Download Elnet GR - User Manual 02.05.10

Transcript
Elnet GR
Electrical Measurements & Power Quality
Table of Contents
CHAPTER 1
INTRODUCTION .......................................5
1.1
About the
Multimeter .................................5
1.2
How to use this manual ...........................................6
1.3
Safety Information ...................................................8
1.4
Warranty ..................................................................9
1.5
Your comments are welcome ................................. 11
1.6
Disclaimer ...............................................................12
CHAPTER 2 — INSTALLATION ......................................13
2.1
Contents of packaging ...........................................14
2.2
Mechanical mounting ............................................15
2.3
Wiring Schematics .................................................17
2.4
Rear Panel Connections ........................................18
2.5
Manufacturing Data. .............................................23
CHAPTER 3 — USING THE
3.1
Front Panel .............................................................24
3.2
Control Buttons ......................................................25
3.3
Lock Utility.............................................................26
CHAPTER 4 — NECESSARY
2
Multimeter .............24
SETTINGS ...........29
4.1
Settings for Current Transformer ........................30
4.2
Electrical Connection Check.................................35
4.3
TOU Setting............................................................37
4.4
Change language ....................................................38
4.5
Time Settings ..........................................................38
4.6
Date Settings...........................................................40
4.7
Zero Accumulating Values ....................................41
CHAPTER 5 — FRONT PANEL DISPLAYS ....................42
5.1
Current for 3 Phases ..............................................42
5.2
Frequency for 3 Phases ..........................................43
5.3
Current in Neutral Line ........................................44
5.4
Voltage for 3 Phases ...............................................46
5.5
Active Power for all 3 Phases (P) ..........................47
5.6
Reactive Power for all 3 Phases (Q) .....................49
5.7
Apparent Power for all 3 Phases (S) .....................50
5.8
Power Factor for each Phase.................................51
5.9
Overall Power Factor ............................................52
5.10
Active Energy ......................................................53
5.11
Reactive Energy ..................................................54
5.12
Apparent Energy ................................................55
5.13 Power Quality .....................................................56
5.13 .1 Wave Form Graphs ......................................56
5.13 .2 Harmonics Bar Graphs ................................61
5.13 .3 Voltage Total Harmonic Distortion (THD) .64
5.13 .4 Current Total Harmonic Distortion (THD) 65
3
5.13 .5
Current THD,TDD,KF .................................67
CHAPTER 6 — ALARM REPORT ....................................68
6.1.1.
Alarm setting.................................................69
6.1.2.
Display Alarms Report .................................71
CHAPTER 7 — DEMAND REPORTS ..............................72
CHAPTER 8 — DATA LOGGING .....................................73
CHAPTER 9 — COMMUNICATION................................76
9.1
Communication Connections ................................76
9.2 Communication Settings .......................................76
9.3 Address ................................................................77
9.4 Baud Rate ............................................................77
9.5 Parity ...................................................................78
9.6
Communication Set Up .........................................78
9.7
Communication with UniArt Software ................82
CHAPTER 10 — Specifications .........................................85
Appendix A — Installation & Configuration Check List ...86
4
CHAPTER 1
INTRODUCTION
1.1 About the
Multimeter
Large consumers of electricity e.g. factories, hotels, hospitals,
municipalities, need to know the history of their consumption and
the quality of the power supply. Details such as Voltage, Current,
Power Factor, Hertz, Neutral Current, Energy Demands and all
electricity related events are recorded in the
.
An additional feature of the Multimeter is the ability to measure
Harmonics. Part of the Electricity Supply Authority’s bill reflects
poor or good Harmonics in the consumer’s system, therefore it is
in his interest to monitor Harmonics and try to improve it.
These are all recorded on a continual basis and can be recalled
and shown on the front panel display of the instrument with a few
simple key-strokes any time the user wishes.
The
is a compact, multi
functional, three-phase Multimeter simple to install and is
especially designed to integrate into Building Management
Systems. It requires no special mounting and is ideally suited for
mounting on the front face of any standard electrical panel.
The Configuration and Setup is menu driven, with password
protection.
Communication with external devices is simple and is based on
standard known technology.
The
boasts a new
innovative built in “Flash Memory”, which pioneers a new
frontier into electrical measurement. It has a 1 MB of FLASH
5
MEMORY with a capacity of recording up to 2 years of power
malfunctions and interruptions.
Readings, graphs, tables & history are shown on the graphic
display of the
This
display is a state of the art screen with a resolution of 160X128.
Each
is carefully and
meticulously manufactured using quality components and the
latest production methods. Before leaving the factory each
is calibrated and sent to
the customer accompanied by the test certificate and Certificate of
Compliance (C.O.C).
1.2 How to use this manual
We at CONTROL APPLICATIONS Ltd, envisage this manual to
be used by three types of people, i.e. the Installation Technician,
the Senior Electrical Engineer and the end User. For this reason
this manual is divided into chapters for ease of reference by each
of these different people. There could be a situation where two of
the abovementioned tasks can be combined, or in a rare instance
one person could handle all three tasks.
CHAPTER 1, Introduction, describes the
its potential users, the readings it can
provide and some of its features in brief.
