Technical Data
POINT I/O
1734 Series
42003
About POINT I/O
POINT I/OTM is a family of modular input/output modules. This
solution allows you to precisely specify the right amount of I/O for
your application needs, thus increasing your flexibility and reducing
installation costs.
The POINT I/O system is ideal for industries where flexibility and low
cost-of-ownership are key to successful control system design and
operation.
How the POINT I/O
System Works
The POINT I/O modules and Removable Terminal Blocks (RTBs)
operate independently allowing for simplified installation and
commissioning. The latching device on the Removable Terminal
Blocks (RTBs) keeps the I/O assembly into place as indicated by the
audible “click” sound.
I/O Module
Removable Terminal
Block (RTB)
Mounting Base
42002
For a detailed description of each of these components, refer to the
table on page 3.
2 Overview
POINT I/O
Overview
POINT I/O Features and
Benefits
• Just-what-you-need granularity reduces system size and cost.
• Network options provide a variety of control system solutions.
• Bidirectional bus interconnect system improves reliable power
and communication pass-through.
• DIN-rail disconnect system allows you to vertically remove
components without interrupting adjacent components.
• Mechanical keying for field-side protection allows you to
prevent incorrect module insertion into a preconfigured terminal
base.
• Electronic module ID allows for system-side protection.
• Remove cartridge and terminations independently without
interrupting communications on the network.
• Light-gray terminals facilitate visual inspection and verification.
• You can pre-assemble the system and then mount it as a unit on
the DIN-rail.
• Removable termination facilitates system installation,
commissioning, and maintenance.
• You can mount the system vertically or horizontally, allowing for
“real-world” installation.
What this Product Data
Contains
Use the following table to find product information in this document.
For Information On
Description
POINT I/O System
Overview of the POINT I/O System
3
Communication Adapter
DeviceNet Adapter (Cat. No. 1734-ADN)
12
Communication Interface
DeviceNet Interface (Cat. No. 1734-PDN)
14
Communication Adapter
PROFIBUS Adapter (Cat. No. 1734-APB)
15
1734D Series
1734D Series 24V dc 8 In/8 Out Combo Module (Cat. No. 1734D-IB8XOB8E, -IB8XOB8ES)
17
1734D Series 24V dc 8 In/8 N.O. Relay Combo Module (Cat. No. 1734D-IB8XOW8, -IB8XOW8S)
19
1734D Series 120V ac 8 In/8 Out Combo Module (Cat. No. 1734D-IA8XOA8, -IA8XOA8S)
21
1734D Series 120V ac 8 In/8 N.O. Relay Combo Module (Cat. No. 1734D-IA8XOW8, -IA8XOW8S)
23
The mounting base (1734-MB) and Removable Terminal Blocks (1734-RTB or -RTBS) are sold
together as wiring assemblies under the catalog number 1734-TB (screw clamp terminations) and
1734-TBS (spring clamp terminations).
26
Wiring Base Assembly with 12 Screw-Clamp or Spring-Clamp Removable Terminal Blocks (Cat
Nos. 1734-TB3, -TB3S)
27
120V ac 2 Input Module (Cat. No. 1734-IA2)
29
120/220V ac 2 Output Module (Cat. No. 1734-OA2)
30
220V ac 2 Input Module (Cat. No. 1734-IM2)
31
Wiring Base Assemblies
AC Modules
Publication 1734-TD002B-EN-P - January 2001
See Page
POINT I/O
Overview 3
DC Modules
24V dc 2 Input Sink Module (Cat. No. 1734-IB2)
33
24V dc 4 Input Sink Module (Cat. No. 1734-IB4)
34
24V dc 2 Input Source Module (Cat. No. 1734-IV2)
35
24V dc 4 Input Source Module (Cat. No. 1734-IV4)
36
24V dc Electronically Protected 2 Point Output Module (Cat. No. 1734-OB2E)
37
24V dc Electronically Protected 4 Point Output Module (Cat. No. 1734-0B4E)
38
24V dc Analog 2 Current Input Module (Cat. No. 1734-IE2C/B)
40
24Vdc Analog 2 Current Output Module (Cat. No. 1734-OE2C/B)
41
24V Encoder/Counter Module (Cat. No. 1734-IK)
43
5V Encoder/Counter Module (Cat. No. 1734-IJ)
44
24V dc Very High Speed Counter Module (Cat. No. 1734-VHSC24)
45
5V dc Very High Speed Counter Module (Cat. No. 1734-VHSC5)
47
Relay Module
24V dc, 120V ac, and 240V ac 2 Relay Sink/Source Output Module (Cat. No. 1734-OW2)
49
Field Power Distributor
Field Power Distributor (Cat. No. 1734-FPD)
52
Expansion Power Supply
24V dc Expansion Power Supply (Cat. No. 1734-EP24DC)
55
Related Publications and
Mounting Dimensions
Related Publications and Mounting Dimensions
56
Analog Modules
Counter Modules
Understanding the
System Design
The POINT I/O system consists of four main components.
I/O module
Removable Terminal
Block (RTB)
communication adapter
42003
wiring base assembly
For Information On
See Page
• Communication
Interfaces
4
• Mounting Bases
6
41973
42005
Publication 1734-TD002B-EN-P - January 2001
4 Overview
POINT I/O
• Wiring Assembly with
Removable Terminal
Blocks (RTBs)
6
• I/O Modules
7
42006
42007
The POINT I/O system also has an optional component.
For Information On
See Page
• Expansion Power Unit
9
• Field Power Distributor
8
42008
42012
Communication Interfaces
POINT I/O communication interfaces provide the interface between a
fieldbus network and the POINT I/O backplane (PointBusTM). POINT
I/O has three classes of fieldbus interfaces: an adapter (1734-ADN), a
low-cost communication interface (1734-PDN), and an interface with
integrated I/O (1734D Series).
POINT I/O modules attach to the DeviceNet network using round
media. Each adapter interfaces the POINT I/O backplane with the
DeviceNet network and supplies 5V logic power to the I/O modules.
Publication 1734-TD002B-EN-P - January 2001
POINT I/O
Overview 5
Refer to the sections on the 1734-EP24DC expansion power unit and
1734-FPD field potential distributor for more information on how they
expand the backplane to support up to 64 modules.
• a DeviceNet adapter (1734-ADN)
42009
The 1734-ADN DeviceNet adapter collects I/O data from up to
64 modules via the I/O backplane. This data is presented to the
scanner module located on the DeviceNet network allowing the
I/O modules to appear on DeviceNet as one node, requiring
only one DeviceNet node address. The 1734-ADN provides an
isolated dc/dc converter between field 24V dc and PointBus 5V.
You can connect up to 12 modules to each 1734-ADN (with a
maximum of 10A of field power) before using the integrated,
isolated 24V dc expansion power unit (refer to the 1734-EPDC24
section on page 9) to provide expansion power to both digital
and analog modules.
• a low-cost communication interface (1734-PDN)
This low-cost DeviceNet interface is not seen as a node on the
DeviceNet network, yet each module attached to this adapter is
viewed as a separate node. The backplane power is derived
from the DeviceNet network and is not isolated.
41973
You can connect up to 12 modules to each 1734-PDN with a
maximum of 10A of field power. Refer to the 1734-FPD section
on page 8 for logical and partitioning examples.
• an interface with integrated I/O (1734D Series)
The 1734D Series functions as a 1734-PDN adapter, but can
communicate on the network as a module since it also contains
I/O. For this reason, the POINT Block Family of Products is seen
as a non-isolated node on the DeviceNet network and each
module attached to this adapter is viewed as a separate node.
42057
TIP
You will need to address I/O modules used with the
1734-PDN and the 1734D Series interfaces as
individual nodes on the DeviceNet network. You can
do this by using Sequential Auto Addressing (SAA) or
node commissioning. For a brief description, see
page 11. For more detailed information, refer to the
POINT I/O User Manual, publication
1734-UM001A-EN-P.
Publication 1734-TD002B-EN-P - January 2001
6 Overview
POINT I/O
Mounting Base
Overview
The POINT I/O system follows a “No Tools” design approach. The
mounting base (1734-MB), I/O module, and Removable Terminal
Block (1734-RTB) may be assembled as a system without tools. The
POINT I/O mounting base, following this “No Tools” model, mounts
directly on the DIN-rail either vertically or horizontally.
42005
The mounting base provides the mounting locations for the I/O
modules and the Removable Terminal Blocks (RTBs). The mounting
base also forms the interconnect for the I/O backplane
communication and field power distribution.
Additional features of the mounting base include:
• 60µ−in gold-plated, card-edge contacts for long-term reliability
• DIN-rail mount/lock/unlock - color-coded on the top and
bottom
• bidirectional bus interface creates a reliable connection
• field power and chassis ground (via DIN rail) interconnect
• mechanical keying prevents incorrect module placement
• color-coded mechanical features for visual inspection
Removable Terminal Blocks (RTB)
The Removable Terminal Blocks (RTBs) provide eight or twelve
separate terminal locations for you to connect field wiring. They also
provide you with vertical access to wire and screw terminations. Each
terminal is numbered and a separate terminal point is provided for
each wire, including a shield ground terminal point for 2-point analog
modules.
42053
The RTB also follows the “No Tools” design approach. Once the RTB
is wired properly, you never need to touch the screws. These RTBs
separate independently of the base and I/O module to facilitate rapid
installation and commissioning of the system, whether it’s one loop or
one sub-system at a time. You can pivot the RTB into place or insert it
vertically.
Each terminal is numbered on the bottom of the RTB to simplify
troubleshooting during commissioning or maintenance cycles.
TIP
42006
Publication 1734-TD002B-EN-P - January 2001
The mounting base (1734-MB) and Removable
Terminal Blocks (1734-RTB or -RTBS) are sold
together under the catalog number 1734-TB or -TB3
(screw clamp terminations) and 1734-TBS or -TB3S
(spring clamp terminations).
POINT I/O
Overview 7
I/O Modules
POINT I/O modules convert field device signals into control status
indicators. To facilitate installation, commissioning, and maintenance,
you can Remove and Insert Under Power (RIUP).
42007
ATTENTION
!
Remove field-side power before removing or
inserting modules. Modules are designed so you can
remove and insert them under backplane power.
When you remove or insert a module while
field-side power is applied, you may cause an
electrical arc. An electrical arc can cause personal
injury or property damage because it may:
• send an erroneous signal to your system’s field
devices causing unintended machine motion
• cause an explosion in a hazardous environment
Repeated electrical arcing causes excessive wear to
the contacts on both the module and its mating
connector. Worn contacts may create electrical
resistance.
POINT I/O modules provide a variety of LED indicators:
• module status
• network status
• power indication
• calibration status
• I/O point status (ON/OFF/fault or diagnostic)
Refer to each module’s product page later in this document for
detailed information.
About the POINT I/O Modules’ Diagnostics
All status and diagnostic information (strobed, polled, cyclic, or
change-of-state) is reported back over the network communication
adapter. A single point of failure is detected and reported at the
module and to the control system.
Point Level Diagnostics
Module Status
Network Status
Node Level Diagnostics
• Module Status Indicator
indicates the health of the
module
• Network Status Indicator
indicates the health of the
PointBus or backplane
• I/O Point Indicator
indicates I/O (ON/OFF or
fault/diagnostic) status
• Digital outputs
Short circuit for ON-state
Open circuit for OFF-state
• Analog I/O
Loss of field power
Open wire
Calibration status
I/O Channel Status
42011
Publication 1734-TD002B-EN-P - January 2001
8 Overview
POINT I/O
Power Supplies and Power
Distribution
Power units may be divided into three categories:
• Power Supply
The power supply transforms and/or rectifies one field voltage
level to a different field voltage level.
• Field Power Distributor
The field power distributor allows you to convert your field
power so that you may have a broad range of voltage inputs in
your 12 module system. This range of voltage inputs includes 5V
dc to 250V dc and/or 24V ac to 240V ac applications and I/O
modules.
• Expansion Power Unit
The expansion power unit provides an additional +5V
backplane power so you can add up to 12 more modules to
your system. This power unit continues to pass data
communication to the modules you add to your system.
Power Supply
The 1794-PS13 power supply from the FLEX I/O family of products
may be used with POINT I/O to supply 24V dc to the 1734-FPD field
power distributor.
Field Power Distributor
42012
The 1734-FPD field power distributor passes through all POINT I/O
backplane signals, but does not provide additional backplane power.
The field power distributor gives you the ability to change the field
power distribution source for I/O modules to the right of the
1734-FPD field power distributor. This facilitates logical or functional
partitioning of low-channel count, high I/O-mix applications using the
1734-PDN and 1734D Series communication interfaces.
You can use the 1734-FPD field power distributor with a broad range
of voltage inputs including 5V dc to 250V dc and/or 24V ac to 240V ac
applications and I/O modules.
Publication 1734-TD002B-EN-P - January 2001
POINT I/O
Overview 9
Expansion Power Unit
42008
The 1734-EP24DC expansion power unit passes 24V dc field power to
the I/O modules to the right of it. This unit extends the backplane bus
power and creates a new field voltage partition segment for driving
field devices for up to 12 I/O modules. The expansion power unit
separates field power from I/O modules to the left of the unit,
effectively providing functional and logical partitioning for:
•
•
•
•
separates field power between input and output modules
separating field power to the analog and digital modules
grouping modules to perform a specific task or function
dark-gray color for easy visual inspection and identification
You can use multiple expansion power units with the 1734-ADN
adapter to assemble a full system. For instance, if you are using the
1734-ADN adapter, you may use a 1734-EP24DC expansion power
unit to add additional modules in 12 module increments. For example,
if you had a 36 module system with a 1734-ADN adapter, you would
have two 1734-EP24DC expansion power units to provide more
PointBus current for modules to the right of the supply.
ATTENTION
You can only use the 1734-EP24DC expansion power
unit with the 1734-ADN adapter.
!
Publication 1734-TD002B-EN-P - January 2001
10 Overview
POINT I/O
Wiring POINT I/O Modules
to the Terminal Base Unit
The 1734-TB and -TBS terminal base units provide one location for
every wire you need to connect to a two-POINT module. The
1734-TB3 and -TB3S terminal base units provide a location for every
wire you need to connect a three-point module
0
2
1
Ch 0
Ch 1
Ch 2
Ch 3
C
C
4
0
1
Ch 0
Ch 1
Ch 2
Ch 3
C
C
2
3
3
4
5
5
6
6
7
V
7
V
V
41975
V
8
9
C
C
10
11
V
V
42696
Module Termination Function
Terminal
Number
IA2
0
In 0
Out 0
In 0
In 0
In 0
In 0
In 0
Out 0
Out 0
In 0
Out 0
A
1
In 1
Out 1
In 1
In 1
In 1
In 1
In 1
Out 1
Out 1
In 1
Out 1
2
NC
NC
NC
NC
In 2
NC
In 2
Out 0
Out 2
Chass
Gnd
3
NC
NC
NC
NC
In 3
NC
In 3
Out 1
Out 3
4
L2/N
L2/N
L2/N
C
C
C
C
C
5
L2/N
L2/N
L2/N
C
C
C
C
6
L1
L1
L1
V
V
V
7
L1
L1
L1
V
V
V
1
OA2
IM2
IB2
IB4
IV2
IV4
OB2E
OB4E
IE2C
OE2C
IK
IJ
VHSC24
VHSC5
Mod 1
Mod 2
Mod 1
Mod 2
A
A
Chas
Gnd
A
Chas
Gnd
Out 0
A
Aret
Aret
Aret
Chas
Gnd
Aret
Chas
Gnd
Out 1
A
Chass
Gnd
B
B
B
Ret 0
B
Ret 0
Out 0
B
Chass
Gnd
Chass
Gnd
Bret
Bret
Bret
Ret 1
Bret
Ret 1
Out 1
B
C
C
C
Z
Z
Z
-Vaux
Z
-Vaux
C or
L2/N
C
C
C
C
Zret
Zret
Zret
-Vaux
Zret
-Vaux
C or
L2/N
V
V
C
V
V
Chass
Gnd
Chass
Gnd
Out 0
+Vaux
Out 0
+Vaux
V or L1
V
V
C
V
V
Chass
Gnd
Chass
Gnd
Out 1
+Vaux
Out 1
+Vaux
V or L1
Relay contacts are not connected to the field power bus.
V = 24V dc = Supply C = Common = DC Return
-Vaux and +Vaux = Auxiliary Supply
NC = No Connection
Configuring POINT I/O
Modules
Chass Gnd = Chassis Ground L1 = AC Power
L2/N = AC Return/Neutral
Aret, Bret, and Cret = Inputs
Configuring POINT I/O modules is as easy as POINT and click.
RSNetWorxTM allows you to simply ID the network and configure the
I/O modules with easy-to-use Electronic Data Sheet (EDS) files - just
POINT to the field and click on your selection.
To obtain EDS files for use in configuration, go to:
http://www.ab.com/networks/eds
Publication 1734-TD002B-EN-P - January 2001
OW21
POINT I/O
Communication Interface’s Table of Contents 11
Communication Interface’s Table of Contents
Use the following table to determine which communication
interface will meet your application needs.
