure (if LGPS used) 45 CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats. COMPONENT TEST To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST/TWIN terminal to the "Com 24V" terminal. Status LED will flash last status code and then turn ON the inducer motor. The inducer motor will start in HIGH speed and remain on HIGH speed until the end of the test then shift to LOW speed for 7 to 15 seconds. The hot surface ignitor, blower motor LO HEAT speed, blower motor HI HEAT speed, and blower motor COOL speed will be turned ON for 10-15 seconds each. Gas Valve and Humidifier will not be turned on. When the blower is turned OFF the inducer will be switched to low-speed for 10 seconds. 327885-101 REV. B A02258 Fig. 21 -- Service Label 15 BRN GRN/YEL BRN HI 1 2 3 BLU 16 LEGEND Fig. 22 -- Wiring Diagram GND GV GVR 1, 2 HPS HPSR HSI HSIR HUM IDM IDR IHI/LOR ILK JB LED LGPS LPS LS OL PCB ACR ACRDJ BHI/LOR BHT/CLR BLWR BLWM CAP 1, 2 CPU DHUM EAC-1 EAC-2 FRS FSE FU1 FU2 PLT ACRDJ GRY HPS RED PL1 FRS STATUS CODE LED 1 WHT YEL RED LPS LS NOTE #8 AIR CONDITIONING RELAY, SPST (N.O.) AIR CONDITIONING RELAY DISABLE JUMPER BLOWER MOTOR SPEED CHANGE RELAY, SPDT BLOWER MOTOR SPEED CHANGE RELAY, SPDT BLOWER MOTOR RELAY, SPST-(N.O.) BLOWER MOTOR, PERMANENT-SPLIT-CAPACITOR CAPACITOR MICROPROCESSOR AND CIRCUITRY DHUM CONNECTION ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.0 AMP MAX.) ELECTRONIC AIR CLEANER CONNECTION (COMMON) FLAME ROLLOUT SW. -MANUAL RESET, SPST-(N.C.) FLAME-PROVING ELECTRODE FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED FUSE OR CIRCUIT BREAKER CURRENT INTERRUPT DEVICE (FIELD SUPPLIED AND INSTALLED) EQUIPMENT GROUND GAS VALVE-REDUNDANT GAS VALVE RELAY, DPST-(N.O.) HIGH-HEAT PRESSURE SWITCH, SPST (N.O.) HIGH-HEAT PRESSURE SWITCH RELAY, SPST (N.C.) HOT SURFACE IGNITER (115VAC) HOT SURFACE IGNITER RELAY, SPST (N.O.) 24VAC HUMIDIFIER CONNECTION (0.5 AMP. MAX.) INDUCED DRAFT MOTOR, 2-SPEED, SHADED POLE INDUCED DRAFT MOTOR RELAY, SPST-(N.O.) INDUCER MOTOR SPEED CHANGE RELAY, SPDT BLOWER ACCESS PANEL INTERLOCK SWITCH, SPST-(N.O.) JUNCTION BOX LIGHT-EMITTING DIODE FOR STATUS CODES - AMBER LOW GAS PRESSURE SWITCH, SPST-(N.O.) LOW-HEAT PRESSURE SWITCH, SPST (N.O.) LIMIT SWITCH, AUTO-RESET, SPST (N.C.) AUTO-RESET INTERNAL MOTOR OVERLOAD TEMPERATURE SWITCH (N.C.) PRINTED CIRCUIT BOARD CONTROL Y1 DHUM G Com W/W1 Y/Y2 R 24V LHT OFF DLY W2 ON OFF TEST/TWIN SELECT CHART BLOWER SW LO-HT OFF-DELAY ONLY 1 * 2 3 90 ON NORM SEC. OFF HEAT 1 LO 2 3 * 120 ON HEAT SEC. OFF ONLY 2 3 ON 150 OFF SEC. 2 3 ON 180 OFF SEC. * FACTORY SETTINGS NOTE #3 C GV WHT GRN/YEL 0.5 AMP @ 24 VAC WHT FUSE 3-AMP FU1 NOTE #6 IDR HSIR IHI/LOR L1 NOTE #11 RED PL1 PL2 PL3 PL4 PL5 PLT TRAN TEST/TWIN PL2 IDM WHT BLK YEL ORN BLU RED OL RED BLU BLK BRN WHT BRN START PL5 HSI JUNCTION FIELD EARTH GROUND 326797-101 REV. A PLUG RECEPTACLE FIELD SPLICE EQUIPMENT GROUND TRAN ACR PCB COM 24V Y1 G Y/Y2 W2 DHUM TEST/TWIN W/W1 R HUM NOTE #5 L1 IDR HSIR IHI/LOR L2 L2 1 3 2 NOTE #2 PL2 BHI/LOR LO HEAT EQUIPMENT GROUND 1 2 PL5 HSI PL4 CPU GVR-2 FRS EAC-1 GVR-1 HPSR LS PL1-7 PL1-11 PL1-9 PL1-1 CAP-1 LPS C FSE PL1-5 HI L2 24VAC SEC 2 SEC 1 TRAN NOTE #11 GV L2 L2 PR1 115VAC START BLWM IDM OL LGPS (WHEN USED) HPS PL1-10 M PL1-3 PL1-4 PL1-2 PL1-12 PL1-8 NOTE #6 FU1 COM NOTE #3 PL1-6 EAC-2 OL 4 LO COM 3 HI 1 2 SCHEMATIC DIAGRAM (NATURAL GAS & PROPANE) LO SPARE-1 MED LO NOTE #10 BHT/CLR MED HI HEAT SPARE-2 MED HI COOLING BLWR HI NOTE #9 ILK TO 115VAC FIELD-DISCONNECT SWITCH 352AAV If any of