CHAPTER 2, Installation, provides detailed instructions for
unpacking, mechanical mounting, and electrical wiring up
instructions for the Installation Technician.
6
CHAPTER
3, Using the
, describes in detail front Panel, the functions of the
control buttons, and the Lock Utility.
CHAPTER 4, Parameter Configuration & Settings explains in
detail the minimum parameters settings needed by the Senior
Electrical Engineer to set up and configure the
.
CHAPTER 5, Front Panel Displays, is an easy to follow step-bystep guide to obtain readings, graphs, tables and histories for the
User.
CHAPTER 6, Alarm reports gives details about how to program
the Alarms in the
.
CHAPTER 7, Demand reports is an easy to follow step-by-step
guide to obtain the Demand reports up to 2 years.
CHAPTER 8, Data Logging is an easy to follow step-by-step
guide to obtain all the stored peaks of current, voltage, energy,
power factor etc. up to 2 years of data logging.
CHAPTER 9, Communications gives
Communication capabilities of the
, and how to Set Up.
details
about
the
CHAPTER 10, Specifications, is a detailed list of specifications of
.
the
APPENDIX A, Installation & Configuration Check List, provides
a Check List to insure no important steps will be missed during
the initial set up.
7
1.3 Safety Information
The purpose of this manual is to help you. Please read the
instructions carefully before performing any installation and note
any precautions.
WARNING
Ensure that all incoming AC power and other
power sources are turned off before
performing any work on the
Failure to
do so may result in serious or even fatal
injury and/or equipment damage.
If
the
is damaged in any way do NOT
connect it to any power source.
To prevent a potential fire or shock hazard,
never expose the
to rain or moisture.
Keep the surrounding area free of dirt and
clutter especially metal objects. Good
housekeeping pays.
Inspect the cables periodically for cracks,
kinks or any other signs of wear
Keep children away.
Do not pull the cords.
8
Users should stay alert and not approach the
rear of the
while tired or under the
influence of alcohol, medicines or any other
chemical substance that would tend to make a
person drowsy.
Do not wear loose clothing or dangling
jewelry.
Above all use common sense at all times.
1.4 Warranty
CONTROL APPLICATIONS Ltd provides a 12- Month warranty
against faulty workmanship or components from date of dispatch
provided that the product was properly installed and used.
CONTROL APPLICATIONS Ltd does not accept liability for any
damage that may be caused by natural disasters (such as floods,
fire, earthquake, lightening etc.).
CONTROL APPLICATIONS Ltd does not accept liability for any
damage that may be caused by malfunction of the
.
CONTROL APPLICATIONS Ltd will advise the customer on the
proper installation and use of the
but will not accept any responsibility that the
instrument is suitable for the application for which it was
originally purchased.
This warranty may become void if the Installation; Parameter
Configuration & Setting Instructions are not carried out according
to the instructions set out by CONTROL APPLICATIONS Ltd.
9
The
has no user
serviceable parts and should be opened and serviced by a duly
qualified authorized representative only. The sensitive electronics
could become damaged if exposed to a static environment. This
action would void the warranty.
This warranty is limited to the repair and/or replacement at
CONTROL APPLICATION Ltd sole discretion of the defective
product during the warranty period. Repaired or replaced products
are warranted for ninety (90) days from the date of repair or
replacement, or for the remainder of the original product’s
warranty period, whichever is longer.
CONTROL APPLICATIONS Ltd is always at your service to
advise the customer on any problem that may be encountered
regarding any installation, operation, parameter & configuration
settings or maintenance.
10
1.5 Your comments are welcome
CONTROL APPLICATIONS Ltd. sincerely thanks you for
choosing our
We are
confident that it will provide you with many years of trouble free
service and give you all the power and energy information and
history that you expected from the instrument when you bought it.
While every effort was made to keep the information as reliable,
helpful, accurate and up to date as possible, all possible
contingencies cannot be covered. Technical or typographical
errors could occur, and we would be happy to receive any
comments, criticisms or notifications of any such errors from you,
our valued customer.
Street Address:
Electronic Address:
24A HaBarzel St.
Tel-Aviv 69710
Israel
Tel: 972-3-647-4998
Fax: 972-3-647-4598
[email protected]
11
1.6 Disclaimer
Information in this User Manual is subject to change without
notice and does not represent a commitment on the part of
CONTROL APPLICATIONS Ltd.
CONTROL APPLICATIONS Ltd supplies this User Manual as is
without warranty of any kind; either expressed or implied, and
reserves the right to make improvements and/or changes in the
manual or the product at any time.
While it is the intention of CONTROL APPLICATIONS Ltd to
supply the customer with accurate and reliable information in this
User Manual, CONTROL APPLICATIONS Ltd assumes no
responsibility for its use, or for any infringement of rights of the
fourth parties which may result from its use.
This User Manual could contain technical or typographical errors
and changes are periodically made to the information herein;
these changes may be incorporated in new editions of the
publication.
12
CHAPTER 2 — INSTALLATION
In this Chapter you will find the information and instructions that
the Installation Technician needs to mount and connect the
WARNING!
During operation, hazardous voltages are
present in connecting cables and terminal
blocks.
Fully qualified personnel must do all work.