See Page
Interface
Purpose
1734-ADN
DeviceNet Adapter (Cat. No. 1734-ADN)
12
1734-PDN
DeviceNet Interface (Cat. No. 1734-PDN)
14
1734-APB
PROFIBUS Adapter (Cat. No. 1734-APB)
15
1734D-IB8XOB8E,
-IB8XOB8ES
1734D Series 24V dc 8 In/8 Out Combo Module
(Cat. No. 1734D-IB8XOB8E, -IB8XOB8ES)
17
1734D-IB8XOW8,
-IB8XOW8S
1734D Series 24V dc 8 In/8 N.O. Relay Combo
Module (Cat. No. 1734D-IB8XOW8,
-IB8XOW8S)
19
1734D-IA8XOA8,
-IA8XOA8S
1734D Series 120V ac 8 In/8 Out Combo
Module (Cat. No. 1734D-IA8XOA8, -IA8XOA8S)
21
1734D-IA8XOW8,
-IA8XOW8S
1734D Series 120V ac 8 In/8 N.O. Relay Combo
Module (Cat. No. 1734D-IA8XOW8,
-IA8XOW8S)
23
Understanding Sequential Auto Addressing (SAA)
and Node Commissioning
When using I/O modules with the 1734-ADN, 1734-PDN, and the
1734D Series interfaces, you will need to address the modules as
individual nodes on the DeviceNet network. You can do this by
using:
•Node Commissioning
Node commissioning allows you to assign the node address
for individual devices. This is done one device at a time.
•Sequential Auto Addressing (SAA)
Sequential Auto Addressing allows you to commission
multiple nodes at one time. Used in conjunction with EDS
files, you assign the first node with a node address and the
SAA function will automatically assign node addresses to the
remaining nodes.
For more information, refer to the POINT I/O User Manual,
publication 1734-UM001A-EN-P.
Publication 1734-TD002B-EN-P - January 2001
12 DeviceNet Adapter (Cat. No. 1734-ADN)
POINT I/O
1734-ADN DeviceNet Adapter
Specifications - 1734-ADN DeviceNet Adapter Module
Communication Interface Specifications
DeviceNet Adapter (Cat. No. 1734-ADN)
Expansion I/O Capacity
12 modules (Note: Total expansion up to 63
modules - 12 modules with 1734-ADN - add
1734-EP24DC modules for additional 12 modules
for each additional EP24 up to 63 module
maximum)
DeviceNet Communication
Rate
125K bit/s (500m maximum)
250K bit/s (250m maximum)
500K bit/s (100m maximum)
DeviceNet Cable
Allen-Bradley part number 1485C-P1-Cxxx
Refer to publication DN-2.5 for more information
Module Location
Starter module - left side of 1734 system
Adapter Status
Adapter
Status
DeviceNet
Status
DeviceNet Status
PointBus Status
PointBus
Status
1734-ADN
System Power
System
Power
Field
Power
Field Power
DeviceNet Power Specifications
Power Supply
NC
NC
Chas Gnd
Chas Gnd
C
C
V
V
NC = No ConnectionChas Gnd = Chassis Ground
C = CommonV = Supply
41970
Input Voltage Rating
24V dc nominal
DeviceNet Input Voltage
Range
11-25V dc DeviceNet specification
Input Overvoltage Protection
Reverse polarity protected
DeviceNet Power
Requirements
24V dc (+4% = 25V dc max) @ 30mA maximum
Power Supply Specifications
Power Supply
Note: In order to comply with CE Low Voltage
Directives (LVD), you must use a Safety Extra Low
Voltage (SELV) or a Protected Extra Low Voltage
(PELV) power supply to power this adapter.
Input Voltage Rating
24V dc nominal
10-28.8V dc range
Field Side Power
Requirements
24V dc (+20% = 28.8V dc maximum) @ 400mA
maximum
Wiring
12/24V dc
Power
0
1
NC
NC
2
Do not connect 120/240V ac
power to this supply.
3
Chass Chass
Gnd Gnd
4
5
C
V dc
6
7
V
NC = No Connection
C = Common
DeviceNet
connection
C
This dc supply will be
connected to the
internal power bus.
V
Chas Gnd = Chassis Ground
V = Supply
Black
-V
Blue
CAN - Low
Bare
Shield
White
CAN - High
Red
+V
Publication 1734-TD002B-EN-P - January 2001
30880
42065
Note: In order to comply with CE Low Voltage
Directives (LVD), you must use a Safety Extra Low
Voltage (SELV) or a Protected Extra Low Voltage
(PELV) power supply to power this adapter.
Inrush Current
6A maximum for 10ms
PointBus Output Current
1A maximum @ 5V dc ±5% (4.75 - 5.25)
Input Overvoltage Protection
Reverse polarity protected
Interruption
Output voltage will stay within specifications when
input drops out for 10ms at 10V with maximum
load.
POINT I/O
DeviceNet Adapter (Cat. No. 1734-ADN) 13
General Specifications
Indicators
3 red/green status indicators
Adapter status
DeviceNet status
PointBus status
2 green power supply status indicators:
System Power (PointBus 5V power)
Field Power (24V from field supply)
Power Consumption
8.1W maximum @ 28.8V dc
Power Dissipation
2.8W maximum @ 28.8V
Thermal Dissipation
9.5 BTU/hr maximum @ 28.8V dc
Isolation Voltage
1250V rms/V ac
Field Power Bus
Nominal Voltage
Supply Voltage Range
Supply Current
24V dc
10-28.8V dc range,
10A maximum
Dimensions
Inches
3.0H x 2.16W x 5.25L
(Millimeters) (76.2H x 54.9W x 133.4L)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
Conductors
Wire Size
Category
Terminal Base Screw Torque
Field Wiring Terminations
DeviceNet
Power Supply
-20 to 55oC (-4 to 131oF)
-40 to 85oC (-40 to 185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75oC or higher
3/64 inch (1.2mm) insulation maximum
21
7 pound-inches (0.6Nm)
1 - Black Wire
2 - Blue Wire
3 - Bare Wire
4 - White Wire
5 - Red Wire
-V
CAN Low
Shield
CAN High
+V
0 - No Connection
2 - Chassis Ground
4 - Common
6 - Supply
Mass
9.0 oz/255 grams
Publications
Installation Instructions
1734-IN007A-EN-P
1 - No Connection
3 - Chassis Ground
5 - Common
7 - Supply
Agency Certification (when
product is marked)
1
Use this conductor category information for planning conductor routing as described in
publication 1770-4.1, “Industrial Automation Wiring and Grounding Guidelines.”
Publication 1734-TD002B-EN-P - January 2001
14 DeviceNet Interface (Cat. No. 1734-PDN)
POINT I/O
1734-PDN DeviceNet Interface
DeviceNet Cable
Allen-Bradley part number 1485C-P1-Cxxx
Refer to publication DN-2.5 for details
Module Location
Starter module - left side of 1734 system
DeviceNet Interface (Cat. No. 1734-PDN)
DeviceNet Power Specifications
Power Supply
Note: In order to comply with CE Low Voltage
Directives (LVD), you must use a Safety Extra Low
Voltage (SELV) or a Protected Extra Low Voltage
(PELV) power supply to power this interface.
DeviceNet Connector
System Power
(PointBus 5V Power)
DeviceNet Power
(24V from DeviceNet)
No Connection
Input Voltage Rating
24V dc nominal
Input Voltage Range
11-25V dc DeviceNet specification
Input Overvoltage Protection
Reverse polarity protected
Inrush Current
6A for 5ms
Indicators
2 green power supply status indicators
System power (PointBus 5V power)
DeviceNet power (24V from DeviceNet)
No Connection
General Specifications
Chas Gnd
Power Consumption
8.0W max @ 25V dc
Power Dissipation
1.2W max @ 25V
Thermal Dissipation
4.1 BTU/hr max @ 25V dc
Isolation Voltage
1528Vrms or 2593V dc
Pointbus Output Current
Chas Gnd
C
C
V
V
NC = No Connection
C = Common
Chas Gnd = Chassis Ground
V = Supply
42087
Field Power Bus
Voltage
Current
Dimensions HxWxL
Wiring
0
1
NC
12/24V dc
Power
NC
2
Chas Chas
Gnd Gnd
4
V dc
NC = No Connection
C = Common
DeviceNet
connection
3
5
C
C
V
V
6
7
This supply will be
connected to the
internal power bus.
Conductors
Wire Size
Category
Chas Gnd = Chassis Ground
V = Supply
Black
-V
Blue
CAN - Low
Bare
Shield
White
CAN - High
Red
+V
Terminal Base Screw Torque
42064
Field Wiring Terminations
DeviceNet
Power Supply
10V to 28.8V dc range,
120V ac, or 240V ac
50/60Hz
10A max
76.2mm x 25.4mm x 133.4mm
(3.0in x 1.0in x 5.25in)
-20 to +55oC (-4 to +131oF)
-40 to 85oC (-40 to +185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75oC or higher
3/64 inch (1.2mm) insulation maximum
21
7 pound-inches (0.6 Nm)
1 - Black Wire
2 - Blue Wire
3 - Bare Wire
4 - White Wire
5 - Red Wire
-V
CAN Low
Drain
CAN High
+V
0 - No Connection
2 - Chassis Ground
4 - Common
6 - Supply
Mass
4.56 oz/129.3 grams
Publications
Installation Instructions
1734-IN057B-EN-P
1 - No Connection
3 - Chassis Ground
5 - Common
7 - Supply
Agency Certification
42065
Specifications - 1734-PDN
Communication Interface Specifications
Expansion I/O Capacity
12 modules
Communication Rate
125K bit/s (500m max)
250K bit/s (250m max)
512K bit/s (100m max)
DeviceNet Power
Requirements
24V dc (+4% = 25V dc max) @ 400mA max
Publication 1734-TD002B-EN-P - January 2001
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
1.3A max @ 5V dc +5% (4.75-5.25)
1
Use this conductor category information for planning conductor routing. Refer
to publication 1770-4.1, “Industrial Automation Wiring and Grounding
Guidelines.”
POINT I/O
PROFIBUS Adapter (Cat. No. 1734-APB) 15
1734-APB PROFIBUS Adapter
Input Voltage Rating
24V dc nominal
10-28.8V dc range
Field Side Power
Requirements
24V dc (+20% = 28.8V dc max) @ 400mA max
PROFIBUS Adapter (Cat. No. 1734-APB)
Node
Address
Thumbwheel
Adapter Status
PROFIBUS Status
PointBus Status
Adapter
Status
PROFIBUS
Status
PointBus
Status
Input Overvoltage Protection
Reverse polarity protected
Inrush Current
6A max for 10ms
Indicators
3 red/green status indicators
Adapter status
PROFIBUS status
PointBus status
2 green power supply status indicators
System power (PointBus 5V power)
Field power (24V from field supply)
Interruption
Output voltage will stay within specifications when
input drops out for 10ms at 10V with max load.
1734-APB
System Power
Field Power
System
Power
Field
Power
General Specifications
NC
NC
Chas Gnd
C
V
Pointbus Output Current
Chas Gnd
8.1W max @ 28.8V dc
Power Dissipation
2.8W max @ 28.8V
C
Thermal Dissipation
9.5 BTU/hr max @ 28.8V dc
Isolation Voltage
1250Vrms/V ac
Field Power Bus
Nominal Voltage
Supply Voltage Range
Supply Current
24V dc
10-28.8V dc range
10A max
V
NC = No Connection
C = Common
Chas Gnd = Chassis Ground
V = Supply
42697
Dimensions HxWxL
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
Wiring
12/24V dc
Power
0
1
NC
Do not connect 120/240V ac
power to this supply.
2
3
4
5
Conductors
C
6
7
V
NC = No Connection
C = Common
NC
Chas Chas
Gnd Gnd
C
V dc
This dc supply will be
connected to the
internal power bus.
V
Chas Gnd = Chassis Ground
V = Supply
Wire Size
Category
Terminal Base Screw Torque
Field Wiring Terminations
PROFIBUS
42064
PROFIBUS Connection Plug Wiring
Power Supply
Pin 6 - +5V
Pin 8 - RX/TX Data
1A max @ 5V dc +5% (4.75-5.25)
Power Consumption
Pin 3 - RX/TX Data +
Pin 4 - Request to send (RTS)
Pin 5 - Data Ground
76.2mm x 54.9mm x 133.4mm
(3.0in x 2.16in x 5.25in)
-10 to +55oC (14 to 131oF)
-40 to 85oC (-40 to +185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75oC or higher
3/64 inch (1.2mm) insulation maximum
21
7 pound-inches (0.6 Nm)
1 - Not Connected
2 - Not Connected
3 - +RTXTX Data Line
4 - Request To Send
5 - Ground Bus
0 - No Connection
2 - Chassis Ground
4 - Common
6 - Supply
Mass
9.0 oz/255 grams
Publications
Installation Instructions
1734-IN014A-EN-P
6 - +5V Bus
7 - Not Connected
8 - Negative RTX/TX
9 - Not Connected
Housing - Earth Ground
1 - No Connection
3 - Chassis Ground
5 - Common
7 - Supply
Agency Certification
42698
Specifications - 1734-APB
1
Communication Interface Specifications
Expansion I/O Capacity
12 modules (Note: Total expansion up to 63
modules - 12 modules with 1734-APB - add
1734-EP24DC modules for additional 12 modules
for each EP24 up to 63 module maximum)
Module Location
Starter module - left side of 1734 system
Use this conductor category information for planning conductor routing. Refer
to publication 1770-4.1, “Industrial Automation Wiring and Grounding
Guidelines.”
Power Specifications
Power Supply
Note: In order to comply with CE Low Voltage
Directives (LVD), you must use a Safety Extra Low
Voltage (SELV) or a Protected Extra Low Voltage
(PELV) power supply to power this adapter.
Publication 1734-TD002B-EN-P - January 2001
16 1734D Series
POINT I/O
About the 1734D Series
En
24
CH
1734D Series
DeviceNet
Connector
CL
5V
CH
GND
SH
CL
PointBus
Expansion
Port
24V
to 5V
RT
Inputs
Microprocessor
Outputs
0
4
0
4
1
5
1
5
10-60
2
6
2
6
0-9
3
7
3
7
Field Bus
Connector
I/O Circuits
42004
!
The 1734D Series is a set of DIN-rail mounted
products with an integrated DeviceNet
communication interface, various combinations of
onboard I/O points, removable terminations, and a
PointBus expansion port.
The DeviceNet interface presents the integrated
I/O as a single DeviceNet node while expansion
I/O modules will appear as separate nodes.
The 1734D Series includes a non-isolated
DeviceNet communication interface. The 24V dc
from the DeviceNet connection powers a
non-isolated dc/dc converter that generates +5V
dc. This +5V dc powers the 1734D Series
electronics and connects to the PointBus port to
power the expansion I/O electronics.
Power
Connections
I/O Connections
41971
120V ac
or
24V dc
ATTENTION
!
Whatever field power you supply is
connected to the internal
field-power bus. For example, if
120V ac is applied to the power
connections, there will be 120V
ac applied to the modules
through the internal
field-power bus.
POINT I/O modules to the right of
the 1734D products will also have
that internal power bus voltage
applied, unless you use a 1734-FPD
to interrupt and change the field
power-bus voltage.
Publication 1734-TD002B-EN-P - January 2001
POINT I/O
1734D Series 24V dc 8 In/8 Out Combo Module (Cat. No. 1734D-IB8XOB8E, -IB8XOB8ES) 17
1734D-IB8XOB8E, -IB8XOB8ES Module
Output
0
1
Out 0 Out 1
1734D Series 24V dc 8 In/8 Out Combo Module (Cat. No. 1734D-IB8XOB8E, -IB8XOB8ES)
Module Status
2
3
Out 2 Out 3
Network Status
Load
Load
4
5
C
C
C
C
6
Inputs
Outputs
0
4
0
4
1
5
1
5
10-60
2
6
2
6
0-9
3
7
3
7
1’s Node Address Rotary Switch
DeviceNet
connection
42004
Wiring
Field
Power
12/24V dc
Power
0
2
NC
NC
NC
5
6
0
1
Cin
3
C
6
5
6
C
7
C
6
7
2
1
2
C
C
6
7
4
3
5
6
C
7
C
7
Sink Input
1
In 0
3-wire
2-wire
Prox
6
V
Prox
Bare
Shield
Blue
CAN - Low
Black
-V
42065
Input Specifications are IEC 1+ 24V dc Input Compliant
ON-State Voltage Range
10V dc min
24V dc nominal
28.8V dc max
ON-State Current
2.5mA min
6.3mA nominal @ 24V dc
7.6mA max
OFF-State Voltage
5V dc max
OFF-State Current
1.5mA min
Input Impedance
4.7K Ω max (3.6K Ω nominal)
Input Filter Time
OFF to ON
ON to OFF
0.5ms hardware + (0-65ms selectable)
0.5ms hardware + (0-65ms selectable)
Prox
C
V
CAN - High
Specifications - 1734D-IB8XOB8E, -IB8XOB8ES
ON-State Voltage Range
5
C
V = 12/24V dc
C = Common
In 3
4
White
Output Specifications
3
In 2
Prox
In 1
2
+V
7
C
6
Red
5
Vin Vin V
V
V
V
C
C
C
C
RTB 0
RTB 1
RTB 2
RTB 3
RTB 4
This supply will be connected to the internal power bus.