the original equipment wire is replaced use wire rated for 105°C. Use only copper wire between the disconnect switch and the furnace junction box (JB). This wire must be connected to furnace sheet metal for control to prove flame. Symbols are electrical representation only. Solid lines inside PCB are printed circuit board conductors and are not included in the legend. Replace only with a 3 amp fuse. Blower motor (BLWM) and inducer motor (IDM) contain internal auto-reset thermal overload switches (OL). Neutral connections are interchangeable within the NEUTRAL connector block. Blower motor speed selections are for average conditions, see installation instructions for optimum selection. MED not available on some models. Factory connected when LGPS is not used. Ignition lockout will occur after four consecutive unsuccessful trials-for-ignition. Control will auto-reset after three hours. 13. Blower-on delay: gas high-heat 60 seconds, gas low-heat 45 seconds, cooling or heat pump 2 seconds. 14. Blower off-delay: gas heating selections are 90, 120, 150, 180 seconds, cooling or heat pump 90 seconds or 5 seconds when dehumidify call is active. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. NOTES: CAP-1 ILK JB GND PRINTED CIRCIUT BOARD FIELD WIRING SCREW TERMINAL CONDUCTOR ON CONTROL PCB FIELD CONTROL WIRING (24VAC) FIELD CONTROL WIRING (115VAC) FACTORY CONTROL WIRING (24VAC) FACTORY POWER WIRING (115VAC) CONTROL PCB TERMINAL TERMINAL FU2 L1 NOTE #2 WHT BLK NEUTRAL FUSE OR CIRCUIT BREAKER & DISCONNECT SWITCH (WHEN REQ’D) BLWM OL 2 1 GRN /YEL 2 3 4 BRN IDM WHT 12-CIRCUIT PCB CONNECTOR 3-CIRCUIT PCB HSI & IDM CONNECTOR 6-CIRCUIT ICM MOTOR CONNECTOR (NOT SHOWN) 4-CIRCUIT IDM CONNECTOR 2-CIRCUIT HSI CONNECTOR 3-CIRCUIT FACTORY TEST CONNECTOR TRANSFORMER, 115VAC/24VAC COMPONENT TEST & TWINNING TERMINAL WHT HI MED HI MED MED LO LO BLK WHT PL3 1 RED BLK GRN/YEL BLK BLK RED WHT FSE ORN LGPS (WHEN USED) CAP-2 BRN GRN/YEL M HUM SEC-1 SEC-2 CAP-2 CONNECTION DIAGRAM NEUTRAL - L2 EAC-2 BLWR BHT/CLR BLW BHI/LOR HI-HEAT COOL LO-HEAT PR-1 SPARE-2 HSI HI LO EAC-1 1 AMP @ 115 VAC SPARE - 1 PRINTED CIRCIUT BOARD ACRDJ A02176 A05095 17 YES Go to section below for the status code that was flashed. Determine status code. The status code is a 2 digit number with the first digit determined by the number of short flashes and the second digit by the number of long flashes? YES Is LED status light blinking ON/OFF slowly with a combination of short and long flashes? NO Is LED status light blinking rapidly without a pause? Is LED status light on? START YES NO YES NO NO NO Was there a previous status code other than #11? NO YES Replace furnace control. YES 352AAV Run system through a low-heat, high-heat, or cooling cycle to check operation. Status codes are erased after 72 hours. On RED LED boards stored status codes can also be erased whenever (115V or 24V) is interrupted. YES Does the control respond to W/W1, W2, Y1, Y/Y2, and G (24V) thermostat signals? A05111 The thermostat is not compatible with the furnace control. Either install a ballast resistor, connect the Com24V thermostat terminal to the thermostat, or replace the thermostat. NO Does the problem repeat when using a jumper wire? Disconnect all the thermostat wires from the furnace control. YES Is 24V present at W/W1, W2, Y1, Y/Y2 or G thermostat terminals on the furnace control? NO Check room thermostat or interconnecting cable. Close circuit breaker and go back to START. Replace transformer. YES Is circuit