Download Programmable logic relays

Transcript
How to order
Order code
Power supply
Digital
Total n°
INPUTS
Digital/Analog (0-10VDC) ∂
n°
Base relay unit
LRD12R D024
24VDC
6
2
LRD12T D024
24VDC
6
2
LRD20R D024
24VDC
8
4
LRD20T D024
24VDC
8
4
LRD12R A024
24VAC
8
0
LRD20R A024
24VAC
12
0
LRD10R A240
100-240VAC
6
0
LRD20R A240
100-240VAC
12
0
Expansion and communication modules
LRE08R D024
24VDC
4
0
LRE08T D024
24VDC
4
0
LRE08R A024
24VAC
4
0
LRE08R A240
100-240VAC
4
0
LRE P00
Modbus® protocol communication unit
Accessories
LRX M00
Program backup memory
LRX C00
PC-LRD connecting cable, 1.5m long
LRX SW
Programming and supervision software (cd-rom)
LRX 1V3 D024
Power supply unit, 100-240VAC/24VDC, 1.3A
LRX D00
User’s manual Italian edition (paper)
LRX D01
User’s manual English edition (paper)
LRX D02
User’s manual Spanish edition (paper)
LRX D03
User’s manual French edition (paper)
Starter kits
LRDKIT 12R D024
LRD starter kit complete with LRD12R D024 relay, LRX SW software and LRX C00 cable
LRDKIT 12R A024
LRD starter kit complete with LRD12R A024 relay, LRX SW software and LRX C00 cable
LRDKIT 10R A240
LRD starter kit complete with LRD10R A240 relay, LRX SW software and LRX C00 cable
Digital
OUTPUTS
RTC
n°
Type
4
4
8
8
4
8
4
8
Relay
Transistor
Relay
Transistor
Relay
Relay
Relay
Relay
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
4
4
4
4
Relay
Transistor
Relay
Relay
No
No
No
No
Technical characteristics
Power supply
Rated utilisation voltage Ue (Frequency range)
Operating limits
Digital inputs
Rated voltage
State 0
Input voltage
State 1
0 to 1
Delay time
1 to 0
Analog inputs for 24VDC version only
Input signal range
Display resolution
Conversion
Current consumption at 10VDC
Input impedance
Admissible overload
Maximum cable length
Digital outputs
Type of output / Rated current Ith
Applied voltage
Ambient conditions
Operating / Storage temperature
Relative humidity
Maximum pollution degree
Housing
Version
Type of terminal
Conductor section
Connections
Tightening torque
Maximum cable length
LRD10… / LRD12…
Dimensions (wxhxd)
LRD20…
Expansions LRE…
Degree of protection
Certfications and compliance
Certfications obtained / Compliant with standards
∂ Digital inputs can be used as analog inputs.
LRD…D024
24VDC
20.4-28.8VDC
LRD…A024
24VAC
-
LRD…A240
100-240VAC (50-60Hz)
85-264VAC
24VDC
< 5VDC / < 0.625mA
> 15VDC / > 1.875mA
3-5ms
3-5ms
24VAC
< 6VAC
> 14VAC
5ms
5ms
110-220VAC
< 40VAC / < 0.28mA (LRD10R A240) < 0.15mA (LRD20R A240)
> 79VAC / > 0.41mA
45-50ms (Ue=100VAC) – 18-22ms (Ue=240VAC)
45-50ms (Ue=100VAC) – 85-90ms (Ue=240VAC)
0-10V
0.01V
10bits
< 0.17mA
< 1kΩ
28VDC
≤ 30m of screened type
LRD…R… / LRE08R…
Relay / 8A
12-240VAC / 12-125VDC
-
LRD…T… / LRE08T…
Transistor / 0.3A 24VDC
21.6-26.4VDC
-20…+55°C / -40…+70°C
20-90%, without condensation
2
Modular for mounting on 35mm DIN rail (IEC/EN 60715) or M4x15mm screw fixing
Screw
0.75-3.5mm2/ 12 AWG
0.4-0.6Nm/0.3-0.4lbft
≤ 100m
72x106x57.3mm
126x106x57.3mm
38x106x57.3mm
IP20
cULus / IEC/EN 61131-2