NC = No Connection
Chas Gnd = Chassis Ground
42064
C = Common
V = Supply
0
42015
3
4
5
7
1
2
3
4
5
0
1
0
3
4
5
0
1
2
2
Outputs
4
3
4
7
0
1
2
3
4
Cin
V dc
0
1
NC
Inputs
Load
V = 12/24V dc, C = Common
Field power is supplied from internal power bus
I/O status
10’s Node Address Rotary Switch
Load
7
10V dc min
24V dc nominal
28.8V dc max
ON-State Voltage Drop
0.2V max @ 0.75A
ON-State Current
0.75A max (electronically protected)
OFF-State Voltage
1.5V dc max
41967
Publication 1734-TD002B-EN-P - January 2001
18 1734D Series 24V dc 8 In/8 Out Combo Module (Cat. No. 1734D-IB8XOB8E, -IB8XOB8ES)
General Specifications
Pointbus Output Current
1A max @ 5V dc output power
DeviceNet Current
95mA max for POINTBlock
350mA for maximum with expansion of 12 POINT
I/O modules
Number of POINT I/O
Expansion Modules
12 max at expansion port
Isolation Voltage
1250Vrms or 2121V dc for 1s between user power
and DeviceNet
Indicators
1 red/green module status indicator
1 red/green network status indicator
16 I/O status indicators (8 input/8 output)
Power Dissipation
2.0W max @ 24V dc
Power Consumption
8.2W max @ 24V dc
Field Power Bus
Supply Voltage
Voltage Range
Supply Current
24V dc nominal
10-28.8V dc
10A max
Dimensions HxWxL
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
Conductors
Wire Size
Category
Terminal Base Screw Torque
Field Wiring Terminations
DeviceNet
Field Power Supply
76.2mm x 60.0mm x 133.4mm
(3.00in x 2.36in x 5.25in)
-20 to +55oC (-4 to +131oF)
-40 to 85oC (-40 to 185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75oC or higher
3/64 inch (1.2mm) insulation maximum
21
7 pound-inches (0.6 Nm)
1 - Black Wire
2 - Blue Wire
3 - Bare Wire
4 - White Wire
5 - Red Wire
-V
CAN Low
Drain
CAN High
+V
0 - No Connection
2 - No Connection
4 - Common
6 - Supply
1 - No Connection
3 - No Connection
5 - Common
7 - Supply
Mass
12.02 oz/340.77 grams
Publication
Installation Instructions
1734-5.20
Agency Certification
1
Class I Division 2 certified
Groups A, B, C, D certified
Use this conductor category information for planning conductor routing. Refer
to publication 1770-4.1, “Industrial Automation Wiring and Grounding
Guidelines.”
Publication 1734-TD002B-EN-P - January 2001
POINT I/O
POINT I/O
1734D Series 24V dc 8 In/8 N.O. Relay Combo Module (Cat. No. 1734D-IB8XOW8, -IB8XOW8S) 19
1734D-IB8XOW8, -IB8XOW8S Module
Output Wiring (Load Powered by External Power)
1734D Series 24V dc 8 In/8 N.O. Relay Combo Module (Cat. No. 1734D-IB8XOW8, -IB8XOW8S)
0
Power
Supply
Module Status
Out 1A
2
Network Status
3
Out 0B Out 1B
4
Outputs
0
4
0
4
1
5
1
5
10-60
2
6
2
6
0-9
3
7
3
7
Load
6
10’s Node Address Rotary Switch
DeviceNet
connection
42004
NC
V dc
NC
3
NC
NC
4
5
6
Vin
0
1
2
4
Cin
7
Vin
4
3
C
6
6
5
C
C
V
7
V
V
0
1
0A
2
7
6
7
V
5
3
4
5
C
0
1
2
3
OB
1
1A
3
4A
2
Sink Input
1B
4B
0
5
4
2A
3A
5A
7A
6
7
6
7
2B
3B
5B
7B
NC
4
2-wire
6
V = 12/24V dc
C = Common
CAN - High
Bare
Shield
Blue
CAN - Low
Black
-V
5
C
C
V
V
42065
Specifications - 1734D-IB8XOW8, -IB8XOW8S
Input Specifications are IEC 1+ 24V dc Input Compliant
ON-State Voltage Range
10V dc min
24V dc nominal
28.8V dc max
ON-State Current
2.5mA min
6.3mA nominal @ 24V dc
7.6mA max
42270
In 1
3
NC
White
5
1
2
Prox
+V
6B
4
Chas Gnd = Chassis Ground
V = Supply
In 0
Red
6A
3
RTB 0
RTB 1
RTB 2
RTB 3
RTB 4
This supply will be connected to the internal power bus.
NC = No Connection
C = Common
42271
Outputs
0
1
2
2
Cin
Inputs
0
Load
Out = Output channel relay contacts
Power Supply = can range from +5V dc to 240V ac
C = Common
Wiring
12/24V dc
Field Power
Power
7
Out 2B Out 3B
I/O status
1’s Node Address Rotary Switch
1
5
Out 2A Out 3A
Inputs
0
Power
Supply
1
Out 0A
Prox
OFF-State Voltage
5V dc max
OFF-State Current
1.5mA min
Input Impedance
5.3K Ω max
Input Filter Time
OFF to ON
ON to OFF
0.5ms hardware + (0-65ms selectable)
0.5ms hardware + (0-65ms selectable)
3-wire
7
41966
Publication 1734-TD002B-EN-P - January 2001
20 1734D Series 24V dc 8 In/8 N.O. Relay Combo Module (Cat. No. 1734D-IB8XOW8, -IB8XOW8S)
Output Specifications
Relay Type
Output Voltage Range
(load dependent)
Output Current Rating
(at rated power)
Power Rating
Minimum Load
POINT I/O
General Specifications
Form A, normally open (N.O.)
Single Pole, Single Throw (SPST)
5-28.8V dc @ 2.0A resistive
48V dc @ 0.5A resistive
125V dc @ 0.25A resistive
125V ac @ 2.0A resistive
240V ac @ 2.0A resistive
Resistive
2A @ 5-28.8V dc
0.5A @ 48V dc
0.25A @ 125V dc
2A @ 125V ac
2A @ 240V ac
Inductive
2.0A steady state @ 5-28.8V dc, L/R - 7ms
0.5A steady state @ 48V dc, L/R = 7ms
0.25A steady state @ 125V dc, L/R = 7ms
2.0A steady state, 15A make @ 125V ac,
PF = cos θ = 0.4
2.0A steady state, 15A make @ 240V ac,
PF = cos θ = 0.4
250W max for 125V ac resistive loads
480W max for 240V ac resistive loads
60W max for 28.8V dc resistive loads
24W max for 48V dc resistive loads
31W max for 125V dc resistive loads
250VA max for 125V ac inductive loads
480VA max for 240V ac inductive loads
60VA max for 28.8V dc inductive loads
24VA max for 48V dc inductive loads
31VA max for 125V dc inductive loads
Pointbus Output Current
1A max @ 5V dc output
DeviceNet Current
95mA max for POINTBlock
350mA for maximum with expansion of 12 POINT I/O
modules
Number of POINT I/O
Expansion Modules
12 max at expansion port
Isolation Voltage
1250Vrms or 2121V dc for 1s between user power
and DeviceNet
Indicators
1 red/green module status indicator
1 red/green network status indicator
16 I/O status indicators (8 input/8 relay output)
Power Dissipation
2.0W max @ 24V dc
Power Consumption
8.2W max @ 24V dc
Field Power Bus
Supply Voltage
Voltage Range
Supply Current
24V dc nominal
10-28.8V dc
10A max
Dimensions HxWxL
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
Conductors
Wire Size
10mA per point
Initial Contact Res.
30mΩ
Switching Frequency
1 operation/3s at rated load
Bounce Time
1.2ms average
Expected Contact Life
300K cycles resistive; 100K cycles inductive
Maximum OFF-State
Leakage
1.5mA max
Output Delay Time
10ms max ON/OFF
Category
-20 to +55oC (-4 to +131oF)
-40 to 85oC (-40 to 185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75oC or higher
3/64 inch (1.2mm) insulation maximum
21
Terminal Base Screw Torque 7 pound-inches (0.6 Nm)
Field Wiring Terminations
DeviceNet
Field Power Supply
1 - Black Wire
2 - Blue Wire
3 - Bare Wire
4 - White Wire
5 - Red Wire
-V
CAN Low
Drain
CAN High
+V
0 - No Connection
2 - No Connection
4 - Common
6 - Supply
1 - No Connection
3 - No Connection
5 - Common
7 - Supply
Mass
13.82 oz/391.80 grams
Publication
Installation Instructions
1734-5.21
Agency Certification
1
Publication 1734-TD002B-EN-P - January 2001
76.2mm x 60.0mm x 133.4mm
(3.00in x 2.36in x 5.25in)
Class I Division 2 certified
Groups A, B, C, D certified
Use this conductor category information for planning conductor routing. Refer
to publication 1770-4.1, “Industrial Automation Wiring and Grounding
Guidelines.”
POINT I/O
1734D Series 120V ac 8 In/8 Out Combo Module (Cat. No. 1734D-IA8XOA8, -IA8XOA8S) 21
1734D-IA8XOA8, -IA8XOA8S Module
Output Wiring
0
1734D Series 120V ac 8 In/8 Out Combo Module (Cat. No. 1734D-IA8XOA8, -IA8XOA8S)
1
In 0
Module Status
In 1
2
Network Status
3
In 2
In 3
Load
4
Inputs
4
0
4
1
5
1
5
10-60
2
6
2
6
0-9
3
7
3
7
6
DeviceNet
connection
42004
Wiring
Field Power
V ac
NC
2
3
NC
NC
4
5
7
1
2
3
4
L2
L2
L1
L2
L1
L1
3
L2
Red
+V
White
CAN - High
Bare
Shield
Blue
CAN - Low
Black
-V
L2
L2
L2
7
L2
Input
0
1
In 1
2
42065
7
5
6
7
L2
3
6
Specifications - 1734D-IA8XOA8, -IA8XOA8S
Input Specifications
L2
RTB 0
RTB 1
RTB 2
RTB 3
RTB 4
This supply will be connected to the internal power bus.
NC = No Connection
Chas Gnd = Chassis Ground
41976
L2/N = AC Return/Neutral L1 = AC Power
In 0
42269
5
4
5
L2
1
4
2
3
6
7
1
2
4
5
6
7
L1in L1in L1
7
0
1
0
2
3
6
L2
6
5
4
5
0
1
4
2
3
2
7
Outputs
0
1
0
L2in L2in
6
Inputs
0
1
L2
L1 = 120V ac
L2 = Return
10’s Node Address Rotary Switch
NC
L2
I/O status
1’s Node Address Rotary Switch
0
L2
Outputs
0
120V ac
Power
Load
5
L2
ON-State Voltage
65V ac min
ON-State Current
5.0mA min
OFF-State Voltage
43V ac max
OFF-State Current
2.5mA max
Nominal Input Impedance
17.0kΩ
Input Delay Time
OFF to ON
ON to OFF
20.0ms hardware + (0-65ms selectable)
20.0ms hardware + (0-65ms selectable)
External AC Power Supply
Voltage
120V ac, 60Hz nominal
External AC Power Supply
Voltage Range
85-132V ac, 47-63Hz
3
In 2
In 3
Prox
Prox
4
6
L1 = 120V ac
L2 = Return
5
L2
L2
L1
L1
7
42268
Publication 1734-TD002B-EN-P - January 2001
22 1734D Series 120V ac 8 In/8 Out Combo Module (Cat. No. 1734D-IA8XOA8, -IA8XOA8S)
Output Specifications
General Specifications
Maximum ON-State Voltage
Drop
1.2V @ 0.5A
ON-State Current
10mA per output min
ON-State Current
500mA per output max @ 55oC
(sufficient to operate an A-B Bulletin 500 NEMA
size 3 motor starter)
750mA per output max @ 40oC
1A per output max @ 30oC
OFF-State Leakage
2.25mA max
Output Voltage Range
85-132V ac, 47-63Hz
Output Current Rating
6A per module (6 channels @ 1A each max)
Delay Time
OFF to ON
ON to OFF
POINT I/O
1ms max
ïcycle max
External AC Power Supply
Voltage
120V ac, 60Hz nominal
External AC Power Supply
Voltage Range
85-132V ac, 47-63Hz
Pointbus Output Current
1A max @ 5V ac output
DeviceNet Current
95mA max for POINTBlock
350mA for maximum with expansion of 12 POINT
I/O modules
Number of POINT I/O
Expansion Modules
12 max at expansion port
Isolation Voltage
1250Vrms or 2121V dc for 1s between user power
and DeviceNet
Indicators
1 red/green module status indicator
1 red/green network status indicator
16 I/O status indicators (8 input/8 output)
Power Dissipation
2.0W max @ 24V dc
Power Consumption
8.2W max @ 24V dc
Field Power Bus
Supply Voltage
Voltage Range
Supply Current
24V dc nominal
10-28.8V dc
10A max
Dimensions HxWxL
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
Conductors
Wire Size
Category
Terminal Base Screw Torque
Field Wiring Terminations
DeviceNet
Field Power Supply
-20 to +55oC (-4 to +131oF)
-40 to 85oC (-40 to 185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75oC or higher
3/64 inch (1.2mm) insulation maximum
21
7 pound-inches (0.6 Nm)
1 - Black Wire
2 - Blue Wire
3 - Bare Wire
4 - White Wire
5 - Red Wire
-V
CAN Low
Drain
CAN High
+V
0 - No Connection
2 - No Connection
4 - AC return
6 - AC power
1 - No Connection
3 - No Connection
5 - AC return
7 - AC power
Mass
13.88 oz/393.50 grams
Publication
Installation Instructions
1734-5.22
Agency Certification
1
Publication 1734-TD002B-EN-P - January 2001
76.2mm x 60.0mm x 133.4mm
(3.00in x 2.36in x 5.25in)
Class I Division 2 certified
Groups A, B, C, D certified
Use this conductor category information for planning conductor routing. Refer
to publication 1770-4.1, “Industrial Automation Wiring and Grounding
Guidelines.”
POINT I/O
1734D Series 120V ac 8 In/8 N.O. Relay Combo Module (Cat. No. 1734D-IA8XOW8, -IA8XOW8S) 23
1734D-IA8XOW8, -IA8XOW8S Module
Output Wiring (Load Powered by External Power)
1734D Series 120V ac 8 In/8 N.O. Relay Combo Module (Cat. No. 1734D-IA8XOW8, -IA8XOW8S)
0
Power
Supply
Module Status
Out 1A
2
Network Status
Power
Supply
1
Out 0A
3
Out 0B Out 1B
4
5
Out 2A Out 3A
Inputs
0
Load
Outputs
4
0
6
4
7
Load
Out 2B Out 3B
1
5
1
5
10-60
2
6
2
6
0-9
3
7
3
7
I/O status
Out = Output channel relay contacts
L1 = 120V ac
L2 = Return
42271
1’s Node Address Rotary Switch
10’s Node Address Rotary Switch
DeviceNet
connection
42004
Wiring
120V ac
Power
Field Power
0
V ac
0
1
NC
NC
2
3
NC
NC
4
5
0
7
1
2
4
3
4
L2
6
L2
6
L1
0A
L2
0B
L2
L1
L1
4B
CAN - High
Bare
Shield
Blue
CAN - Low
Black
-V
3A
6A
7A
6B
1
In 1
2
Specifications - 1734D-IA8XOW8, -IA8XOW8S
Input Specifications
7
Input
0
42065
5
6
3B
5B
7B
RTB 0
RTB 1
RTB 2
RTB 3
RTB 4
This supply will be connected to the internal power bus.
NC = No connection
41959
L2/N = AC Return/Neutral L1 = AC Power
In 0
White
5A
3
4
7
2B
4A
1B
2A
1
2
5
6
7
1A
3
4
5
0
1
2
7
6
7
L1in L1in L1
5
3
4
5
0
1
2
3
+V
Outputs
0
1
2
L2in L2in
6
Inputs
Red
ON-State Voltage
65V ac min
ON-State Current
5.0mA min
OFF-State Voltage
43V ac max
OFF-State Current
2.5mA max
Nominal Input Impedance
17.0kΩ
Input Delay Time
OFF to ON
ON to OFF
20.0ms hardware + (0-65ms selectable)
20.0ms hardware + (0-65ms selectable)
External AC Power Supply
Voltage
120V ac, 60Hz nominal
External AC Power Supply
Voltage Range
85-132V ac, 47-63Hz
3
In 2
In 3
Prox
Prox
4
6
L1 = 120V ac
L2 = Return
5
L2
L2
L1
L1
7
42268
Publication 1734-TD002B-EN-P - January 2001
24 1734D Series 120V ac 8 In/8 N.O. Relay Combo Module (Cat. No. 1734D-IA8XOW8, -IA8XOW8S)
Output Specifications
Relay Type
Output Voltage Range (load
dependent)
Output Current Rating
(at rated power)
Power Rating
Minimum Load
POINT I/O
General Specifications
Form A, normally open (N.O.)