breaker closed? Close door switch and go back to START. Check for continuity in wire from circuit breaker to furnace. NO NO NO Replace door switch. YES Is there 115V going to switch? Is door switch closed? To recall status code briefly remove and reconnect one RED wire from the limit switch or flame rollout switch to display stored status code. On RED LED control do not remove power or blower access panel before initiating status code recall. You can also recall the previous status code by momentarily shorting the TEST/TWIN terminal to Com24V terminal until the LED goes out. LED will flash the status of the previous code or status code #11 (1 short and 1 long flash) if there was no previous code. After the control repeats the code 4 times, the control will start the component test sequence. Once initiated the control will turn ON at HI HEAT speed. The inducer will run for the entire component test. The HSI, blower motor LO HEAT speed, HI HEAT speed, and COOL speed will run for 10 – 15 seconds each. Gas valve and humidifier will not be turned on. When the blower motor is turned OFF the inducer will be switched to low-speed for 10 seconds. Check for correct line voltage polarity and grounding. If units are twinned, check for proper low-voltage (24V) transformer phasing. Replace furnace control. YES Is there 24V at SEC-1 and SEC-2? YES Is there 115V at L1 and L2? TROUBLESHOOTING GUIDE — TWO-STAGE NO A05095 E2008 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Printed in U.S.A. 18 Edition Date: 12/08 Catalog No. SM352AAV ---01 Replaces:SP05--- 69 33 LIMIT CIRCUIT FAULT – Indicates the limit or flame rollout switch is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 min. status code #33 continues to flash until blower shuts off. Flame rollout switch requires manual reset. Check for: - Dirty filter or restricted duct system. - Loose blower wheel. - Defective switch or connections. - Defective blower motor or capacitor. - Inadequate combustion air supply (flame rollout switch open). - Restricted vent. - Proper vent sizing. - Excessive wind. 34 IGNITION PROVING FAILURE – If flame is not sensed during the trial for ignition period, the control will repeat the ignition sequence 3 more times before lockout #14 occurs. If flame signal is lost during the blower on-delay period, blower will come on for the selected blower off-delay. Check the following items first before proceeding to the next step. - Gas valve turned off. - Manual shut-off valve. - Green/Yellow wire MUST be connected to furnace sheet metal. - Flame sensor must not be grounded. To determine whether the problem is in the gas valve, igniter, or flame sensor the system can be operated in the component test mode to check the igniter. First remove the R thermostat connection from the control and initiate the component test sequence. Does the igniter glow orange/white by the end of the 15 second warm-up period? 13 LIMIT CIRCUIT LOCKOUT – Lockout occurs if the limit or flame rollout switch is open longer than 3 minutes. Control will auto-reset after 3 hours. See code 33. Flame rollout switch requires manual reset. 22 ABNORMAL FLAME-PROVING SIGNAL Flame is proved while gas valve is deenergized. Inducer will run until fault is cleared. Check for: - Stuck open or leaky gas valve. 31 HIGH-HEAT PRESSURE SWITCH OR RELAY DID NOT CLOSE OR REOPENED - Check for: - Control relay may be defective. - Gas valve is miswired. - See status code 32. 