Failure to follow this rule may result in
serious or even fatal injury to personnel
and/or damage to equipment.
Refer to Section 1.3 Safety information before
carrying out any installation.
Read this manual thoroughly and make sure
you understand the contents before
connecting the
to any power source.
13
2.1 Contents of packaging
The
is packed and
shipped in a carton approximately 24.5 cm long X 19 cm wide X
12 and cm high.
Before opening the package, ensure the area, clean and dry.
Without using any sharp instruments, carefully open the carton of
the
Please check the contents of the carton, it should contain:
1. Your new
2.
3.
4.
5.
6.
7.
14
User
Manual (this book).
Test Certificate and Certificate of
Compliance (C.O.C).
A pair of Panel mounting clips.
1 X two pole connector plugs
1 X three pole connector plugs
3 X Four pole connector plugs
2.2 Mechanical mounting
To Mount the
NOTE!
!
Do not mount the
too close to any main electrical
conductors.
Allow sufficient space to carry
maintenance to the back of the
out
Choose a suitable location, and prepare a
rectangular hole according to the dimensions shown
in Figure 2.1
Width
138 mm
Height
138 mm
Figure 2.1. Panel Cutout
15
Slide the
into the pre-prepared rectangular
hole (ensure it is the right way up), then push
the two mounting clips provided in the
packaging into position. Use mild force to
ensure the clips are securely positioned on the
outer case of the
Tighten the two mounting screws and ensure
the
is firmly in place.
Figure 2.2. Mounting Clips
16
2.3 Wiring Schematics
To wire up the
Rear
Panel
Figure 2.3. Schematic Wiring Diagram
17
2.4 Rear Panel Connections
Please re-read section 1.3 for safety instructions.
To connect the Rear Panel
All Connections, except those to the CT core of the
are made via terminal connector
plugs (Voltage input, Power Supply, Communication etc.).
Max. recommended tightening torque for the connector screws is
0.5 Nm.
are
The CT cores of the
located externally on the rear of the instrument and the lead from
the leg of the external Current Transformer must pass through in
the correct direction.
NOTE!
!
Ensure all the connections to the leads of the current
transformer wiring are secure and there is no mechanical
strain on the wire. The cross section of the leads to the
current transformer must be compatible to the power of the
current transformer. We recommend a power transformer
with at least 3VA and the length of the wiring of the
transformer no longer than 3m.
18
Insert the lead from side “L” of the Current Transformers of Line
1 through the bottom of the CT core I1A, (top left looking from
back), of the
.
Ensure the leads from leg “L” of the Current
Transformer on Line 1 pass through the bottom of
CT core I1A.
Ensure the other end of the lead emerging from the
top of C T core I1A is connected to leg “K” of the
Current Transformer on Line 1
WARNING!
Never allow an open circuit between the two Current
Transformers.
WARNING
Repeat the procedure for Line 2 and Line 3.
19
Connect the rest of the connections to the
by means of terminal connector plugs.
The Rear Panel (See Figure 2.4.) has all connections printed and
is simple to follow. (See table 2-1 for connections)
Figure 2.4. Rear Panel
20
Pin
Designation
Description
Remarks
V1
Line1 Supplied
Voltage
Through a 6Amp fuse
V2
Line2 Supplied
Voltage
Through a 6Amp fuse
V3
Line3 Supplied
Voltage
Through a 6Amp fuse
N
Neutral
Measurement neutral Line
I1A
From Current
Transformer on
Line1
Note the correct direction to
insert the lead
I2A
From Current
Transformer on
Line2
Note the correct direction to
insert the lead
I3A
From Current
Transformer on
Line3
Note the correct direction to
insert the lead
Power Supply 110 - Or 110-260 VDC, external power
260 VAC
supply or bridged from phase
measurement
Np
Neutral
Dout
Alarms, see chapter
5.6.1
Din
Not in use
Neutral of external power supply
21
Pin
Designation
Description
RS485 — -
RS485 Comm. (-) Line
RS485 — +
RS485 Comm. (+) Line
RS232 — TXD
RS232 Comm. Transmit
RS232 — RXD
RS232 Comm. Receive
RS232 — COM
RS232 Comm. Common
RJ45
10 BASE-T line to
Network
Remarks
Via standard
Communications
plug
Table 2-1 Rear Panel connections
22
2.5 Manufacturing Data.
Press F1 on the keyboard for 6 seconds. The following screen will
appear.
Figure 2.5. Elnet Information
Number
Screen
Description
1
Ep. Date
Production date of software operating system
2
Ep. Time
No. of times the program has been updated
3
Version
Program version no.
4
Comm #
Address of MODBUS Protocol
5
Unit ID
Consecutive calibration no.
6
IP
Ethernet/IP address
7
MC
Ethernet/MAC address
Table 2-2 Production Data
23
CHAPTER 3 — USING THE
Multimeter
In this chapter you will find descriptions and functions of the
front panel and the control buttons and how to use them.
3.1 Front Panel
To operate the front panel
The Front Panel has a graphic screen and 6 operating buttons.
All the readings are shown on a state of the art 160 X 128
resolution graphic screen and are explained in detail in Chapter 5.
The Control Buttons and their functions are fully explained in
Section 3.2.