Single Pole, Single Throw (SPST)
5-30V dc @ 2.0A resistive
48V dc @ 0.5A resistive
125V dc @ 0.25A resistive
125V ac @ 2.0A resistive
240V ac @ 2.0A resistive
Resistive2A @ 5-30V dc
0.5A @ 48V dc
0.25A @ 125V dc
2A @ 125V ac
2A @ 240V ac
Inductive
2.0A steady state @ 5-30V dc, L/R - 7ms
0.5A steady state @ 48V dc, L/R = 7ms
0.25A steady state @ 125V dc, L/R = 7ms
2.0A steady state, 15A make @ 125V ac,
PF = cos θ = 0.4
2.0A steady state, 15A make @ 240V ac,
PF = cos θ = 0.4
250W max for 125V ac resistive loads
480W max for 240V ac resistive loads
60W max for 28.8V dc resistive loads
24W max for 48V dc resistive loads
31W max for 125V dc resistive loads
250VA max for 125V ac inductive loads
480VA max for 240V ac inductive loads
60VA max for 28.8V dc inductive loads
24VA max for 48V dc inductive loads
31VA max for 125V dc inductive loads
10mA per point
Pointbus Output Current
1A max @ 5V ac output
DeviceNet Current
95mA max for POINTBlock
350mA for maximum with expansion of 12 POINT
I/O modules
Number of POINT I/O
Expansion Modules
12 max at expansion port
Isolation Voltage
1250Vrms or 2121V dc for 1s between user power
and DeviceNet
Indicators
1 red/green module status indicator
1 red/green network status indicator
16 I/O status indicators (8 input/8 relay output)
Power Dissipation
2.0W max @ 24V dc
Power Consumption
8.2W max @ 24V dc
Field Power Bus
Supply Voltage
Voltage Range
Supply Current
24V dc nominal
10-28.8V dc
10A max
Dimensions HxWxL
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
Conductors
Wire Size
76.2mm x 60.0mm x 133.4mm
(3.00in x 2.36in x 5.25in)
-20 to +55oC (-4 to +131oF)
-40 to 85oC (-40 to 185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75oC or higher
3/64 inch (1.2mm) insulation maximum
21
Initial Contact Res.
30mΩ
Switching Frequency
1 operation/3s at rated load
Bounce Time
1.2ms average
Terminal Base Screw Torque 7 pound-inches (0.6 Nm)
Expected Contact Life
300K cycles resistive; 100K cycles inductive
Maximum OFF-State
Leakage
1.5mA max
Field Wiring Terminations
DeviceNet
Output Delay Time
10ms max ON/OFF
Category
Field Power Supply
-V
CAN Low
Drain
CAN High
+V
0 - No Connection
2 - No Connection
4 - AC return
6 - AC power
1 - No Connection
3 - No Connection
5 - AC return
7 - AC power
Mass
13.87 oz/393.41 grams
Publication
Installation Instructions
1734-5.23
Agency Certification
1
Publication 1734-TD002B-EN-P - January 2001
1 - Black Wire
2 - Blue Wire
3 - Bare Wire
4 - White Wire
5 - Red Wire
Class I Division 2 certified
Groups A, B, C, D certified
Use this conductor category information for planning conductor routing. Refer
to publication 1770-4.1, “Industrial Automation Wiring and Grounding
Guidelines.”
POINT I/O
Wiring Base Assembly’s Table of Contents 25
Wiring Base Assembly’s Table of Contents
Use the following table to determine which wiring base assembly
will meet your application needs.
W
Adapter
Purpose
See Page
1734-TB, -TBS
Wiring Base Assembly with 8 Screw-Clamp or
Spring-Clamp Removable Terminal Blocks (Cat
Nos. 1734-TB, -TBS)
26
1734-TB3,
-TB3S
Wiring Base Assembly with 12 Screw-Clamp or
Spring-Clamp Removable Terminal Blocks (Cat
Nos. 1734-TB3, -TB3S)
27
Publication 1734-TD002B-EN-P - January 2001
26 Wiring Base Assembly with 8 Screw-Clamp or Spring-Clamp Removable Terminal Blocks (Cat Nos. 1734-TB, -TBS)
Wiring Base Assembly with 8
Screw-Clamp Removable Terminal
Blocks
Wiring
POINT I/O
0
2
Wiring Base Assembly with 8 Screw-Clamp or Spring-Clamp Removable Terminal Blocks (Cat Nos. 1734-TB,
-TBS)
1
Ch 0
Ch 1
Ch 2
Ch 3
C
C
4
3
5
6
7
V
V
41975
Specifications - 1734-TB, -TBS
General Specifications
42063
Field Power Bus
Supply Voltage
Supply Current
28.8V dc, 120/240V ac
10A maximum
Dimensions Inches
(Millimeters)
2.56H x 0.472W x 6.25L
(65H x 12W x 160L)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
Wiring Base Assembly with 8
Spring-Clamp Removable Terminal
Blocks
Conductors
Wire Size
Category
7 pound-inches (0.6Nm)
Mass
1734-TB - 3.44 oz/97.5 grams
1734-TBS - 3.07 oz/87.0 grams
Agency Certification (when
product is marked)
1
The mounting base (1734-MB) and Removable
Terminal Blocks (1734-RTB or -RTBS) are sold
together as wiring assemblies under the catalog
number 1734-TB (screw clamp terminations) and
1734-TBS (spring clamp terminations).
Publication 1734-TD002B-EN-P - January 2001
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded rated at 75oC or higher
3/64 inch (1.2mm) insulation maximum
21
Terminal Base Screw Torque
Publications
Installation Instructions
42062
-20 to 55oC (-4 to 131oF)
-40 to 85oC (-40 to 185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
1734-IN511A-EN-P
marked by
UR US Underwriters Laboratories
C
Use this conductor category information for planning conductor routing as
described in publication 1770-4.1, “Industrial Automation Wiring and
Grounding Guidelines.”
POINT I/O
Wiring Base Assembly with 12 Screw-Clamp or Spring-Clamp Removable Terminal Blocks (Cat Nos. 1734-TB3, -TB3S) 27
Wiring Base Assembly with 12
Screw-Clamp Removable Terminal
Blocks
Wiring
0
1
Ch 0
Ch 1
Ch 2
Ch 3
C
C
2
Wiring Base Assembly with 12 Screw-Clamp or Spring-Clamp Removable Terminal Blocks (Cat Nos. 1734-TB3,
-TB3S)
3
4
5
6
7
V
V
8
9
C
C
10
11
V
V
42696
42063
Specifications - 1734-TB3, -TB3S
General Specifications
Wiring Base Assembly with 12
Spring-Clamp Removable Terminal
Blocks
Field Power Bus
Supply Voltage
Supply Current
28.8V dc, 120/240V ac
10A maximum
Dimensions Inches
(Millimeters)
2.56H x 0.472W x 6.25L
(65H x 12W x 160L)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
Conductors
Wire Size
Category
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded rated at 75oC or higher
3/64 inch (1.2mm) insulation maximum
21
Terminal Base Screw Torque
7 pound-inches (0.6Nm)
Mass
1734-TB3 - 3.44 oz/97.5 grams
1734-TB3S - 3.07 oz/87.0 grams
Publications
Installation Instructions
Agency Certification (when
product is marked)
42062
1
The mounting base (1734-MB) and Removable
Terminal Blocks (1734-RTB or -RTBS) are sold
together as wiring assemblies under the catalog
number 1734-TB3 (screw clamp terminations) and
1734-TB3S (spring clamp terminations).
-20 to 55oC (-4 to 131oF)
-40 to 85oC (-40 to 185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
1734-IN013A-EN-P
marked by
UR US Underwriters Laboratories
C
Use this conductor category information for planning conductor routing as
described in publication 1770-4.1, “Industrial Automation Wiring and
Grounding Guidelines.”
Publication 1734-TD002B-EN-P - January 2001
28 AC Module’s Table of Contents
POINT I/O
AC Module’s Table of Contents
Use the following table to determine which ac module will meet
your application needs.
Publication 1734-TD002B-EN-P - January 2001
AC Module
Purpose
See Page
1734-IA2
120V ac 2 Input Module (Cat. No. 1734-IA2)
29
1734-OA2
1734-OA2 Module
30
1734-IM2
220V ac 2 Input Module (Cat. No. 1734-IM2)
31
POINT I/O
120V ac 2 Input Module (Cat. No. 1734-IA2) 29
1734-IA2 Module
Specifications - 1734-IA2 120V ac Input Module
This module is IEC3 120V ac Input Compliant
120V ac 2 Input Module (Cat. No. 1734-IA2)
Input Specifications
Module Status
Module
Status
Network Status
Network
Status
NODE:
120/220VAC
Sink
Input
Status of Input 0
0
Status of Input 1
1
NC
L2/N
L1
Channel 1 Connection
NC
L2/N
L2/N = 120V ac Return
1
Ch 0
Ch 1
NC
NC
4
3
Prox
5
L2/N
L2/N
2-Wire
3-Wire
6
7
L1
Ch 0 = Channel 0
NC = No Connection
L1 = 120V ac
3.7mA minimum
6.9mA nominal @ 120V ac, 60Hz
OFF-State Voltage
43V ac maximum
OFF-State Current
2.5mA maximum
Nominal Input Impedance
10.6kΩ
L1
Ch 1 = Channel 1
L2/N = 120V ac Neutral
20ms hardware filter plus 1ms - 64ms digital filter
programmable in increments of 1ms
Indicators
2 yellow input status, logic side
1 green/red network status, logic side
1 green/red module status, logic side
Keyswitch Position
8
Module Location
L1
0
2
ON-State Current
General Specifications
Wiring
Prox
65V ac minimum
120V ac nominal
132V ac maximum
Delay Time
OFF to ON and
ON to OFF
42016
NC = No Connection
L1 = 120V ac Supply
2 (1 group of 2) non-isolated, sinking
ON-State Voltage
1
1734
IA2
Channel 0 Connection
Inputs per Module
75mA maximum @ 5V dc
Power Dissipation
0.7W maximum @ 28.8V dc
Thermal Dissipation
2.4 BTU/hr maximum @ 28.8V dc
Isolation Voltage
Tested at 1250V rms/V ac for 1s
External AC Power Supply
Voltage
120V ac, 60Hz nominal
External AC Power Supply
Voltage Range
85-132V ac, 47-63Hz
Dimensions
2.21H x 0.47W x 2.97L
(56.0H x 12.0W x 75.5L)
Inches
(Millimeters)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
Conductors Wire Size
Category
41960
1734-TB, -TBS, TB3, or -TB3S wiring base assembly
Pointbus Current
-20 to 55°C (-4 to 131°F)
-40 to 85°C (-40 to 185°F)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded rated at 75°C or greater
3/64 inch (1.2mm) insulation maximum
22
Terminal Base Screw Torque
7 pound-inches (0.6Nm)
Field Wiring Terminations
0 - Input 0
2 - No Connection
4 - L2/N
6 - L1
Publications
Installations Instructions
1734-IN010A-EN-P
Mass
1.09 oz/30.9 grams
Agency Certification (when
product is marked)
LISTED
C
1
2
1 - Input 1
3 - No Connection
5 - L2/N
7 - L1
US
Class I, Division 2
Groups A, B, C, and D certified
Off/on delay is time from a valid output “on” signal to output energization.
On/off delay is time from a valid output “off” signal to output deenergization.
Use this conductor category information for planning conductor routing as
described in publication 1770-4.1, “Industrial Automation Wiring and
Grounding Guidelines.”.
Publication 1734-TD002B-EN-P - January 2001
30 120/220V ac 2 Output Module (Cat. No. 1734-OA2)
POINT I/O
1734-OA2 Module
Specifications - 1734-OA2 220V ac Output Module
This module is IEC3 120V/220V ac Output Compliant
120/220V ac 2 Output Module (Cat. No. 1734-OA2)
Output Specifications
Module Status
Module
Status
Network Status
Network
Status
NODE:
120/220VAC
Sink
Output
Status of Output 0
0
Status of Output 1
1
1734
OA2
Channel 0 Connection
NC
L2/N
Channel 1 Connection
NC
Outputs per Module
2 non-isolated, sourcing
ON-State Voltage Range
74V ac minimum
120/220V ac nominal
264V ac maximum
ON-State Voltage Drop
1.0V maximum @ 0.75A
ON-State Current
10mA minimum per channel
750mA maximum per channel
OFF-State Leakage
2.7mA max
Output Current Rating
1.5A (2 channels @ 0.75A each)
Surge Current
16A for 100ms, repeatable every 10s
Delay Time1
OFF to ON
ON to OFF
1/2 cycle maximum
1/2 cycle maximum
Indicators (field side
indication, logic driven)
2 yellow status
2 green/red status
Keyswitch Position
8
General Specifications
L2/N
Module Location
L1
L1
41961
NC = No Connection
L2/N = 120/220V ac Return
L1 = 120/220V ac Supply
2.7 BTU/hr maximum @ 28.8V dc
Tested at 1500V rms/V ac dc for 1s
External AC Power Supply
Voltage
120/220V ac, 60Hz nominal
External AC Power Supply
Voltage Range
85-264V ac, 47-63Hz
Ch 1
3
Dimensions Inches
(Millimeters)
2.21H x 0.47W x 2.97L
(56.0H x 12.0W x 75.5L)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
-20 to 55°C (-4 to 131°F)
-40 to 85°C (-40 to 185°F)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
1
Load
NC
NC
4
5
L2/N
Load
L2/N
6
7
L1
0.8W maximum @ 28.8V dc
Isolation Voltage
0
2
75mA maximum @ 5V dc
Power Dissipation
Thermal Dissipation
Wiring
Ch 0
1734-TB, -TBS, TB3, or -TB3S wiring base assembly
Pointbus Current
L1
Ch 0 = Channel 0
Ch 1 = Channel 1
NC = No Connection L2/N = 120/220V ac Return
L1 = 120/220V ac Supply
Field power is supplied from the internal power bus.
Conductors Wire Size
Category
42014
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded rated at 75°C or greater
3/64 inch (1.2mm) insulation maximum
22
Terminal Base Screw Torque
7 pound-inches (0.6Nm)
Field Wiring Terminations
0 - Output 0
2 - No Connection
4 - L2/N Return
6 - L1
Mass
1.09 oz/30.9 grams
Publications
Installation Instructions
1734-IN009A-EN-P
Agency Certification (when
product is marked)
LISTED
C
1
2
Publication 1734-TD002B-EN-P - January 2001
1 - Output 1
3 - No Connection
5 - L2/N Return
7 - L1
US
Class I, Division 2
Groups A, B, C, and D certified
Off/on delay is time from a valid output “on” signal to output energization.
On/off delay is time from a valid output “off” signal to output deenergization.
Use this conductor category information for planning conductor routing as
described in publication 1770-4.1, “Industrial Automation Wiring and
Grounding Guidelines.”.
POINT I/O
220V ac 2 Input Module (Cat. No. 1734-IM2) 31
1734-IM2 Module
Specifications - 1734-IM2 220V ac Output Module
This module is IEC3 220V ac input compliant.
220V ac 2 Input Module (Cat. No.
Input Specifications
1734-IM2)
Wiring
0
1
Ch 0
2
Prox
2 (1 group of 2) non-isolated, sinking
ON-State Voltage
159V ac minimum
220V ac nominal
264V ac maximum
ON-State Current
5.7mA minimum
8.0mA nominal
9.61mA maximum
Ch 1
NC
NC
4
2-Wire
Number of Inputs
3
Prox
5
L2/N
L2/N
6
3-Wire
L1
Ch 0 = Channel 0
NC = No Connection
L1 = 220V ac
43V ac maximum
OFF-State Current
2.9mA maximum
Nominal Input Impedance
22.3kΩ
Delay Time1
7
L1
OFF-State Voltage
OFF to ON and
ON to OFF
Ch 1 = Channel 1
L2/N = 220V ac Neutral
20ms hardware filter plus 1ms - 64ms digital
filter programmable in increments of 1ms
Indicators
2 yellow input status, logic side
1 green/red network status, logic side
1 green/red module status, logic side
Keyswitch Position
8
41968
General Specifications
Module Status
Module
Status
Network Status
Module Location
Network
Status
NODE:
220VAC
Sink
Input
Status of Input 0
0
Status of Input 1
1
1734
IM2
Channel 0 Connection
NC
L2/N
L1
Pointbus Current
75mA maximum @ 5V dc
Power Dissipation
0.7W maximum @ 28.8V dc
Thermal Dissipation
2.4 BTU/hr maximum @ 28.8V dc
Isolation Voltage
Tested at 1500V rms/V for 1s
External AC Power Supply
Voltage
220V ac, 60Hz nominal
External AC Power Supply
Voltage Range
159-264V ac, 47-63Hz
Dimensions
2.21H x 0.47W x 2.97L
(56.0H x 12.0W x 75.5L)
Inches
(Millimeters)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
Channel 1 Connection
NC
L2/N
Conductors
L1
Wire Size
41962
NC = No Connection
L1 = 220V ac Supply
1734-TB, -TBS, TB3, or -TB3S wiring base
assembly
Category
L2/N = 220V ac Return
-20 to 55°C (-4 to 131°F)
-40 to 85°C (-40 to 185°F)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75°C or greater
3/64 inch (1.2mm) insulation maximum
22
Terminal Base Screw Torque
7 pound-inches (0.6Nm)
Field Wiring Terminations
0 - Input 0
1 - Input 1
2 - No Connection 3 - No Connection
4 - L2/N
5 - L2/N
6 - L1
7 - L1
Mass
1.09 oz/30.90 grams
Publications
Installation Instructions
1734-IN008A-EN-P
Agency Certification (when
product is marked)
LISTED
C
1
2
US
Class I, Division 2
Groups A, B, C, and D certified
Off/on delay is time from a valid output “on” signal to output energization.