24 SECONDARY VOLTAGE FUSE IS OPEN Check for: - Short circuit in secondary voltage (24V) wiring including thermostat leads. Disconnect thermostat leads to isolate short circuit. 23 PRESSURE SWITCH DID NOT OPEN Check for: - Obstructed pressure tube. - Pressure switch stuck closed. 21 GAS HEATING LOCKOUT – Turn off power and wait 5 minutes to retry. Check for: - Stuck closed gas valve relay on control. - Miswire or short to gas valve wire. 14 IGNITION LOCKOUT – System failed to ignite gas and prove flame in 4 attempts. Control will auto-reset after 3 hours. See status code 34. 12 BLOWER ON AFTER POWER UP – (115V OR 24V) – Normal operation. Blower runs for the selected blower offdelay, if unit is powered up during a call for heat (R-W/W1 closed) or when (RW/W1 opens) during the blower on-delay period. 32 LOW-HEAT PRESSURE SWITCH DID NOT CLOSE OR REOPENED – If open longer than 5 minutes, inducer shuts off for 15 minutes before retry. If opens during blower on-delay period, blower will come on for the selected blower offdelay. Check for: - Proper vent sizing. - Low inducer voltage (115V). - Low inlet gas pressure (if LGPS used). - Inadequate combustion air supply. - Disconnected or obstructed pressure tubing. - Defective inducer motor. - Defective pressure switch. - Excessive wind. - Restricted vent. 11 NO PREVIOUS CODE – Stored codes are erased after 72 hours. On RED LED boards stored status codes can also be erased whenever power (115V or 24V) is interrupted. Run system through a low-heat, high-heat, or cooling cycle to check system. YES NO Fixed. YES Will main burners ignite and stay on? YES Is current near typical value? Clean flame sensor with fine steel wool and recheck current. Nominal current is 4.0 to 6.0 microamps. YES Repeat call for heat and check flame sensor current during trial for ignition period. Is the DC microamps below 0.5? NO Do the main burners stay on? YES Do the main burners ignite? YES Does gas valve open and allow gas to flow? YES Reconnect the R thermostat lead and set thermostat to call for heat. Connect voltmeter across gas valve connections. Does gas valve receive 24V? Unplug igniter harness from control and initiate another component test sequence. Check for 115V between pin 1 and NEUTRAL-L2 on the control. Was 115V present for the 15 second period? 43 LOW-HEAT PRESSURE SWITCH OPEN WHILE HIGH-HEAT PRESSURE SWITCH IS CLOSED - Check for: - Low-heat pressure switch stuck open. - Disconnected or obstructed pressure tube. - Miswired pressure switches. - Low inlet gas pressure (if LGPS used). 352AAV NO NO NO YES NO NO NO YES NO Replace furnace control. Replace electrode. Check connections and retry. If current is near typical value (4.0-6.0 nominal) and burners will not stay on, repeat check in highheat. If burners will still not stay on replace control. If burners operate in high-heat then switch to low-heat, check manifold pressure. If OK, check burner carryover and flame sensor location. Allow blower to come on and repeat test to check for intermittent operation. Check for: - Inadequate flame carryover or rough ignition. - Low inlet gas pressure. - Proper firing rate. Check that all gas valves are turned on. Replace valve. Check connections. If OK, replace control. Check for continuity in the harness and igniter. Replace defective component. Replace furnace control. 45 CONTROL CIRCUITRY LOCKOUT Autoreset after 1 hour lockout due to: - Flame circuit failure. - Gas valve relay stuck open. - Software check error. Reset power to clear lockout. Replace control if code repeats.