7:3 List of disposable parameters
A list of all disposable PSE18...370 parameters is available in table 7.1.
Rated Current of motor Ie
Setting range
Individual
See tables in
chapter 3:7.3
PSE Softstarter
types. Setting
range is 30-100
percent of Ie
1...30 s
Start Ramp time
Default
value
Access
from
Fieldbus
Display
symbol
HMI
Description
Parameter
transfer with
External Keypad
Table 7.1
Individual
W
W
10 s
W
W
T
Stop Ramp time
OFF, 1...30 s
OFF
W
W
T
Initial/End Voltage
30...70 %
40 %
W
W
T
Current limit
1.5 x 7 Ie
7.0 x Ie
W
W
T
Torque Control during start ramp
OFF/On
OFF
W
W
T
Torque Control during stop ramp
OFF/On
On
W
W
T
OFF, 30...100 %
OFF
W
W
T
Kick Start
Electronic Motor Overload Protection
(EOL)
Actual setting
T
Tripping Class (EOL)
OFF, 10 A, 10,
20, 30
Type of operation (EOL)
HAnd/Auto
1
10
W
W
T
HAnd
W
W
T
R = Readable
W = Writeable
T = Will be transferred (uploaded/downloaded)
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
Chapter 7
57