Download Appendix A
Transcript
202/1 202 Drive Fault Register (Continued) Btt: 6 Hex Value: 0040H Sug. Var. Name: FLT_FLD@ Range: N/A Access: Read Only UDC Error Code: 1006 LED: PM. FLT on the PMI Processor module Description: The Field Loss Fault bit will be set when: l 0 The field current feedback value is less than the Field Loss Trip Point parameter value entered during configuration for 5 times the electrical time constant of the field. This assumes FLD_RUN@ (register 100/1 100, bit 4) has been turned on. The field current feedback value dips below the Field Loss Trip Point parameter for 30 msec. after the field has been turned on. Bit: 7 Hex Value: 0080H Sug. Var. Name: FLT_TAC@ Range: N/A Access: Read Only UDC Error Code: 1007 LED: FDBK OK on the Resolver & Drive I/O module Description: The Speed Feedback Loss Fault bit is set when the motor’s CEMF is greater than 40% of the rated armature voltage value entered as a configuration parameter and the speed feedback signal is less than 5% of the motor base speed as entered as a configuration parameter. This bit is not used if the No Speed Feedback option is selected as a configuration parameter. Bit: 8 Hex Value: 01 OOH Sug. Var. Name: FLT_TBW@ Range: N/A Access: Read Only UDC Error Code: 1008 LED: FDBK OK on the Resolver & Drive l/O module Description: The Motor Speed Feedback Broken Wire Fault bit is set if a sine or cosine signal being used for speed or other application feedback is missing due to a broken wire or the resolver gain tunable (RES_GAN%) being set too low. This bit is always tested if a resolver is used. This bit is not set if No Speed Feedback is selected during parameter entry and register 101 /1 101, bit 10 is set. Refer to register 101/1 101, bit 10 for more information. Bit: 9 Hex Value: 0200H Sug. Var. Name: FLT_RES@ Range: N/A Access: Read Only UDC Error Code: 1009 LED: N/A Description: The Resolver Fault bit is set when a blown fuse is detected on the Resolver & Drive l/O module. 3-27