Figure 3.1. Front Panel
24
3.2 Control Buttons
To operate the Control Buttons on Front Panel
has six Control
The
Buttons. With these buttons the User and Senior Electrical
Engineer can achieve all the functions necessary.
The Control Buttons are arranged on a keypad below the display
screen and require slight finger pressure to click.
Figure 3.2. Control Buttons
Button
accepts the choice and executes the
commands.
Button
performs the function that the arrow
above is pointing to (e.g. move the
curser), or selects the prompt that the
arrow is pointing to.
25
Buttons
operate exactly the same as
button F1
Button
returns to the previous step or to the
Main Menu
3.3 Lock Utility
To lock and unlock the Control Buttons
The Control Buttons can be locked against any unauthorized or
accidental usage.
NOTE!
Only sub menus can be locked. The Lock Utility does
not work on the Main Menu.
26
To Lock press
for six (6) seconds.
A “Keyboard Locked!” message appears on the screen when any button
is pressed.
Figure 3.3. Keyboard locked
To Unlock simply press
for six (6) seconds.
A “Keyboard Unlocked!” message appears on the screen and
normal functions can resume.
27
Figure 3.4. Keyboard Unlocked
NOTE!
In the event of a general power failure, the
will return to
the screen that was showing before the power failure occurred.
28
CHAPTER 4 — NECESSARY
SETTINGS
In this chapter you will find instructions to set the minimum
settings that are necessary to allow the
to function properly.
WARNING!
The selection, installation and settings of the
Current Transformer are the most vital and
fundamental actions required to ensure the
accuracy of the
.
It is essential to know the ratio of the Current
Transformer being installed into the system in
order to set the parameter for the Current
Transformer correctly.
All three main current Lines MUST have
Current Transformers of the same ratio
installed onto them.
29
4.1 Settings for Current Transformer
To set or change settings for Current Transformer
NOTE!
The most important setting necessary for the proper
functioning of the
is the Current Transformer setting.
The cross section of the leads to the current Transformer
must be compatible to the power of the current
transformer. We recommend a power transformer with at
least 3VA and the length of the wiring of the transformer
no longer than 3m.
1
From Main Menu scroll to Technical Menu
2
Click
The Check Password screen appears
30
Figure 4.1. Check Password
NOTE!
The password is 1
3
Move the cursor with the F1, F2, F3, & F4 buttons to
number 1. (See Section 3.2 for description of button
functions).
4
Click
The number 1 will appear in the password field.
Figure 4.2. Password Field
31
5
Move the cursor to the # Sign with F1, F2, F3, & F4
buttons, (See Section 3-2 for description of button
functions).
If the incorrect password is inserted into the Password
field, an Error message appears
Figure 4.3. Error Message
Go back to step 3 and start again.
6
32
Click
The Technical Menu screen appears
Figure 4.4. Technical Menu
7
Scroll to Current Transformers
8
Click
The Current Transformer screen appears
Figure 4.5. Current Transformer
33
The present setting for the Current Transformer is shown.
If it is a new installation, the ratio will show 5 A:5 A
9
Click
The Insert Value screen appears
Figure 4.6. Insert Value
Use Button
or
to move the cursor.
Use Button
or
to change the value + or -.
10 To save Click
34
11 To cancel Click
4.2 Electrical Connection Check
NOTE!
To avoid any problems arising from incorrect Voltage
Connections or accidental reversal of Current
Transformer Connections, it is necessary to perform a
Phase Order Check before continuing.
To perform Electrical connection Check
See Section 4.1 for instructions to arrive at the Technical Menu
1
From Technical Menu scroll to Connection check
2
Click
The Connection Check screen appears
Figure 4.7. Connection Check
35
Voltage and Current Messages
Message
OK
Voltage
Current
Voltage “OK” present on Lines.
Current present in
If “OK” is not present on 3 Lines, Lines and synchronized
then its not connected correctly
with Voltage Lines. If
“OK” is not present on
3 Lines, then its not
connected correctly
OPP
NO
Wired in incorrect
direction
No Voltage
No current
Table 4-1 Voltage and Current Messages
Phase Order Messages
Message
Voltage
OK
Correct Phase Order of Voltage Connections
OPP
Incorrect Phase Order i.e. Line 2 does not follow Line 1
and/or Line 1 does not follow Line3
Table 4-2 Phase Order Messages
36
4.3 TOU Setting
is capable of working
in several TOU Settings. The user can choose the TOU Setting
according to the country requested.
To set TOU
See Section 4.1 for instructions to arrive at the Technical Menu
From Technical Menu scroll to TOU Setting
Click
The TOU Setting screen appears
Figure 4.8. TOU Setting
Then choose the relevant country by pressing the enter button on
its name.
37
4.4 Change language
To change language on the display screen
NOTE!
The “Change Language Utility” toggles between
English and Hebrew and works on the Main screen
only.
Click
for 6 seconds
4.5 Time Settings
To set Time
See Section 4.1 for instructions to arrive at the Technical Menu
From Technical Menu scroll to Set Clock
Click
38
The Set Clock screen appears
Figure 4.9. Set Clock
Use
Use
Click
Click
o
or
to select Hour, Minute, Second.
or
to change time.
to return to Technical menu.
to return to Main menu.