On/off delay is time from a valid output “off” signal to output deenergization.
Use this conductor category information for planning conductor routing as
described in publication 1770-4.1, “Industrial Automation Wiring and
Grounding Guidelines.”.
Publication 1734-TD002B-EN-P - January 2001
32 DC Module’s Table of Contents
POINT I/O
DC Module’s Table of Contents
Use the following table to determine which dc module will meet
your application needs.
Publication 1734-TD002B-EN-P - January 2001
DC Module
Purpose
See Page
1734-IB2
24V dc 2 Input Sink Module (Cat. No. 1734-IB2)
33
1734-IB4
24V dc 4 Input Sink Module (Cat. No. 1734-IB4)
34
1734-IV2
24V dc 2 Input Source Module (Cat. No.
1734-IV2)
35
1734-IV4
24V dc 4 Input Source Module (Cat. No.
1734-IV4)
36
1734-OB2E
24V dc Electronically Protected 2 Point Output
Module (Cat. No. 1734-OB2E)
37
1734-OB4E
24V dc Electronically Protected 4 Point Output
Module (Cat. No. 1734-0B4E)
38
POINT I/O
24V dc 2 Input Sink Module (Cat. No. 1734-IB2) 33
1734-IB2 Module
Specifications - 1734-IB2
Input Specifications (IEC 3 24V dc Input Compliant)
24V dc 2 Input Sink Module (Cat. No. 1734-IB2)
Module Status
Module
Status
Network Status
Inputs per Module
2 (1 group of 2) sinking
ON-State Voltage
10V dc min
24V dc nominal
28.8V dc max
ON-State Current
2mA min
4mA nominal @ 24V dc
5mA max
Network
Status
NODE:
24VDC
Sink
Input
Status of Input 0
0
Status of Input 1
1
NC
5V dc max
OFF-State Current
1.5mA min
Input Impedance
4.7K Ω max, 3.6K Ω nominal
Input Filter Time
OFF to ON
ON to OFF
1734
IB2
Input 0 Connection
OFF-State Voltage
1
Indicators
2 yellow input status, logic side
1 green/red network status, logic side
1 green/red module status, logic side
Keyswitch Position
1
Input 1 Connection
NC
0.5 hardware + (0-63ms selectable)
0.5 hardware + (0-63ms selectable)
General Specifications
C
V
C
V
42088
Input = (0 and 1)
C = Common (4 and 5)
NC = No Connection (2 and 3)
V = Supply (6 and 7)
Wiring
0
Sink Input
2
Prox
In 1
NC
NC
C
C
4
Prox
5
3-Wire
6
75 mA max @ 5V dc
Power Dissipation
0.7W max @ 28.8V dc
Thermal Dissipation
2.4 BTU/hr max @ 28.8V dc
Isolation Voltage
1250V rms/V ac
Field Power Bus
Supply Voltage
Voltage Range
24V dc nominal
10-28.8V dc
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
3
2-Wire
1734-TB, -TBS, TB3, or -TB3S wiring base assembly
Pointbus Current
Dimensions HxWxL
1
In 0
Module Location
Conductors
Wire Size
7
V
V
Category
V = 12/24V dc, C = Common
12/24V dc is supplied through the internal power bus
56.0mm x 12.0mm x 75.5mm
(2.21in x 0.47in x 2.97in)
-20 to +55oC (-4 to +131oF)
-40 to 85oC (-40 to 185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75oC or higher
3/64 inch (1.2mm) insulation maximum
21
Terminal Base Screw Torque
7 pound-inches (0.6 Nm)
Field Wiring Terminations
0 - Input 0
2 - No Connection
4 - Common
6 - User Supply
Mass
1.09 oz/30.90 grams
Publication
Installation Instructions
1734-IN051B-EN-P
41963
Agency Certification
LISTED
C
1
2
1 - Input 1
3 - No Connection
5 - Common
7 - User Supply
US
Class I, Division 2
Groups A, B, C, and D certified
Input off-to-on filter time is the time from a valid input signal to recognition by
the module. Input on-to-off time is the time from a valid input signal to
recognition by the module.
Use this conductor category information for planning conductor routing. Refer
to publication 1770-4.1, “Industrial Automation Wiring and Grounding
Guidelines.”.
Publication 1734-TD002B-EN-P - January 2001
34 24V dc 4 Input Sink Module (Cat. No. 1734-IB4)
POINT I/O
1734-IB4 Module
Specifications - 1734-IB4
Input Specifications (IEC 3 24V dc Input Compliant)
24V dc 4 Input Sink Module (Cat. No. 1734-IB4)
Module Status
Module
Status
Network Status
Inputs per Module
4 (1 group of 4) sinking
ON-State Voltage
10V dc min
24V dc nominal
28.8V dc max
ON-State Current
2mA min
4mA nominal @ 24V dc
5mA max
Network
Status
NODE:
24VDC
Sink
Input
Status of Input 0
0
Status of Input 1
Status of Input 2
Status of Input 3
1
2
3
OFF-State Voltage
5V dc max
OFF-State Current
1.5mA min
Input Impedance
4.7K Ω max, 3.6K Ω nominal
Input Filter Time
OFF to ON
ON to OFF
1734
IB4
Input 0 Connection
Input 1 Connection
Input 2 Connection
Input 3 Connection
1
0.5 hardware + (0-63ms selectable)
0.5 hardware + (0-63ms selectable)
Indicators
4 yellow input status, logic side
1 green/red network status, logic side
1 green/red module status, logic side
Keyswitch Position
1
General Specifications
C
V
C
Module Location
V
42082
Input = (0, 1, 2, and 3) C = Common (4 and 5)
V = Supply (6 and 7)
Wiring
0
Prox
1.0W max @ 28.8V dc
Thermal Dissipation
3.4 BTU/hr max @ 28.8V dc
Isolation Voltage
1250V rms/V ac
Field Power Bus
Supply Voltage
Voltage Range
24V dc nominal
10-28.8V dc
1
In 0
2-Wire
75 mA max @ 5V dc
Power Dissipation
Dimensions HxWxL
Sink Input
3-Wire
Prox
2
In 2
In 1
In 3
4
3
5
C
Prox
Prox
C
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
Conductors
6
Wire Size
7
V
V
V = 12/24V dc, C = Common
12/24V dc is supplied through the internal power bus
Category
41967
1734-TB, -TBS, TB3, or -TB3S wiring base assembly
Pointbus Current
56.0mm x 12.0mm x 75.5mm
(2.21in x 0.47in x 2.97in)
-20 to +55oC (-4 to +131oF)
-40 to 85oC (-40 to 185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75oC or higher
3/64 inch (1.2mm) insulation maximum
21
Terminal Base Screw Torque
7 pound-inches (0.6 Nm)
Field Wiring Terminations
0 - Input 0
2 - Input 2
4 - Common
6 - User Supply
Mass
1.12 oz/31.75 grams
Publication
Installation Instructions
1734-IN051B-EN-P
Agency Certification
LISTED
C
1
2
Publication 1734-TD002B-EN-P - January 2001
1 - Input 1
3 - Input 3
5 - Common
7 - User Supply
US
Class I, Division 2
Groups A, B, C, and D certified
Input off-to-on filter time is the time from a valid input signal to recognition by
the module. Input on-to-off time is the time from a valid input signal to
recognition by the module.
Use this conductor category information for planning conductor routing. Refer
to publication 1770-4.1, “Industrial Automation Wiring and Grounding
Guidelines.”
POINT I/O
24V dc 2 Input Source Module (Cat. No. 1734-IV2) 35
1734-IV2 Module
Specifications - 1734-IV2
Input Specifications (IEC 3 24V dc Input Compliant)
24V dc 2 Input Source Module (Cat. No. 1734-IV2)
Module Status
Network Status
Module
Status
Inputs per Module
2 (1 group of 2) sourcing
ON-State Voltage
10V dc min
24V dc nominal
28.8V dc max
ON-State Current
2mA min
4mA nominal @ 24V dc
5mA max
Network
Status
NODE:
24VDC
Source
Input
Status of Input 0
0
Status of Input 1
1
NC
5V dc max
OFF-State Current
1.5mA min
Input Impedance
4.7K Ω max, 3.6K Ω nominal
Input Filter Time
OFF to ON
ON to OFF
1734
IV2
Input 0 Connection
OFF-State Voltage
1
Indicators
2 yellow input status, logic side
1 green/red network status, logic side
1 green/red module status, logic side
Keyswitch Position
1
Input 1 Connection
NC
0.5 hardware + (0-63ms selectable)
0.5 hardware + (0-63ms selectable)
General Specifications
C
V
Module Location
C
V
42084
Input = (0 and 1)
C = Common (4 and 5)
NC = No Connection (2 and 3)
V = Supply (6 and 7)
Wiring
Source Input
Prox
2-Wire
0
2
1
In 0
In 1
NC
NC
C
C
V
V
4
3
5
6
75mA max @ 5V dc
Power Dissipation
0.7W max @ 28.8V dc
Thermal Dissipation
2.4 BTU/hr max @ 28.8V dc
Isolation Voltage
1250V rms/V ac
Field Power Bus
Supply Voltage
Voltage Range
24V dc nominal
10-28.8V dc
Dimensions HxWxL
Prox
3-Wire
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
Conductors
7
V = 12/24V dc, C = Common
12/24V dc is supplied through the internal power bus
41965
1734-TB, -TBS, TB3, or -TB3S wiring base assembly
Pointbus Current
Wire Size
Category
56.0mm x 12.0mm x 75.5mm
(2.21in x 0.47in x 2.97in)
-20 to +55oC (-4 to +131oF)
-40 to 85oC (-40 to 185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75oC or higher
3/64 inch (1.2mm) insulation maximum
21
Terminal Base Screw Torque
7 pound-inches (0.6 Nm)
Field Wiring Terminations
0 - Input 0
2 - No Connection
4 - Common
6 - User Supply
Mass
1.10 oz/31.19 grams
Publication
Installation Instructions
1734-IN052B-EN-P
Agency Certification
LISTED
C
1
2
1 - Input 1
3 - No Connection
5 - Common
7 - User Supply
US
Class I, Division 2
Groups A, B, C, and D certified
Input off-to-on filter time is the time from a valid input signal to recognition by
the module. Input on-to-off time is the time from a valid input signal to
recognition by the module.
Use this conductor category information for planning conductor routing. Refer
to publication 1770-4.1, “Industrial Automation Wiring and Grounding
Guidelines.”
Publication 1734-TD002B-EN-P - January 2001
36 24V dc 4 Input Source Module (Cat. No. 1734-IV4)
POINT I/O
1734-IV4 Module
Specifications - 1734-IV4
Input Specifications (IEC 3 24V dc Input Compliant)
24V dc 4 Input Source Module (Cat. No. 1734-IV4)
Module Status
Module
Status
Network Status
10V dc min
24V dc nominal
28.8V dc max
ON-State Current
2mA min
4mA nominal @ 24V dc
5mA max
Network
Status
Status of Input 0
Status of Input 1
0
Status of Input 2
Status of Input 3
2
1
3
5V dc max
OFF-State Current
1.5mA min
Input Impedance
4.7K Ω max, 3.6K Ω nominal
1
4 yellow input status, logic side
1 green/red network status, logic side
1 green/red module status, logic side
Input 3 Connection
Keyswitch Position
1
C
Module Location
Input 1 Connection
Input 2 Connection
General Specifications
V
42085
Input = (0, 1, 2, and 3) C = Common (4 and 5)
V = Supply (6 and 7)
Wiring
0
75mA max @ 5V dc
Power Dissipation
1.0W max @ 28.8V dc
Thermal Dissipation
3.4 BTU/hr max @ 28.8V dc
Isolation Voltage
1250V rms/V ac
Field Power Bus
Supply Voltage
Voltage Range
24V dc nominal
10-28.8V dc
2-Wire
Prox
2
1
In 0
In 1
In 2
In 3
C
C
V
V
4
3
5
6
Prox
Prox
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
Conductors
Wire Size
7
Category
V = 12/24V dc, C = Common
12/24V dc is supplied through the internal power bus
1734-TB, -TBS, TB3, or -TB3S wiring base assembly
Pointbus Current
Dimensions HxWxL
Source Input
0.5 hardware + (0-63ms selectable)
0.5 hardware + (0-63ms selectable)
Indicators
Input 0 Connection
V
OFF-State Voltage
Input Filter Time
OFF to ON
ON to OFF
1734
IV4
C
Prox
4 (1 group of 4) sourcing
ON-State Voltage
NODE:
24VDC
Source
Input
3-Wire
Inputs per Module
56.0mm x 12.0mm x 75.5mm
(2.21in x 0.47in x 2.97in)
-20 to +55oC (-4 to +131oF)
-40 to 85oC (-40 to 185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75oC or higher
3/64 inch (1.2mm) insulation maximum
21
Terminal Base Screw Torque
7 pound-inches (0.6 Nm)
Field Wiring Terminations
0 - Input 0
2 - Input 2
4 - Common
6 - User Supply
Mass
1.12 oz/31.75 grams
Publication
Installation Instructions
1734-IN052B-EN-P
41969
Agency Certification
LISTED
C
1
2
Publication 1734-TD002B-EN-P - January 2001
1 - Input 1
3 - Input 3
5 - Common
7 - User Supply
US
Class I, Division 2
Groups A, B, C, and D certified
Input off-to-on filter time is the time from a valid input signal to recognition by
the module. Input on-to-off time is the time from a valid input signal to
recognition by the module.
Use this conductor category information for planning conductor routing. Refer
to publication 1770-4.1, “Industrial Automation Wiring and Grounding
Guidelines.”
POINT I/O
24V dc Electronically Protected 2 Point Output Module (Cat. No. 1734-OB2E) 37
1734-OB2E Module
Specifications - 1734-OB2E
Output Specifications
24V dc Electronically Protected 2 Point Output Module (Cat. No. 1734-OB2E)
Module Status
Network Status
Module
Status
Number of Outputs
2 (1 group of 2) sourcing
ON-State Voltage Range
10V dc min
24V dc nominal
28.8V dc max
ON-State Voltage Drop
0.2V dc max
Network
Status
NODE:
24VDC
Source
Output
ON-State Current
1.0mA min per channel
28.8V dc max
Status of Output 0
0
OFF-State Voltage
Status of Output 1
1
OFF-State Leakage
Output Signal Delay
OFF to ON
ON to OFF
1734
OB2E
Output 0 Connection
Output 0 Connection
C
0.5mA max
1
0.1ms max
0.1ms max
Output Current Rating
Max 1.0A per output
2.0 max per module
Output 1 Connection
Surge Current
2A for 10ms, repeatable every 3 seconds
Output 1 Connection
Indicators (field side
indication, logic driven)
2 yellow output status;
2 red output fault
2 green/red module/network status
C
Keyswitch Position
1
General Specifications
V
Module Location
V
42086
C = Common
V = Supply
Wiring
0 Out
Load
Out 1
0 1
2 Out Out 3
0 1
4
C
C
V
V
6
5
75mA max @ 5V dc
Power Dissipation
0.8W max @ 28.8V dc
Thermal Dissipation
2.7 BTU/hr max @ 28.8V dc
Isolation Voltage
1250V rms/V ac
External dc Power
Supply Voltage
Voltage Range
Supply Current
24V dc nominal
10 to 28.8V dc
8mA
Dimensions HxWxL
Load
7
41972
V = 12/24V dc, C = Common
Field power is supplied from the internal power bus
Module power is supplied from the internal power bus
1734-TB, -TBS, TB3, or -TB3S wiring base assembly
Pointbus Current
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
Conductors
Wire Size
Category
56.0mm x 12.0mm x 75.5mm
(2.21in x 0.47in x 2.97in)
-20 to +55oC (-4 to +131oF)
-40 to 85oC (-40 to 185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75oC or higher
3/64 inch (1.2mm) insulation maximum
21
Terminal Base Screw Torque
7 pound-inches (0.6 Nm)
Field Wiring Terminations
0 - Output 0
2 - Output 0
4 - Common
6 - Supply
Mass
1.15 oz/32.60 grams
Publication
Installation Instructions
1734-IN056B-EN-P
Agency Certification
LISTED
C
1
2
1 - Output 1
3 - Output 1
5 - Common
7 - Supply
US
Class I, Division 2
Groups A, B, C, and D certified
Off/on delay is time from a valid output “on” signal to output energization.
On/off delay is time from a valid output “off” signal to output deenergization.
Use this conductor category information for planning conductor routing. Refer
to publication 1770-4.1, “Industrial Automation Wiring and Grounding
Guidelines.”
