Download Programmable logic relays
Transcript
How to order Order code Power supply Digital Total n° INPUTS Digital/Analog (0-10VDC) ∂ n° Base relay unit LRD12R D024 24VDC 6 2 LRD12T D024 24VDC 6 2 LRD20R D024 24VDC 8 4 LRD20T D024 24VDC 8 4 LRD12R A024 24VAC 8 0 LRD20R A024 24VAC 12 0 LRD10R A240 100-240VAC 6 0 LRD20R A240 100-240VAC 12 0 Expansion and communication modules LRE08R D024 24VDC 4 0 LRE08T D024 24VDC 4 0 LRE08R A024 24VAC 4 0 LRE08R A240 100-240VAC 4 0 LRE P00 Modbus® protocol communication unit Accessories LRX M00 Program backup memory LRX C00 PC-LRD connecting cable, 1.5m long LRX SW Programming and supervision software (cd-rom) LRX 1V3 D024 Power supply unit, 100-240VAC/24VDC, 1.3A LRX D00 User’s manual Italian edition (paper) LRX D01 User’s manual English edition (paper) LRX D02 User’s manual Spanish edition (paper) LRX D03 User’s manual French edition (paper) Starter kits LRDKIT 12R D024 LRD starter kit complete with LRD12R D024 relay, LRX SW software and LRX C00 cable LRDKIT 12R A024 LRD starter kit complete with LRD12R A024 relay, LRX SW software and LRX C00 cable LRDKIT 10R A240 LRD starter kit complete with LRD10R A240 relay, LRX SW software and LRX C00 cable Digital OUTPUTS RTC n° Type 4 4 8 8 4 8 4 8 Relay Transistor Relay Transistor Relay Relay Relay Relay Yes Yes Yes Yes Yes Yes Yes Yes 4 4 4 4 Relay Transistor Relay Relay No No No No Technical characteristics Power supply Rated utilisation voltage Ue (Frequency range) Operating limits Digital inputs Rated voltage State 0 Input voltage State 1 0 to 1 Delay time 1 to 0 Analog inputs for 24VDC version only Input signal range Display resolution Conversion Current consumption at 10VDC Input impedance Admissible overload Maximum cable length Digital outputs Type of output / Rated current Ith Applied voltage Ambient conditions Operating / Storage temperature Relative humidity Maximum pollution degree Housing Version Type of terminal Conductor section Connections Tightening torque Maximum cable length LRD10… / LRD12… Dimensions (wxhxd) LRD20… Expansions LRE… Degree of protection Certfications and compliance Certfications obtained / Compliant with standards ∂ Digital inputs can be used as analog inputs. LRD…D024 24VDC 20.4-28.8VDC LRD…A024 24VAC - LRD…A240 100-240VAC (50-60Hz) 85-264VAC 24VDC < 5VDC / < 0.625mA > 15VDC / > 1.875mA 3-5ms 3-5ms 24VAC < 6VAC > 14VAC 5ms 5ms 110-220VAC < 40VAC / < 0.28mA (LRD10R A240) < 0.15mA (LRD20R A240) > 79VAC / > 0.41mA 45-50ms (Ue=100VAC) – 18-22ms (Ue=240VAC) 45-50ms (Ue=100VAC) – 85-90ms (Ue=240VAC) 0-10V 0.01V 10bits < 0.17mA < 1kΩ 28VDC ≤ 30m of screened type LRD…R… / LRE08R… Relay / 8A 12-240VAC / 12-125VDC - LRD…T… / LRE08T… Transistor / 0.3A 24VDC 21.6-26.4VDC -20…+55°C / -40…+70°C 20-90%, without condensation 2 Modular for mounting on 35mm DIN rail (IEC/EN 60715) or M4x15mm screw fixing Screw 0.75-3.5mm2/ 12 AWG 0.4-0.6Nm/0.3-0.4lbft ≤ 100m 72x106x57.3mm 126x106x57.3mm 38x106x57.3mm IP20 cULus / IEC/EN 61131-2