39
4.6 Date Settings
To set Date
See Sectio 4.1 for instructions to arrive at the Technical Menu
From Technical Menu scroll to Set Date
Click
The Set Date screen appears
Figure 4.10. Set Date
40
Use
or
to select Day, Month, Year.
Use
or
to change Day, Month, Year.
Click
to return to Technical menu.
Click
to return to Main menu.
4.7 Zero Accumulating Values
To set all accumulating values to Zero
1
2
Repeat step 1 and 2 from Section 4.1.
Move the cursor with the F1, F2, F3, & F4 buttons
(See Section 3.2 for description of button functions).
3
Insert 6425 into the password field.
4
Click #
41
CHAPTER 5 — FRONT PANEL DISPLAYS
In this chapter you will find instructions on how to obtain the
readings that the
provides, e.g., Current, Voltage Power, Power Factor, Energy, and
Power quality.
5.1 Current for 3 Phases
To display Current for all 3 Phases
1 From Main Menu scroll to Current & Voltage
2
Click
The Current screen appears
Figure 5.1. Current Display
3
42
Read the Current for Line1, Line2 and Line3
5.2 Frequency for 3 Phases
To display Frequency for all 3 Phases
1 Display the current screen as described in
section 5.1
2
Click
“ TABLE”
3
Click
“ FREQ”
The Frequency screen appears
Figure 5.2. Frequency for all 3 Phases
43
You can reset the Peak values by using the “CLEAR” button
Read the Frequency in Line 1, Line 2, Line3
5.3 Current in Neutral Line
By using the Vector value of L1/2/3 Current
calculates the Current in the Neutral Line
To display Current in the Neutral Line
NOTE!
If the reading for neutral line is “0” (i.e.
there is no current in the neutral line), then
either there is no current in system,
OR
the current for all three phases is balanced.
44
1
From Main Menu scroll to Current & Voltage
2
Click
3
The Current & Voltage screen appears as described
in section 5.1
4
Click
5
The Current & Voltage table screen appears
- “ TABLE”
Current in Neutral line
Figure 5.3. Combined Displays
Parameter
Description
Units
L1
L2
L3
L12
L23
L13
Voltage from Line1 to Neutral
Voltage from Line2 to Neutral
Voltage from Line3 to Neutral
Voltage across Line1 and Line2
Voltage across Line2 and Line3
Voltage across Line1 and Line3
Volts
Volts
Volts
Volts
Volts
Volts
Table 5-1 Voltage Readings
45
5.4 Voltage for 3 Phases
To display Voltage for all 3 Phases and across Phases
1
From the Main Menu scroll to Current & Voltage
2
Click
The Current & Voltage screen appears
Figure 5.4. Combined Displays
3
Click “VOLT”
The Voltage screen appears
46
5.5 Active Power for all 3 Phases (P)
To display Active Power for all 3 phases
1 From Main Menu scroll to Power Display
2
Click
The Active Power screen appears
Figure 5.5. Active power
To display Power Table
3 Click
Parameter
P
Q
S
P
Q
S
PF
Description
Unit
Active Power for each Line
Watts
Reactive Power for each Line
VAR
Apparent Power for each Line
VA
Total Active Power for all 3 Lines
Watts
Total Reactive Power for all 3 Lines VAR
Total Apparent Power for all 3 Lines VA
Power Factor
Table 5-2 Power Readings
47
NOTE!
Peak
is the highest value reached for the adjacent
reading since the
was first switched on,
OR
Since the last time the reset button was pressed.
Peak
is the lowest value reached for the adjacent
reading since the
was first switched on,
OR
Since the last time the reset button was pressed.
NOTE!
The “CLEAR” button resets the Peak
values only for the screen presently being
shown.
48
5.6 Reactive Power for all 3 Phases (Q)
To display Reactive Power for all 3 phases
1 From Main Menu scroll to Power Display
2
Click
The Power Table screen appears
Figure 5.6. Active Power
To display Reactive Power for all 3 phases in a single screen
3
Click
The Reactive Power screen appears
Refer to section 5.4 for
description of peaks.
The “CLEAR” button
resets the Peak values
Figure 5.7. Reactive Power
49
5.7 Apparent Power for all 3 Phases (S)
To display Apparent Power for all 3 phases
1 From Main Menu scroll to Power Display
2
Click
The Power Table screen appears
Figure 5.8. Power Table
To display Apparent Power for all 3 phases in a single screen
3
Click
Refer to section 5.4 for
description of peaks.