Publication 1734-TD002B-EN-P - January 2001
38 24V dc Electronically Protected 4 Point Output Module (Cat. No. 1734-0B4E)
1734-OB4E Module
POINT I/O
Specifications - 1734-OB4E
Output Specifications
24V dc Electronically Protected 4 Point Output Module (Cat. No. 1734-0B4E)
Module Status
Module
Status
Network Status
Number of Outputs
4 (1 group of 4) sourcing
ON-State Voltage Range
10V dc min
24V dc nominal
28.8V dc max
Network
Status
NODE:
ON-State Voltage Drop
0.2V dc max
ON-State Current
1.0mA min per channel
0
OFF-State Voltage
28.8V dc max
1
OFF-State Leakage
24VDC
Source
Output
Status of Output 0
Status of Output 1
Status of Output 2
Status of Output 3
2
Output Signal Delay
OFF to ON
ON to OFF
3
1734
OB4E
Output 0 Connection
Output 2 Connection
C
0.5mA max
1
0.1ms max
0.1ms max
Output Current Rating
Max 1.0A per output
2.0 max per module
Output 1 Connection
Surge Current
2A for 10ms, repeatable every 3 seconds
Output 3 Connection
Indicators (field side
indication, logic driven)
4 yellow output status;
4 red output fault
2 green/red module/network status
C
Keyswitch Position
1
General Specifications
C
C
Module Location
42089
C = CommonV = Supply
Wiring
0 Out
Out 1
0
1
2 Out Out 3
2
3
Load
Load
4
6
C
C
C
C
5
75mA max @ 5V dc
Power Dissipation
1.2W max @ 28.8V dc
Thermal Dissipation
4.1 BTU/hr max @ 28.8V dc
Isolation Voltage
1250V rms/V ac
External dc Power
Supply Voltage
Voltage Range
Supply Current
24V dc nominal
10 to 28.8V dc
16mA
Dimensions HxWxL
Load
Load
7
42015
V = 12/24V dc, C = Common
Field power is supplied from the internal power bus
Module power is supplied from the internal power bus
1734-TB, -TBS, TB3, or -TB3S wiring base assembly
Pointbus Current
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
Conductors
Wire Size
Category
56.0mm x 12.0mm x 75.5mm
(2.21in x 0.47in x 2.97in)
-20 to +55oC (-4 to +131oF)
-40 to 85oC (-40 to 185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75oC or higher
3/64 inch (1.2mm) insulation maximum
21
Terminal Base Screw Torque 7 pound-inches (0.6 Nm)
Field Wiring Terminations
0 - Output 0
2 - Output 2
4 - Common
6 - Common
Mass
1.17 oz/33.17 grams
Publication
Installation Instructions
1734-IN056B-EN-P
Agency Certification
LISTED
C
1
2
Publication 1734-TD002B-EN-P - January 2001
1 - Output 1
3 - Output 3
5 - Common
7 - Common
US
Class I, Division 2
Groups A, B, C, and D certified
Off/on delay is time from a valid output “on” signal to output energization.
On/off delay is time from a valid output “off” signal to output deenergization.
Use this conductor category information for planning conductor routing. Refer
to publication 1770-4.1, “Industrial Automation Wiring and Grounding
Guidelines.”
POINT I/O
Analog Module’s Table of Contents 39
Analog Module’s Table of Contents
Use the following table to determine which analog module will
meet your application needs.
Analog
Module
Purpose
See Page
1734-IE2C/B
24V dc Analog 2 Current Input Module (Cat. No.
1734-IE2C/B)
40
1734-OE2C/B
24Vdc Analog 2 Current Output Module (Cat.
No. 1734-OE2C/B)
41
Publication 1734-TD002B-EN-P - January 2001
40 24V dc Analog 2 Current Input Module (Cat. No. 1734-IE2C/B)
POINT I/O
1734-IE2C/B Module
Common Mode
Rejection Ration
120dB
24V dc Analog 2 Current Input Module (Cat. No. 1734-IE2C/B)
Module Status
Normal Mode Rejection Ratio -60dB
-3db
Notch filter
15.7Hz @ Notch = 60Hz
13.1Hz @ Notch = 50Hz
65.5Hz @ Notch = 250Hz
131Hz @ Notch = 500Hz
Module
Status
Network Status
Network
Status
NODE:
4-20mA
Analog
Input
Status of Input 0
Status of Input 1
Data Format
0
1
Signed integer
Maximum Overload
Fault protected to 28.8V dc
Calibration
Factory calibrated
Indicators
1 green/red network status, logic side
1 green/red module status, logic side
2 green/red input status, logic side
Keyswitch Position
3
1734
IE2C
Input 0 Connection
General Specifications
Input 1 Connection
Module Location
Chas Gnd
Chas Gnd
C
C
V
75mA @ 5V dc
Power Dissipation
0.6W max @ 28.8V dc
Thermal Dissipation
2.0 BTU/hr max @ 28.8V dc
Isolation Voltage
1250V rms/V ac
No isolation between individual channels
V
42083
Chas Gnd = Chassis Ground
C = Common
V = Supply
External dc Power
Supply Voltage
Voltage Range
Supply Current
Dimensions HxWxL
Wiring
ac or
dc
Current
Input
Device
4-wire
Need New DRAWING
0
1
In 0
In 1
Chas
Gnd
Chas
Gnd
2
3
4
V = 12/24V dc supply
C = Common
Chas Gnd = Chassis ground
6
Current
Input
Device
C
C
V
V
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
2-wire
Conductors
5
1734-TB, -TBS, TB3, or -TB3S wiring base assembly
Pointbus Current
Wire Size
Category
7
24V dc nominal
10-28.8V dc
10mA @ 24V dc
56.0mm x 12.0mm x 75.5mm
(2.21in x 0.47in x 2.97in)
-20 to +55oC (-4 to +131oF)
-40 to 85oC (-40 to 185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75oC or higher
3/64 inch (1.2mm) insulation maximum
21
Terminal Base Screw Torque
7 pound-inches (0.6 Nm)
Field Wiring Terminations
0 - Input 0
2 - Ground
4 - Common
6 - Supply
Specifications - 1734-IE2C
Mass
1.22 oz/34.59 grams
Input Specifications
Publication
Installation Instructions
1734-IN053B-EN-P
42017
Number of Inputs
2 single-ended, non-isolated
Resolution
16 bits - over 21mA
0.32µA/cnt
Input Current Terminal
Agency Certification
Absolute Accuracy1
Current Terminal
0.1% Full Scale @ 25oC
Accuracy Drift w/Temp.
Current Terminal
30ppm/oC
Input Update Rate
(per Module)
50ms @ Notch = 60Hz (default)
100ms @ Notch = 50Hz
24ms @ Notch = 250Hz
12ms @ Notch = 500Hz
Step Response (per Channel)
70ms @ Notch = 60Hz (default)
80ms @ Notch = 50Hz
16ms @ Notch = 250Hz
8ms @ Notch = 500Hz
Input Impedance
60Ω
Conversion Type
Delta Sigma
Publication 1734-TD002B-EN-P - January 2001
LISTED
C
4-20mA
0-20mA
1
2
1 - Input 1
3 - Ground
5 - Common
7 - Supply
US
Class I, Division 2
Groups A, B, C, and D certified
Includes offset, gain, non-linearity and repeatability error terms.
Use this conductor category information for planning conductor routing. Refer
to publication 1770-4.1, “Industrial Automation Wiring and Grounding
Guidelines.”
POINT I/O
24Vdc Analog 2 Current Output Module (Cat. No. 1734-OE2C/B) 41
1734-0E2C/B Module
Indicators
1 green/red network status, logic side
1 green/red module status, logic side
2 green/red output status, logic side
Keyswitch Position
4
24Vdc Analog 2 Current Output Module (Cat. No. 1734-OE2C/B)
Module Status
Network Status
Module
Status
General Specifications
Network
Status
Module Location
NODE:
4-20mA
Analog
Output
Pointbus Current
75mA max @ 5V dc
Status of Output 0
0
Power Dissipation
Max 1.0W max @ 28.8V dc
Status of Output 1
1
Thermal Dissipation
3.4 BTU/hr max @ 28.8V dc
Isolation Voltage
1250V rms/V ac tested at 2200V for 1s
No isolation between individual channels
External dc Power
Supply Voltage
Voltage Range
Supply Current
1734
OE2C
Output 0 Connection
Chas Gnd
Output 1 Connection
Dimensions HxWxL
Chas Gnd
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
C
C
V
V
42090
Output = (0 and 1)
C = Common (4 and 5)
Chas Gnd = Chassis Ground (2 and 3)
V = Supply (6 and 7)
Conductors
Wire Size
Category
Wiring
ac or
dc
1734-TB, -TBS, TB3, or -TB3S wiring base
assembly
Current
Output
Device
0
Out
0
2
4-wire
Chas Chas
Gnd Gnd
4
Out = Output channel
Chas Gnd = Chassis ground
V = Not used
6
1
Out
1
C
C
V
V
Current
Output
Device
3
2-wire
5
24V dc nominal
10-28.8V dc (includes 5% ac ripple)
50mA @ 24V dc (including outputs @ 20mA)
56.0mm x 12.0mm x 75.5mm
(2.21in x 0.47in x 2.97in)
-20 to +55oC (-4 to +131oF)
-40 to 85oC (-40 to 185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75oC or higher
3/64 inch (1.2mm) insulation maximum
21
Terminal Base Screw Torque
7 pound-inches (0.6 Nm)
Field Wiring Terminations
0 - Output 0
2 - Ground
4 - Common
6 - Supply
Mass
1.26 oz/35.72 grams
Publication
Installation Instructions
1734-IN054C-EN-P
Agency Certification
7
1
2
Specifications - 1734-OE2C
Output Specifications
Number of Outputs
2 single-ended, non-isolated
Resolution
Current
13 bits over 0-21mA
513µA/cnt
Output Current Terminal
0mA output until communication is established
4-20mA user configurable
0-20mA user configurable
Absolute Accuracy1
Current Terminal
0.1% Full Scale @ 25oC
Accuracy Drift w/Temp.
Current Terminal
30ppm/oC
LISTED
C
42018
1 - Output 1
3 - Ground
5 - Common
7 - Supply
US
Class I, Division 2
Groups A, B, C, and D certified
Includes offset, gain, non-linearity and repeatability error terms.
Use this conductor category information for planning conductor routing. Refer
to publication 1770-4.1, “Industrial Automation Wiring and Grounding
Guidelines.”
Step Response to 63% of FS
24µs
Resistive Load on mA Output 0-330Ω
Conversion Type
Digital to analog converter
Conversion Rate
16µs
Data Format
Signed integer
Calibration
Factory calibrated
Publication 1734-TD002B-EN-P - January 2001
42 Counter Module’s Table of Contents
POINT I/O
Counter Module’s Table of Contents
Use the following table to determine which counter module will
meet your application needs.
Publication 1734-TD002B-EN-P - January 2001
Counter
Module
Purpose
See Page
1734-IK
24V Encoder/Counter Module (Cat. No. 1734-IK)
43
1734-IJ
5V Encoder/Counter Module (Cat. No. 1734-IJ)
44
1734-VHSC24
24V dc Very High Speed Counter Module (Cat.
No. 1734-VHSC24)
45
1734-VHSC5
5V dc Very High Speed Counter Module (Cat.
No. 1734-VHSC5)
47
POINT I/O
24V Encoder/Counter Module (Cat. No. 1734-IK) 43
1734-IK Module
General Specifications
24V Encoder/Counter Module (Cat. No. 1734-IK)
Module Status
Module
Status
Network Status
Network
Status
Module Location
1734-TB, -TBS, -TB3, -TB3S wiring base
assembly
Keyswitch Position
2
Pointbus Current
160mA maximum
Power Dissipation
1.5W maximum @ rated load
NODE:
Status of Input A
A
Status of Input B
B
Status of Input Z
Z
1734
IK
Input A
Input Aret
Input B
Input Bret
Input Z
Input Zret
Thermal Dissipation
5.1 BTU/hr maximum @ rated load
Isolation Voltage (minimum)
Prequalified at 1250V ac/rms between:
System side
Chassis ground
A/B/Z inputs
External dc Power
No additional external power required to power
module.
Dimensions Inches
(Millimeters)
2.21H x 0.47W x 2.97L
(56.0H x 12.0W x 75.5L)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
-20 to 55°C (-4 to 131°F)
-40 to 85°C (-40 to 185°F)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
Conductors Wire Size
Chassis Ground
41974
Wiring
0
2
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75°C or higher
3/64 inch (1.2mm) insulation maximum
22
Chassis Ground
Category
Terminal Base Screw Torque
7 pound-inches (0.6Nm)
Field Wiring Terminations
Module 1
0-A
2-B
4-Z
6 - Chassis ground
1
A
Aret
B
Bret
3
4
5
Z
Zret
Mass
1.15 oz/32.60 grams
Publications
Installation Instructions
User Manual
1734-IN006A-EN-P
1734-UM006A-EN-P
Agency Certification
6
Chas
Gnd
Chas
Gnd
1 - Aret
3 - Bret
5 - Zret
7 - Chassis ground
LISTED
7
C
41975
US
Class I, Division 2
Groups A, B, C, and D certified
A, B, Z, Aret, Bret, and Zret = inputs
Chas Gnd = Chassis Ground
1
Use this conductor category information for planning conductor routing as
described in publication 1770-4.1, “Industrial Automation Wiring and
Grounding Guidelines.”.
Specifications - 1734-IK Encoder/Counter Module
Input Specifications
Number of Inputs
1 - 1 group of A/Areturn, B/Breturn and
Z/Zreturn
Input Voltage
15-24V dc
Input Current
6.1mA @ 15V dc
10.2mA @ 24V dc
Input OFF-State Current
<0.250mA max
Input OFF-State Voltage
<1.8V dc)
Input ON-State Current
>5mA
Input ON-State Voltage
>12.5V dc
Maximum ON-State Voltage
Refer to Input Derating Curve to the right
Input Filter Selections (per A/B/Z Off
group)
10µs
100µs
1.0ms
10.0ms
Maximum Input Frequency
1.0MHz counter and encoder X1 configurations
500kHz encoder X2 configuration (no filter)
250kHz encoder X4 configuration (no filter)
Input Derating Curve
30
28.8
25
Input
Voltage
(V)
Input Voltage
24
20
15
10
5
10
20
30
40
Module Ambient Still Air Temperature (°C)
45
55
Note: Exceeding the maximum input voltage can cause permanent damage to the input.
Publication 1734-TD002B-EN-P - January 2001
44 5V Encoder/Counter Module (Cat. No. 1734-IJ)
POINT I/O
1734-IJ Module
Specifications - 1734-IJ Encoder/Counter Module
Input Specifications
5V Encoder/Counter Module (Cat. No. 1734-IJ)
Number of Inputs
Module
Status
Module Status
Network
Status
1 - 1 group of A/Areturn, B/Breturn and
Z/Zreturn
Input Voltage
5V
Input Current
19.1mA @ 5V dc
25.7mA @ 6V dc
Input OFF-State Current
<0.250mA max
NODE:
Network Status
A
Status of Input A
B
Status of Input B
Z
Status of Input Z
1734
IJ
Input A
Input Aret
Input B
Input Bret
Input Z
Input Zret
Input OFF-State Voltage
<1.25V dc)
Input ON-State Current
>5mA
Input ON-State Voltage
>2.6V dc
Maximum ON-State Voltage
+6V
Input Filter Selections
(per A/B/Z group)
Off
10µs
100µs
1.0ms
10.0ms
Maximum Input Frequency
1.0MHz counter and encoder X1 configurations
500kHz encoder X2 configuration (no filter)
250kHz encoder X4 configuration (no filter)
General Specifications
Chassis Ground
Chassis Ground
41977
Wiring
0
2
1
A
Aret
B
Bret
3
4
5
Z
6
Chas
Gnd
Zret
Chas 7
Gnd
A, B, Z, Aret, Bret, and Zret = inputs
Chas Gnd = Chassis Ground
41975
Module Location
1734-TB, -TBS, -TB3, -TB3S wiring base
assembly
Keyswitch Position
2
Pointbus Current
160mA maximum
Power Dissipation
1.1W maximum @ rated load
Thermal Dissipation
3.75 BTU/hr maximum @ rated load
Isolation Voltage (minimum)
Prequalified at 1250V ac/rms between:
System side
Chassis ground
A/B/Z inputs
External dc Power
No additional external power required to power
module.
Dimensions Inches
(Millimeters)
2.21H x 0.47W x 2.97L
(56.0H x 12.0W x 75.5L)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
-20 to 55°C (-4 to 131°F)
-40 to 85°C (-40 to 185°F)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
Conductors Wire Size
Category
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75°C or higher
3/64 inch (1.2mm) insulation maximum
22
Terminal Base Screw Torque
7 pound-inches (0.6Nm)
Field Wiring Terminations
Module 1
0-A
2-B
4-Z
6 - Chassis ground
Mass
1.15 oz/32.60 grams
Publications
Installation Instructions
User Manual
1734-IN005A-EN-P
1734-UM006A-EN-P
Agency Certification
LISTED
C
1
Publication 1734-TD002B-EN-P - January 2001
1 - Aret
3 - Bret
5 - Zret
7 - Chassis ground
US
Class I, Division 2
Groups A, B, C, and D certified
Use this conductor category information for planning conductor routing as
described in publication 1770-4.1, “Industrial Automation Wiring and
Grounding Guidelines.”.