The “CLEAR” button
resets the Peak values
Figure 5.9. Apparent Power
50
5.8 Power Factor for each Phase
To display Power Factor for each phase
1 From Main Menu scroll to Power Display
2
Click
3
Click
to display “TABLE” format
The Power Table screen appears
Figure 5.10. Power Table
51
4
Click
The Power Factor for each Line screen appears
Figure 5.11. Power Factor for each line
5.9 Overall Power Factor
To display Overall Power Factor
1 From Main Menu scroll to Power Display
2
52
Click
and then click
The Power Table screen appears
Overall Power Factor
Figure 5.12. Power Table
5.10
Active Energy
To display Overall Active Energy
1 From Main Menu scroll to Energy Display
2
Click
The Energy Meter screen appears
Active Energy
Figure 5.13. Energy Meter
53
3 Read the Active Energy for Line1, Line2, Line3
To return to Main Menu
To return to Main Menu click
5.11
Reactive Energy
To display Overall Reactive Energy
1 From Main Menu scroll to Energy Display
Click
The Energy Meter screen appears
Reactive Energy
Figure 5.14. Energy Meter
2 Read the Reactive Energy for Line1, Line2, Line3
To return to Main Menu
3
54
To return to Main Menu click
5.12
Apparent Energy
To display Overall Apparent Energy
1 From Main Menu scroll to Energy Display
2
Click
The Energy Meter screen appears
Apparent Energy
Figure 5.15. Energy Meter
3 Read the Apparent Energy for Line1, Line2, Line3
To return to Main Menu
4
To return to Main Menu Click
55
5.13
Power Quality
NOTE!
Poor Harmonics could invoke a fine and damage to
the electrical system and can be improved by adding
filters.
The
GRAPHIC
Model is capable of displaying Harmonics in Wave Form Graph,
Harmonics Bar Graph, Harmonic Tables and Total Harmonic
Distortion for Voltage and Current.
5.13 .1 Wave Form Graphs
To display Wave Form Graphs
1. From Main Menu scroll to Power Quality
2. Click
The Power Quality screen appears
Figure 5.16. Power Quality
56
3. Scroll to Wave Form Graphs
4. Click
The Wave Form Graphs screens appear.
NOTE!
Available Wave Form Graphs
1. Volts
Line 1, Line 2 and Line 3
2. Current
Line 1, Line 2 and Line 3
3. Active Power
Line 1, Line 2 and Line 3
4. Reactive Power
Line 1, Line 2 and Line 3
5. Apparent Power
Line 1, Line 2 and Line 3
To display Voltage Wave Form Graphs
1. Click
The Voltage Graph screens appears
Figure 5.17. Voltage Graph
57
2. Press
to change Voltage Graph to Line 1,
Line 2 and
Line 3
To display Current Wave Form Graphs
1. Click
The Current Graph screens appears
Figure 5.18.Current Graph
2. Press
to change Current Graph to
Line 1, Line 2 and Line 3
58
To display Active Power Wave Form Graphs
1. Click
The Active Power Graph screens appears
Figure 5.19. Active Power Graph
2. Press
to change Active Power Graph to
Line 1, Line 2 and Line 3
59
To display Reactive Power Wave Form Graphs
1. Click
The Reactive Power Graph screens appears
Figure 5.20. Reactive Power Graph
2. Press
60
to change Reactive Power Graph
to Line 1, Line 2 and Line 3
To display Apparent Power Wave Form Graphs
1. Click
The Apparent Power Graph screens appears
Figure 5.21. Apparent Power Graph
to change Apparent Power Graph
2. Press
to Line 1, Line 2 and Line 3
5.13 .2 Harmonics Bar Graphs
To display Harmonics Bar Graphs
1. From Main Menu scroll to Power Quality Display
2. Click
61
The Power Quality screens appears
Figure 5.22. Power Quality
3. Scroll to Harmonic (Graphs)
4. Click
The Harmonics Volt Bar Graph screens appears
Figure 5.23. Harmonics Bar Graph
62
5. Press
to change Harmonics Volts Bar
Graph to Line 1, Line 2
and Line 3
NOTE!
1st Harmonics is normally 100%. If shown together with
the other Harmonics, distortion to the rest of the
Harmonic Bar Graph will occur. By toggling
,
the
are able
st
to separate 1 Harmonics to prevent this distortion.
To display Harmonics Current Bar Graph
Click
The Harmonic Current Bar Graph screens appears
Figure 5.24. Harmonic Current Bar Graph
63
5.13 .3 Voltage Total Harmonic
Distortion (THD)
NOTE!
The
is
capable of measuring Voltage and Current Harmonic
Distortion for the first 60th Harmonics. These are
presented in a table format with the Total Harmonics
Distortion (THD) also shown.
To display Harmonics Tables
1. From Main Menu scroll to Power Quality Display
2. Click
3. Scroll to Harmonic (Table)
4. Click
64
The Harmonics Volt Table screens appears
Figure 5.25. Harmonic Volt Table
5. Click
to scroll down the Table to observe
all Volt Harmonics till 60th
6. Click
to change Harmonics Volt Table to
Line 1, Line 2 and Line 3
5.13 .4 Current Total Harmonic
Distortion (THD)
To display Harmonics Current Table
Repeat steps 1-4 from Section 5.13.3
65
1. Click
The Harmonic Current Table screens appears
Figure 5.26. Harmonic Current Table
66
2. Click
to scroll down the Table to observe
all the Current Harmonics
till 60th
3. Click
to change Harmonics Current
Table to Line 1, Line 2 and
Line 3
5.13 .5 Current THD,TDD,KF
From Main Menu scroll to Power Quality Display and then scroll to
THD, TDD, KF Current.
The Current, THD, TDD, KF Table screens appears
Figure 5.27. Current THD, TDD, KF
In order to enable the system to calculate properly the TDD value, user
should set the max line current value by using “F4”.
67
CHAPTER 6 — ALARM REPORT
Every second automatically the
monitor all the electrical values and
compare them to the pre-setting alarm values.
The
can handle and store up to1,000 alarms that are stored in the
memory with their time & date data.
The
has three alarm relays each one of them can be linked to one or
more pre-defined alarms.
The following alarms can be defined:
Lines
1. Voltage alarms
L1; L2; L3
2. Current alarms
L1; L2; L3 + neutral line
3. Power factor alarms
L1; L2; L3 +General
4. Harmonics alarms
L1; L2; L3; L0
5. PEAK & SAG alarms
L1; L2; L3
Figure 6.1. Alarm Setting
68
For each one of the above alarms the user can define two alarms - low value
alarm and high value alarm.
The user can select one of sixteen different timers in order to delay each one
of the alarms.
6.1.1.
Alarm setting
See chapter No. 4.1 how to get in the Technical Menu from the main
screen.
From the Technical Menu select “Alarm setting” and press Enter. The
Alarm Setting Screens appear. (See figure 6.1).
From this screen you will be able to set alarms for Voltages, Currents
Power Factor, Harmonics, PEAK& SAG alarms and to set the values
for 16 delay timers that can be linked to each one of the alarms.
For each alarm the user can define:
High alarm – The set point that above that the alarm will be generated.
Low alarm – The set point that below that the alarm will be generated.
Delay timer – One of sixteen timers that define the time duration that
the alarm should be “ON” in order to be written in the memory.
Figure 6.2. Alarm user defines
69
Set Delay Timers:
Up to sixteen delay timers can be defined in the
Multimeter,
user can link for each one of the timer one or more alarms, the delay timer
will check that the alarm is stable and will not write the alarm in the memory
of the
unless the alarm is in “ON” position for the time duration
as set.
In order to set the time duration for the sixteen timers select “Set Delay
Timer” form the screen described in Figure 6.1. Alarm Setting
Screens the following screen appears.
Figure 6.3. Timer Delay
By using “T- / T+ “ (F2 / F3) the timer number can be changed.
By using “SEC “ (F4) the time delay value can be changed.
70
6.1.2.
Display Alarms Report
Two alarm reports can be generated:
Historical alarm report – includes all the information about fixed alarms
(return to normal status).
Current alarm report - includes all the information about existing alarms.
In order to generate an alarm report, from the Main Menu scroll to “Alarm
report “ and press enter, scroll to “ Historical Repot or Current report “ and
select one of them by using ( F3/F4) and press enter. A list of alrms appear –
Press “INFO” (F1) in order to get detailed information. The following screen
will appear:
Figure 6.4. Alarm Details
71
CHAPTER 7 — DEMAND REPORTS
Multimeter can generate reports that will inform the user the date of
the maximum demand. The reports include:
Maximum Demand – for active power and power factor.
Maximum Demand –for reactive power and power factor.
Maximum Demand – for apparent power and power factor.
Maximum Demand – for current and voltage.
The
informs the value of the demand and the relevant power factor,
the time. The date, for all three phases, the demand is the maximum value
within the predefine time interval specified by the user.
Press F1 in order to select I / PF - Current / power factor maximum Demand
Press F2 in order to select P / Q / S active / reactive / apparent power Demand
Press F4 n order to see the power factor together with the power demand
Press F3 “DATE” in order to change the time interval within which the
will check the maximum demand.
72
CHAPTER 8 — DATA LOGGING
multimeter collects automatically important electrical data day by
day, for approximately two years.
From the Main Menu scroll to “Data Logging “ and press Enter. The
following screen appears
Figure 8.1. Data Logging
Daily peaks :
Select Daily peaks and press Enter, then you will be able to get the following
information:
Figure 8.2. Daily Peaks
73
For each one of the above options you will have the ability to get for each
phase the lowest-level value and the highest-level value as specified in the
following screen:
Figure 8.3. Current Peaks
Select one of the above options and press Enter, the following screen will
appear:
Figure 8.4. Current Min. L1
F1 / F2 – change the interval - time base between week / month / 128 days
F3 /F4 – change the date, each press will increase / decrease the date by week
/ month / 128 days.
74
Power Demand :
The operation metod is very similar to the above paragraph “Daily peaks” and
the informatin includes the maximum average for 15 minutes of the active
power, reactive power and apparent power demand.
Total Energy :
The operation metod is very similar to the above paragraph “Daily peaks” and
the informatin includes the toatl energy values for active energy, reactive
energy and apparent energy for each phase and total energy.
Daily Energy :
The operation metod is very similar to the above pragraph “Daily peaks” and
the informatin daily energy consumption for active energy, reactive energy
and apparent energy for each phase and total energy.
Set Fast Trend :
Selecting Data logging form the screen described in Figure 8.1. will enable
you to set a trend report. The size of the trend report is 4200 samples of all
the measurements (currents, voltages, power, power factor and more for all
phases).
The user can set only the cycle time (sampling rate) and the range is from one
second up to 3600 seconds (one hour)
Figure 8.5. Set Fast Trend
75
CHAPTER 9 — COMMUNICATION
9.1
Communication Connections
The
supports RS232
and RS485. Connections for both are provided on the Rear Panel,
(see Figure 6.1) and are made by means of the connectors
provided. The same information can be transmitted along both,
but only one at a time. The user can choose the one that best suits
his current situation and equipment.