POINT I/O
24V dc Very High Speed Counter Module (Cat. No. 1734-VHSC24) 45
1734-VHSC24 Module
Specifications - 1734-VHSC24 Very High Speed Counter Module
Input Specifications
24V dc Very High Speed Counter Module (Cat. No. 1734-VHSC24)
Module Status
Network Status
Status of Input A
Number of Inputs
1 - 1 group of A/Areturn, B/Breturn and Z/Zreturn
Input Voltage
15-24V dc
Input Current
6.1mA @ 15V dc
10.2mA @ 24V dc
Input OFF-State Current
<0.250mA max
Input OFF-State Voltage
<1.8V dc
Input ON-State Current
>5mA
Status of Output 0
Input ON-State Voltage
>12.5V dc
Status of Output 1
Maximum ON-State Voltage
Refer to derating curve on page 46.
Input Filter Selections
Off
10µs
100µs
1.0ms
10.0ms
Maximum Input Frequency
1.0MHz counter and encoder X1 configurations
500kHz encoder X2 configuration (no filter)
250kHz encoder X4 configuration (no filter)
Status of Input B
Status of Input Z
0
0
1
1
Input A
Input Aret
Chas Gnd
Chas Gnd
Input B
Input Bret
RET 0
RET 1
Input Z
Input Zret
-Vaux
-Vaux
Number of Outputs
1 isolated group of 2 capable of 0.5A @ 24V dc
+Vaux
Output Control
Outputs can be tied to any of 4 compare windows
Out 0
Output Specifications
+Vaux
Out 1
Output Supply Voltage Range 10-28.8V dc
42443
Wiring
Module 1
0
2
1
A
Aret
B
Bret
3
4
6
Module 2
5
Z
Zret
Out
0
Out
1
7
0
2
1
Chas
Gnd
Chas
Gnd
RET
0
RET
1
-Vaux
-Vaux
+Vaux
+Vaux
4
<0.5mA
ON-State Voltage Drop
<0.3V dc @ 0.5A
ON-State Current
0.5A maximum
Short Circuit Current
6A - Outputs are short circuit protected and either
cycle until the fault is corrected, or latch off
(depending upon programming)
Short circuit detected when output is turned on.
Open Wire Detection
Open wire detected when output is turned off
Delay Time
OFF to ON
ON to OFF
25µs (load dependent)
150µs (load dependent)
3
5
6
OFF-State Leakage Current
7
42444
A, B, Z, Aret, Bret, and Zret = inputs
Chas Gnd = Chassis Ground
-Vaux = Auxiliary Supply
+Vaux = Auxiliary Supply
Publication 1734-TD002B-EN-P - January 2001
46 24V dc Very High Speed Counter Module (Cat. No. 1734-VHSC24)
Input Derating Curve
General Specifications
Module Location
1734-TB, -TBS, -TB3, -TB3S wiring base assembly
Keyswitch Position
2
Pointbus Current
180mA maximum
Power Dissipation
1.9W maximum @ rated load
Thermal Dissipation
6.5 BTU/hr maximum @ rated load
Isolation Voltage (minimum)
Prequalified for 1250V ac/rms between:
Module 1
System side (PointBus)
Chassis ground
A/B/Z inputs
O0/O1 and user power supply
Module 2
System side
Chassis ground
Vaux +
User power supply common
External dc Power (does not
represent power required to
supply outputs)
No additional external power required to power
module
Field Power Bus
24V dc nominal; range 10-28.8V dc
Dimensions
2.21H x 0.47W x 2.97L
(56.0H x 12.0W x 75.5L)
Inches
(Millimeters)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
Conductors Wire Size
Category
-20 to 55°C (-4 to 131°F)
-40 to 85°C (-40 to 185°F)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75°C or higher
3/64 inch (1.2mm) insulation maximum
22
Terminal Base Screw Torque
7 pound-inches (0.6Nm)
Field Wiring Terminations
Module 1
0-A
2-B
4-Z
6 - Output 0
Module 2
0 - Chassis ground
2 - Return 0
4 - -V
6 - +V
Mass
1.15 oz/32.60 grams
Publications
Installation Instructions
User Manual
1734-IN003B-EN-P
1734-UM003A-EN-P
Agency Certification
2
1 - Aret
3 - Bret
5 - Zret
7 - Output 1
1 - Chassis ground
3 - Return 1
5 - -V
7 - +V
LISTED
C
1
POINT I/O
US
Class I, Division 2
Groups A, B, C, and D certified
Off/on delay is time from a valid output “on” signal to output energization.
On/off delay is time from a valid output “off” signal to output deenergization.
Use this conductor category information for planning conductor routing as
described in publication 1770-4.1, “Industrial Automation Wiring and
Grounding Guidelines.”.
Publication 1734-TD002B-EN-P - January 2001
30
28.8
25
Input
Voltage
(V)
Input Voltage
24
20
15
10
5
10
20
30
40
Module Ambient Still Air Temperature (°C)
45
55
Note: Exceeding the maximum input voltage can cause permanent damage to the input.
POINT I/O
5V dc Very High Speed Counter Module (Cat. No. 1734-VHSC5) 47
1734-VHSC5 Module
Specifications - 1734-VHSC5 Very High Speed Counter Module
Input Specifications
5V dc Very High Speed Counter Module (Cat. No. 1734-VHSC5)
Number of Inputs
Module Status
Network Status
Status of Input A
Status of Input B
Status of Input Z
1 - 1 group of A/Areturn, B/Breturn and
Z/Zreturn
Input Voltage
5V dc
Input Current
19.1mA @ 5V dc
25.7mA @ 6V dc
Input OFF-State Current
<0.250mA max
0
0
Input OFF-State Voltage
<1.25V dc)
1
1
Input ON-State Current
>5mA
Input ON-State Voltage
>2.6V dc
Status of Output 0
Status of Output 1
1734VHSC5
Input A
Input Aret
Chas Gnd
Input B
Input Bret
RET 0
RET 1
Input Z
Input Zret
-Vaux
-Vaux
Out 1
+Vaux
+Vaux
Out 0
Module 1
0
2
A
Aret
B
Bret
4
6
Module 2
1
0
3
2
5
4
Z
Zret
Out
0
Out
1
7
1
Chas
Gnd
Chas
Gnd
RET
0
RET
1
Off
10µs
100µs
1.0ms
10.0ms
Maximum Input Frequency
1.0MHz counter and encoder X1 configurations
500kHz encoder X2 configuration (no filter)
250kHz encoder X4 configuration (no filter)
Output Specifications
Number of Outputs
1 isolated group of 2 capable of 0.5A @ 24V dc
Output Control
Outputs can be tied to any of 4 compare
windows
Output Supply Voltage Range
10-28.8V dc
OFF-State Leakage Current
<0.5mA
ON-State Voltage Drop
<0.3V dc @ 0.5A
ON-State Current
0.5A maximum
Short Circuit Current
6A - Outputs are short circuit protected and
either cycle until the fault is corrected, or latch
off (depending upon programming)
Short circuit detected when output is turned on.
Open Wire Detection
Open wire detected when output is turned off
Delay Time
OFF to ON
ON to OFF
25µs (load dependent)
150µs (load dependent)
3
5
-Vaux
-Vaux
+Vaux
+Vaux
6
+6V
Input Filter Selections
Chas Gnd
42445
Wiring
Maximum ON-State Voltage
7
42444
A, B, Z, Aret, Bret, and Zret = inputs
Chas Gnd = Chassis Ground
-Vaux = Auxiliary Supply
+Vaux = Auxiliary Supply
Publication 1734-TD002B-EN-P - January 2001
48 5V dc Very High Speed Counter Module (Cat. No. 1734-VHSC5)
General Specifications
Module Location
1734-TB, -TBS, -TB3, -TB3S wiring base
assembly
Keyswitch Position
2
Pointbus Current
180mA maximum
Power Dissipation
1.5W maximum @ rated load
Thermal Dissipation
5.1 BTU/hr maximum @ rated load
Isolation Voltage (minimum)
Prequalified at 1250V ac/rms between:
Module 1
System side
Chassis ground
A/B/Z inputs
O0/O1 and user power supply
Module 2
System side
Chassis ground
Vaux +
User power supply common
External dc Power
(does not represent power
required for outputs)
No additional external power required to power
module.
Field Power Bus
24V dc nominal; range 10-28.8V dc
Dimensions Inches
(Millimeters)
2.21H x 0.47W x 2.97L
(56.0H x 12.0W x 75.5L)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
-20 to 55°C (-4 to 131°F)
-40 to 85°C (-40 to 185°F)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
Conductors Wire Size
Category
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75°C or higher
3/64 inch (1.2mm) insulation maximum
22
Terminal Base Screw Torque
7 pound-inches (0.6Nm)
Field Wiring Terminations
Module 1
0-A
2-B
4-Z
6 - Output 0
Module 2
0 - Chassis ground
2 - Return 0
4 - -V
6 - +V
Mass
1.15 oz/32.60 grams
Publications
Installation Instructions
User Manual
1734-IN004B-EN-P
1734-UM003A-EN-P
Agency Certification
2
1 - Chassis ground
3 - Return 1
5 - -V
7 - +V
LISTED
C
1
1 - Aret
3 - Bret
5 - Zret
7 - Output 1
US
Class I, Division 2
Groups A, B, C, and D certified
Off/on delay is time from a valid output “on” signal to output energization.
On/off delay is time from a valid output “off” signal to output deenergization.
Use this conductor category information for planning conductor routing as
described in publication 1770-4.1, “Industrial Automation Wiring and
Grounding Guidelines.”.
Publication 1734-TD002B-EN-P - January 2001
POINT I/O
POINT I/O
24V dc, 120V ac, and 240V ac 2 Relay Sink/Source Output Module (Cat. No. 1734-OW2) 49
1734-OW2 Module
Load powered by External Power Bus
24V dc, 120V ac, and 240V ac 2 Relay Sink/Source Output Module (Cat. No. 1734-OW2)
Module
Status
Module Status
Network Status
0
Power
Supply
2
Network
Status
NODE:
0
Load
1
Status of Output 1
Out
0B
Out
1B
C
C
Output 1A Connection
Output 0B Connection
Output 1B Connection
ATTENTION
C
C
V
V
42081
V = Supply
Load power can be obtained from a variety of
sources, and can range from +5V dc to 240V ac,
depending on relay load.
Load powered by Internal Power Bus
0
Out
0A
Out 1
1A
2
Out
0B
Out 3
1B
C
C
V
V
Load
4
6
Power
Supply
3
6
7
Load
V
Out = Output channel relay contacts
V = Supply (can range from +5V dc to 240V ac)
C = Common
Output 0A Connection
C = Common
1
5
V
1734
OW2
Load
5
7
Out = Output channel relay contacts
V = Supply (can range from +5V dc to 240V ac)
C = Common
IMPORTANT
Out
1A
4
Relay
Output
Status of Output 0
Out
0A
!
42446
•Do not attempt to increase load current
or wattage capability beyond the
maximum rating by connecting 2 or
more outputs in parallel. The slightest
variation in relay switching time may
cause one relay to momentarily switch
the total load current.
•Make certain that all relay wiring is
properly connected before applying
any power to the module.
•Total current draw through the wiring
base unit is limited to 10A. Separate
power connections to the terminal
base unit may be necessary.
•Use the end cap from your adapter or
interface module to cover the exposed
interconnections on the last mounting
base on the DIN rail. Failure to do so
could result in equipment damage or
injury from electric shock.
42019
Relay contacts are not connected
to the internal power bus.
Publication 1734-TD002B-EN-P - January 2001
50 24V dc, 120V ac, and 240V ac 2 Relay Sink/Source Output Module (Cat. No. 1734-OW2)
Wiring with AC Modules Only
PDN
POINT I/O
Wiring Using External Power Source for AC
Relay Power
OW2 OW2
PDN
0
1
0
1
0
IB2
IB4
0
0
IV2
IV4
OW2 OW2 OW2
1
0
1
1
1
0
1
0
1
0
1
0
1
0
1
ac power bus
42008
120V ac
Wiring Using a 1734-FPD to Create a New AC
Power Bus
PDN
IB2
IV2 IB4 IV4
FPD
24V
L2/N L1
120V ac/240V ac
42010
OW2 OW2 OW2
Specifications - 1734-OW2
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
ac power
bus
C
V
L2/N
L1
42009
Publication 1734-TD002B-EN-P - January 2001
Outputs per Module
2 Form A isolated (normally open)
electromechanical relays
Off-State Leakage
Current (max at 240V ac)
1.2mA and bleed resistor thru snubber circuit
Output Voltage Range (load
dependent)
5-28.8V dc @ 2.0A resistive
48V dc @ 0.5A resistive
125V dc @ 0.25A resistive
125V ac @ 2.0A resistive
240V ac @ 2.0A resistive
Output Current Rating
(at rated power)
Resistive
2A @ 5-28.8V dc
0.5A @ 48V dc
0.25A @ 125V dc
2A @ 125V ac
2A @ 240V ac
Inductive
2.0A steady state @ 5-28.8V dc, L/R = 7ms
0.5A steady state @ 48V dc, L/R = 7ms
0.25A steady state @ 125V dc, L/R = 7ms
2.0A steady state, 15A make @ 125V ac,
PF = cos θ = 0.4
2.0A steady state, 15A make @ 240V ac,
PF = cos θ = 0.4
POINT I/O
24V dc, 120V ac, and 240V ac 2 Relay Sink/Source Output Module (Cat. No. 1734-OW2) 51
Specifications - 1734-OW2 (Continued)
General Specifications
Power Rating
(steady state)
Module Location
Output Signal Delay
OFF to ON
ON to OFF
Initial Contact Resistance
250W max. for 125V ac resistive output
480W max. for 240V ac resistive output
60W max. for 28.8V dc resistive output
24W max. for 48V dc resistive output
31W max. for 125V dc resistive output
250VA max. for 125V ac inductive output
480VA max. for 240V ac inductive output
60VA max. for 28.8V dc inductive output
24VA max. for 48V dc inductive output
31VA max. for 125V dc inductive output
10ms maximum (time from valid output on signal to
relay energization by module)
26ms maximum (time from valid output off
signal to relay deenergization by module)
80mA max @ 5V dc
Power Dissipation
0.5W max
Thermal Dissipation
1.7 BTU/hr max
Isolation Voltage
Between any 2 sets
of contacts
Customer load to logic
Field Power Bus
Supply Voltage
Voltage Range
Supply Current
Dimensions HxWxL
30mΩ
Switching Frequency
1 operation/3s (0.3Hz at rated load) max
Operate/Release Time
10ms max
Bounce Time
1.2ms (mean)
Minimum Contact Load
100µA at 100mV dc
Expected Life of
Electrical Contacts
Minimum 100,000 operations @ rated loads
Fusing
Module outputs are not fused. If fusing is desired,
you must supply external fusing.
Indicators
2 green/red module/network status
2 yellow output status
Keyswitch Position
7
1734-TB or -TBS wiring base assembly
Pointbus Current
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
Conductors Wire Size
Category
2550V dc for 1s
2550V dc for 1s
None required
240V ac max
2A per channel maximum, 4A per module
56.0mm x 12.0mm x 75.5mm
(2.21in x 0.47in x 2.97in)
-20 to +55oC (-4 to +131oF)
-40 to 85oC (-40 to 185oF)
5 to 95% noncondensing
12g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75°C or higher
3/64 inch (1.2mm) insulation maximum
22
Terminal Base Screw Torque
7 pound-inches (0.6 Nm)
Field Wiring Terminations
0 - Output 0A
2 - Output 0B
4 - Common
6 - Supply
Mass
1.30 oz/36.86 grams
Publication
Installation Instructions
1734-IN055B-EN-P
Agency Certification
LISTED
C
1
1 - Output 1A
3 - Output 1B
5 - Common
7 - Supply
US
Class I, Division 2
Groups A, B, C, and D certified
Use this conductor category information for planning conductor routing. Refer to
publication 1770-4.1, “Industrial Automation Wiring and Grounding Guidelines.”
Publication 1734-TD002B-EN-P - January 2001
52 Field Power Distributor (Cat. No. 1734-FPD)
POINT I/O
1734-FPD Field Power Distributor
Wiring
Field Power Distributor (Cat. No. 1734-FPD)
0
120/240V ac
1
NC
2
NC
Chas Chas
Gnd Gnd
4
3
5
L2/N
L2/N
L1
L1
V ac
6
NC
7
NC = No Connection Chas Gnd = Chassis Ground
C = Common
V = 12/24V dc
NC
Chas Gnd
This supply will be
connected to the
internal power bus.
Chas Gnd
C
C
V
V
42447
NC = No Connection
C = Common
Chas Gnd = Chassis Ground
V = Supply
Connect
Terminal
L1
6
L2/N
4
Chas Gnd
2
120/240V ac becomes the internal power bus
for modules to the right.
Wiring
0
12/24V dc
1
NC
2
4
NC
Chas Chas
Gnd Gnd
C
C
3
5
V dc
6
V
V
This supply will be
connected to the
internal power bus.
7
NC = No Connection Chas Gnd = Chassis Ground
C = Common
V = 12/24V dc
Connect
Terminal
+V dc
6
-V dc
4
Chas Gnd
2
12/24V dc becomes the internal power bus for
modules to the right.
Publication 1734-TD002B-EN-P - January 2001
30880
42067
POINT I/O
Field Power Distributor (Cat. No. 1734-FPD) 53
Wiring Using a 1734-FPD to Create a New
AC Power Bus
Specifications - 1734-FPD
Input Voltage Rating
12V dc, 24V dc nominal
10-28.8V dc range
120V ac, 240V ac nominal
Input Current
10A maximum
Indicators
None
Module Location
Between I/O modules in 1734 system
Breaks power bus
PDN
FPD
IB2 IB4 OB2E IV4
OW2 OW2 OW2
General Specifications
Pointbus Current
Pass through
Power Consumption
None
Power Dissipation
None
Thermal Dissipation
None
Isolation Voltage
1528V rms/V ac
Field Power Bus
Supply Voltage
Supply Current
Dimensions HxWxL
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
Conductors Wire Size
Category
264V ac maximum,
12V dc, 24V dc, 10-28.8V dc range
120V ac, 240V ac 50/60 Hz
10A maximum
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
76.2mm x 25.4mm x 133.4mm
(3.00in x 1.00in x 5.25in)
-20 to +55oC (-4 to +131oF)
-40 to 85oC (-40 to 185oF)
5 to 95% noncondensing
12g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 2g @ 10-500Hz per IEC 68-2-6
ac power
bus
C
V
L2/N
L1
42009
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75°C or higher
3/64 inch (1.2mm) insulation maximum
22
Terminal Base Screw Torque
7 pound-inches (0.6Nm)
Field Wiring Terminations
0 - No Connection
2 - Chassis Ground
4 - Common
6 - Supply
Mass
4.38 oz/124.17 grams
Publication
Installation Instructions
1734-IN059B-EN-P
Agency Certification
1 - No Connection
3 - Chassis Ground
5 - Common
7 - Supply
LISTED
C
1
0
US
Class I, Division 2
Groups A, B, C, and D certified
Use this conductor category information for planning conductor routing. Refer
to publication 1770-4.1, “Industrial Automation Wiring and Grounding
Guidelines.”
Publication 1734-TD002B-EN-P - January 2001
54 Field Power Distributor (Cat. No. 1734-FPD)
POINT I/O
Wiring Using a 1734-FPD to Create a New
Analog Power Bus
Wiring Using a 1734-FPD to Create a New
DC Power Bus
This configuration isolates noisy discrete I/O
power from sensitive analog I/O power.
This configuration changes power bus voltage for
12/24V dc systems.
PDN
0
IB2 IB4 OB2E OB4E
1
0
1
0
1
0
1
0
1
FPD
0
PDN
IE2C IE2C OE2C OE2C
1
0
1
0
1
0
1
0
0
1
IB2 IB4 OB2E OB4E
1
0
1
0
1
0
1
0
1
FPD
0
IB2 IB4
1
0
1
0
IV2 OB4E
1
0
1
V
C
Discrete I/O
Power Bus
24V
Publication 1734-TD002B-EN-P - January 2001
Analog I/O
Power Bus
42448
1
12V dc
24V dc
C
0
V
Discrete I/O
Power Bus
12V
Discrete I/O
Power Bus
42449
POINT I/O
24V dc Expansion Power Supply (Cat. No. 1734-EP24DC) 55
1734-EP24DC Expansion Power Supply
Module Location
Between I/O modules in 1734 system
Breaks field power bus
Limitations
Use with POINT I/O adapters only
24V dc Expansion Power Supply (Cat. No. 1734-EP24DC)
General Specifications
Power Consumption
9.8W maximum @ 28.8V dc
Power Dissipation
3.0W maximum @ 28.8V dc
Thermal Dissipation
10.0 BTU/hr maximum @ 28.8V dc
Isolation Voltage
1250V rms/V ac
Field Power Bus
Supply Voltage
Supply Current
12V dc, 24V dc, 10-28.8V dc range
10A maximum
Dimensions HxWxL
NC
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
NC
Chas Gnd
Chas Gnd
C
C
V
V
Conductors Wire Size
NC = No ConnectionChas Gnd = Chassis Ground
C = CommonV = Supply
Wiring
0
Do not connect
120/240V ac
power to this
supply.
1
NC
NC
2
3
4
V dc
6
V
C
V
7 pound-inches (0.6 Nm)
Field Wiring Terminations
0 - No Connection
2 - Chassis Ground
4 - Common
6 - Supply Voltage
Mass
4.38 oz/12.42 grams
Publications
Installation Instructions
1734-IN058A-EN-P
1
5
C
Terminal Base Screw Torque
Agency Certification (when
product is marked)
Chas Chas
Gnd Gnd
7
This dc supply will be
connected to the
internal power bus.
V = 12/24V dc, C = Common
CHAS GND = Chassis ground
30880
-20 to +85oC (-4 to +185oF)
-40 to 85oC (-40 to 185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or
stranded wire rated at 75°C or higher
3/64 inch (1.2mm) insulation maximum
22
Category
42450
12/24V dc
76.2mm x 25.4mm x 133.4mm
(3.00in x 1.00in x 5.25in)
1 - No Connection
3 - Chassis Ground
5 - Common
7 - Supply Voltage
Class I Division 2 certified
Groups A, B, C, D certified
Use this conductor category information for planning conductor routing as
described in publication 1770-4.1, “Industrial Automation Wiring and
Grounding Guidelines.”
Current Derating for Mounting
1.3
1.0
Specifications - 1734-EP24DC
I/O Module Capacity
12 modules
Power Supply
Note: In order to comply with CE Low Voltage
Directives (LVD), you must use a Safety Extra Low
Voltage (SELV) or a Protected Extra Low Voltage
(PELV) power supply to power this adapter.
Input Voltage Rating
24V dc nominal
10-28.8V dc range
Field Side Power
Requirements
24V dc (+20% = 28.8V dc maximum) @ 400mA
maximum
Inrush Current
6A maximum for 10ms
Indicators
1 green field power status indicator
1 green 5V system power indicator
POINTBus Output Current
Horizontal mounting - 1A @ 10-19.2V input
1.3A @ 19.2-28.8V in
Vertical mounting - 1A @ 10-28.8V input
Current
0.5
10
Horizontal - 1A @ (10-19.2V); 1.3A @ (19.2-28.8V)
Vertical - 1A @ (10-28.8V)
19.2
Voltage
28.8
41959
Input Overvoltage Protection Reverse polarity protected
Interruption
Output voltage will stay within specifications when
input drops out for 10ms at 10V with maximum load.
Publication 1734-TD002B-EN-P - January 2001
56 24V dc Expansion Power Supply (Cat. No. 1734-EP24DC)
POINT I/O
Example of Continuing Power
ADN
Example of Logical Partitioning
EP24DC
IB2
Adapter
Status
IB4
OB2EOB4E
ADN
EP24DC
IE2C OE2C IB2 OB2E
IE2C IE2C OE2C
IB2 OB2E OB4E
Adapter
Status
DeviceNet
Status
DeviceNet
Status
PointBus
Status
PointBus
Status
1734-EP24DC
1734-ADN
1734-EP24DC
1734-ADN
System
Power
DeviceNet
Power
System
Power
DeviceNet
Power
System
Power
System
Power
DeviceNet
Power
DeviceNet
Power
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
12/24V dc only
Example of continued power.
42451
The EP24DC expansion power
supply can only be used with
POINT I/O adapters.
IMPORTANT
Example of Functional Partitioning
ADN
EP24DC
IB2
IB4
OB2EOB4E
IE2C IE2C OE2C
Adapter
Status
DeviceNet
Status
PointBus
Status
1734-EP24DC
1734-ADN
System
Power
System
Power
DeviceNet
Power
DeviceNet
Power
0
1
0
1
0
1
0
1
0
1
0
1
12/24V dc
Digital Supply
Publication 1734-TD002B-EN-P - January 2001
0
1
0
1
12/24V dc
Analog
Supply
42452
1
24V dc Supply
0
1
0
1
0
1
0
1
0
1
0
1
0
1
12V dc
Supply
42453
POINT I/O
57
Related Publications
For electronic copies of these publications, go to:
http://www.theautomationbookstore.com
Catalog Number
Description
Communication
Adapter
DeviceNet Adapter (Cat. No. 1734-ADN)
Installation Instructions
Communication
Interface
DeviceNet Interface (Cat. No. 1734-PDN)
Installation Instructions
1734-IN057B-EN-P
1734D Series
1734D Series 24V dc 8 In/8 Out Combo Module (Cat. No. 1734D-IB8XOB8E,
-IB8XOB8ES)
Installation Instructions
1734-5.20
1734D Series 24V dc 8 In/8 N.O. Relay Combo Module (Cat. No.
1734D-IB8XOW8, -IB8XOW8S)
Installation Instructions
1734-5.21
1734D Series 120V ac 8 In/8 Out Combo Module (Cat. No. 1734D-IA8XOA8,
-IA8XOA8S)
Installation Instructions
1734-5.22
1734D Series 120V ac 8 In/8 N.O. Relay Combo Module (Cat. No.
1734D-IA8XOW8, -IA8XOW8S)
Installation Instructions
1734-5.23
Wiring Base Assembly with 8 Screw-Clamp or Spring-Clamp Removable
Terminal Blocks (Cat Nos. 1734-TB, -TBS)
Installation Instructions
1734-IN511A-EN-P
Wiring Base Assembly with 12 Screw-Clamp or Spring-Clamp Removable
Terminal Blocks (Cat Nos. 1734-TB3, -TB3S)
Installation Instructions
1734-IN013A-EN-P
120V ac 2 Input Module (Cat. No. 1734-IA2)
Installation Instructions
1734-IN010A-EN-P
120/220V ac 2 Output Module (Cat. No. 1734-OA2)
Installation Instructions
1734-IN009A-EN-P
220V ac 2 Input Module (Cat. No. 1734-IM2)
Installation Instructions
1734-IN008A-EN-P
24V dc 2 Input Sink Module (Cat. No. 1734-IB2)
Installation Instructions
1734-IN051B-EN-P
24V dc 4 Input Sink Module (Cat. No. 1734-IB4)
Installation Instructions
1734-IN051B-EN-P
24V dc 2 Input Source Module (Cat. No. 1734-IV2)
Installation Instructions
1734-IN052B-EN-P
24V dc 4 Input Source Module (Cat. No. 1734-IV4)
Installation Instructions
1734-IN052B-EN-P
24V dc Electronically Protected 2 Point Output Module (Cat. No.
1734-OB2E)
Installation Instructions
1734-IN056B-EN-P
24V dc Electronically Protected 4 Point Output Module (Cat. No. 1734-0B4E)
Installation Instructions
1734-IN056B-EN-P
24V dc Analog 2 Current Input Module (Cat. No. 1734-IE2C/B)
Installation Instructions
1734-IN053C-EN-P
24Vdc Analog 2 Current Output Module (Cat. No. 1734-OE2C/B)
Installation Instructions
1734-IN054C-EN-P
24V Encoder/Counter Module (Cat. No. 1734-IK)
Installation Instructions
User Manual
1734-IN006A-EN-P
1734-UM006A-EN-P
5V Encoder/Counter Module (Cat. No. 1734-IJ)
Installation Instructions
User Manual
1734-IN005A-EN-P
1734-UM006A-EN-P
24V dc Very High Speed Counter Module (Cat. No. 1734-VHSC24)
Installation Instructions
User Manual
1734-IN003B-EN-P
1734-UM003A-EN-P
5V dc Very High Speed Counter Module (Cat. No. 1734-VHSC5)
Installation Instructions
User Manual
1734-IN004A-EN-P
1734-UM003A-EN-P
Relay Module
24V dc, 120V ac, and 240V ac 2 Relay Sink/Source Output Module (Cat. No.
1734-OW2)
Installation Instructions
1734-IN055B-EN-P
Field Power
Distributor
Field Power Distributor (Cat. No. 1734-FPD)
Installation Instructions
1734-IN059B-EN-P
Expansion Power
Supply
24V dc Expansion Power Supply (Cat. No. 1734-EP24DC)
Installation Instructions
1734-IN058A-EN-P
Wiring Base
Assemblies
AC Modules
DC Modules
Analog Modules
Counter Modules
Related Publications
1734-IN007A-EN-P
Publication 1734-TD002B-EN-P - January 2001
58 Mounting Dimensions
POINT I/O
POINT I/O with a 1734-ADN Mounting Dimensions
Mounting Dimensions
L = 2.16 + [# of I/O x 0.47] + [# of EP24DC or FPD x 1.0] in.
Allow a 25.4 (1.0)
Air Gap All Around
L = 54.9 + [# of I/O x 12.0] + [# of EP24DC or FPD x 25.4] mm
Adapter
Status
DeviceNet
Status
PointBus
Status
133.4
(5.25)
1734-ADN
System
Power
Field
Power
mm (in)
30880
1734-ADN (HxWxL)
76.2 (3.0) x 54.9 (2.16) x 133.4 (5.25)
1734-EP24DC or FPD (HxWxL)
76.2 (3.0) x 25.4 (1.0) x 133.4 (5.25)
ATTENTION
!
Publication 1734-TD002B-EN-P - January 2001
1734-TB or -TBS with I/O (HxWxL)
76.2 (3.0) x 12.0 (0.47) x 133.4 (5.25)
POINT I/O is designed to be grounded through the
DIN rail to chassis ground. To assure proper
grounding of POINT I/O adapters and terminal bases
to chassis ground, the recommended DIN rail
material is zinc-plated, yellow-chromated steel.
Mount POINT I/O adapters and terminal bases only
to zinc-plated, yellow-chromated steel.
POINT I/O
Mounting Dimensions 59
POINT I/O with a 1734-PDN Mounting Dimensions
L = 1.0 + [# of I/O x 0.47] + [# of FPD x 1.0] in.
Allow a 25.4 (1.0) Air
Gap All Around
L = 25.4 + [# of I/O x 12.0] + [# of FPD x 25.4] mm
133.4
(5.25)
mm (in)
42100
1734-PDN (HxWxL)
76.2 (3.0) x 25.4 (1.0) x 133.4 (5.25)
ATTENTION
!
1734-FPD (HxWxL)
76.2 (3.0) x 25.4 (1.0) x 133.4 (5.25)
1734-TB or -TBS with I/O (HxWxL)
76.2 (3.0) x 12.0 (0.47) x 133.4 (5.25)
POINT I/O is designed to be grounded through the
DIN rail to chassis ground. To assure proper
grounding of POINT I/O adapters and terminal bases
to chassis ground, the recommended DIN rail
material is zinc-plated, yellow-chromated steel.
Mount POINT I/O adapters and terminal bases only
to zinc-plated, yellow-chromated steel.
Mounting Dimensions
Publication 1734-TD002B-EN-P - January 2001
60 Mounting Dimensions
POINT I/O
1734D Mounting Dimensions
Mounting Dimensions
L = 2.36 + [# of I/O x 0.47] + [# of FPD x 1.0] in.
Allow a 25.4 (1.0) Air
Gap All Around
L = 60.0 + [# of I/O x 12.0] + [# of FPD x 25.4] mm
133.4
(5.25)
1
mm (in)
30977
1734D (HxWxL)
76.2 (3.0) x 60.0 (2.36) x 133.4 (5.25)
ATTENTION
!
POINT I/O Marker Card
A marker card is available under catalog number 1492-SM5X5. Each
kit contains five 5x5 cards with 100 markers per card.
Support Services
Publication 1734-TD002B-EN-P - January 2001
POINT I/O is designed to be grounded through the
DIN rail to chassis ground. To assure proper
grounding of POINT I/O adapters and terminal bases
to chassis ground, the recommended DIN rail
material is zinc-plated, yellow-chromated steel.
Mount POINT I/O adapters and terminal bases only
to zinc-plated, yellow-chromated steel.
POINT I/O
Support Services
Support Services 61
At Allen-Bradley, customer service means experienced representatives
at Customer Support Centers in key cities throughout the world for
sales, service, and support. Our value-added services include:
Technical Support
•
•
•
•
SupportPlus programs
Telephone support and 24-hour emergency hotline
Software and documentation updates
Technical subscription services
Engineering and Field Services
•
•
•
•
Application engineering assistance
Integration and start-up assistance
Field service
Maintenance support
Technical Training
•
•
•
•
Lecture and lab courses
Self-paced computer and video-based training
Job aids and workstations
Training needs analysis
Repair and Exchange Services
•
•
•
•
Your only “authorized” source
Current revisions and enhancements
Worldwide exchange inventory
Local support
Publication 1734-TD002B-EN-P - January 2001
POINT I/O, PointBus, and RSNetWorx are trademarks of Rockwell Automation.
DeviceNet is a trademark of Open DeviceNet Vendor Association (O.D.V.A.).
Publication 1734-TD002B-EN-P - January 2001 64
Supersedes Publication 1734-TD002A-EN-P - July 2000
© 2001 Rockwell International Corporation. Printed in the U.S.A.