The 10 BASE-T sockets support a standard connection to any
Ethernet network.
Figure 9.1. Communication Connections
9.2 Communication Settings
To enable the User connecting the
to a PC master computer for successful
communications, the Communication Setup parameters of both
must match; i.e. the port of the PC master and the configuration
settings of the Power meter.
76
9.3
Address
Each Power meter in a communication system must have its own
unique address.
Since the
works on
MODBUS, the available addresses are from ‘1’ to ‘247’.
9.4
Baud Rate
The Baud Rate is the communication speed in Bits per second
(BPS) that the
communicates with the PC master. The better the communication
line Quality, the faster the communications may be.
If the communication line is routed through a “noisy”
environment, it may be necessary to decrease the Baud Rate.
Available Baud Rates for the
600
1200
2400
4800
9600
19200
bps
bps
bps
bps
bps
bps
77
9.5
Parity
The choices of parity are either NONE or EVEN (see section
6.1.1 for description of Parity).
9.6
Communication Set Up
To set up Serial Communications
See Section 4.1 for instructions to arrive at the Technical Menu.
From Technical Menu scroll to Communication Settings
1
Click
The Communication Setup screen appears
Figure 9.2. Communication Setup
78
From Communication Setup Menu scroll to Serial Comm.
2
Click
The Communications Settings screen appears
Figure 9.3. Communications Settings
Use Button
or
to select Address, Baud
Rate, Parity
Use Button
or
to change value in selected
field
79
NOTE!
When the selection is made it takes immediate affect
with no further action required.
Click
to return to Technical menu.
Click
to return to Main menu.
To set up Ethernet Communications
From the Communication Setup Menu scroll to Ethernet Comm.
1
80
Click
The Set IP Address screen appears
Figure 9.4. Set IP Address
Use Button
or
to move the cursor
Use Button
or
to change IP Address
81
9.7
Communication with UniArt
Software
CONTROL APPLICATIONS Ltd propriety software, “UniArt” is
used to Read and Write Registers of the
Each Item number in the Registers Table is
a unique field containing information. The UniArt software
manages each Item number as a parameter.
Refer to the UniArt manual how to set up parameters.
To read fields using UniArt
1
Find the reading required in the MODBUS Registers
Table
2
Note the Item Number from the Registers Table
3
Go to the correct File number
Because File capacity in UniArt is limited to 128
parameters, the information contained in the
is stored in several files.
File number is determined by the Item number
4
File # 0 contains
Item number
1 - 128
File # 1 contains
Item number
129 – 256
File # 2 contains
Item number
257 – 384
File # 3 contains
Item number
385 – 512
Go to the correct Point number within that file
Point number is determined by the formula:
Item number – [FILE X 128] = Point Number
82
fields
83
E.G. 1 If the user the wishes to read Voltage Line 2 (Item No 2)
By applying the formula: 2 - [0 X 128] = 2
File = 0 and Point within that file = 2
E.G. 2 If the user the wishes to read 30th Harmonics for Volts Line1
(Item No 330)
By applying the formula: 330 - [2 X 128] = 74
File = 2 and Point within that file = 74
E.G. 3 If the user the wishes to read 7th Harmonic for Current Line 3
(Item No 467)
By applying the formula: 467 - [3 X 128] = 83
File = 3 and Point number within that file = 83
More Examples
E.G. No
Item
No
Field Description
File
Point
1
2
3
4
5
6
7
8
9
2
330
467
128
129
256
257
384
385
Voltage Line 2
30th Harmonics for Volts Line1
7th Harmonic for Current Line 3
0
2
3
0
1
1
2
2
3
2
74
83
128
1
128
1
128
1
20th Harmonics for Volts Line 3
21st Harmonics for Volts Line3
Table 6-6 Examples how to calculate Point for UniArt
84
CHAPTER 10 — Specifications
Item
Description
Power requirements
110/230VAC,60/50 Hz, 30VA
Dimensions
(HxWxD) 144x144x100 mm
Shipping Weight
750 gr.
Measuring voltage limits
700 VAC
Measuring current limits
6A
Operating Voltage limits
1000VAC
Operating Current limits
50A
Enclosure material
ABS Anti flame
Display
Graphic 160x128
Operating temperature
-20 - + 50 C
Storage temperature
-20 - + 80 C
Humidity
0- 90 RH%
Voltage input terminals
VL – E10 1708
Communication port
RS232/ RS485/ 10 BASE -T
Mounting
Front Panel Mounting
All technical specifications are subject to change without notice.
85
Appendix A — Installation & Configuration
Check List
INSTALLATION CHECK LIST
Description
Date
Signature
Check contents of packaging
Remove from packaging
Prepare hole
Mount Multimeter
Connect Multimeter power supply
Connect 3 Current Transformers
Connect 3 Voltage lines
Connect Neutral line
Set Current Transformer Ratio
Connect Communication lines
Check Phase Order Connections
Set Time and Date
Appendix A Table - Installation & Configuration Check List
86