Download Installation Manual - livezi living home
Transcript
Installation Manual Horizontal Discharge Inverter Outdoor Variable Airflow EC Quick Split Indoor Installation Manual CONTENTS PRECAUTIONS1 INSTALLATION INFORMATION 2 ACCESSORIES3 INSPECTING AND HANDLING THE UNIT 4 INDOOR UNIT INSTALLATION 4 OUTDOOR UNIT INSTALLATION 11 INSTALL THE CONNECTING PIPE 13 CONNECT THE DRAIN PIPE 15 CONTROL16 WIRING16 TEST OPERATION 17 1. PRECAUTIONS Be sure to conform with the local, national and international laws and regulations. Read “PRECAUTIONS” carefully before installation. The following precautions include important safety items. Observe them and never forget. Keep this manual with the owner’s manual in a handy place for future reference. Install strictly according to these installation instructions. If installation is defective, it may cause water leakage, electrical shock fire. When installing the unit in a small room, take measures to keep refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage. Contact the place of purchase for more information. Excessive refrigerant in a closed ambient can lead to oxygen deficiency. Use the attached accessories parts and specified parts for installation. Install at a strong and firm location which is able to withstand the set’ s weight. If the strength is not enough or installation is not properly done, the set will drop to cause injury. The appliance must be installed at least 2.5m above floor. The appliance shall not be installed in the laundry. Before obtaining access to terminals, all supply circuits must be disconnected. For electrical work, follow the local national wiring standard, regulation and this installation instructions. An independent circuit must be used. If electrical circuit capacity is insufficient or there is a defect in electrical work, it may cause electrical shock and/or fire. Use the specified cable and connect tightly and clamp the cable so that cable is protected from external force. If connection or fixing is not perfect, it may cause heating/arcing or fire at the connection. Wiring routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock. The safety precautions listed here are divided into two categories. In either case, important safety information is listed which must be read carefully. An all-pole disconnection device which has at least 3mm separation distance in all pole and a residual current device (RCD) with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule. WARNING When carrying out piping connection, take care not to let air substances go into refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury. Failure to observe a warning may result in death. CAUTION Failure to observe a caution may result in injury or damage to the equipment.. Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes. Improper installation work may result in the equipment falling and causing accidents. After completing the installation, make sure that the unit operates properly during the start-up operation. Please instruct the customer on how to operate the unit and keep it maintained. Inform customers that they should store this installation manual along with the owner’s manual for future reference. WARNING Be sure only trained and qualified service personnel to install, repair or service the equipment. Improper installation, repair, and maintenance may result in electric shocks, short-circuit, leaks, fire or other damage to the equipment.Ask your dealer for improvement, repair, and maintenance. P 1300 306 125 (FREECALL) | F 07 3890 8730 | E [email protected] | A 1/49 Miller Street,Murrarie Qld 4172 2 Installation Manual If the refrigerant leaks during installation, ventilate the area immediately. Toxic gas may be produced if the refrigerant comes into the place contacting with fire. The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube. After completing the installation work, check that the refrigerant does not leak. Toxic gas may be produced if the refrigerant leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker. 2. INSTALLATION INFORMATION at first. The air conditioner must be installed by qualified persons. When installing the indoor unit or its tubing, please follow this manual as strictly as possible. CAUTION Ground the air conditioner. Do not connect the ground wire to gas or water pipes, lightning rod or a telephone ground wire. Incomplete grounding may result in electric shocks. To install properly, please read this “installation manual” If the air conditioner is installed on a metal part of the building, it must be electrically insulated according to the relevant standards to electrical appliances. When all the installation work is finished, please turn on the power only after a thorough check. We reserve the right to make changes to this document. Be sure to install an earth leakage breaker. Failure to install an earth leakage breaker may result in electric shocks. Connect the outdoor unit wires, then connect the indoor unit wires. You are not allow to connect the air conditioner with the power source until wiring and piping the air conditioner is done. INSTALLATION ORDER While following the instructions in this installation manual, install drain piping in order to ensure proper drainage and insulate piping in order to prevent condensation. Improper drain piping may result in water leakage and property damage. Select the location; Install the indoor unit; Install the outdoor unit; Install the indoor and outdoor units, power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise. Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise. Install the connecting pipe ; Connect the drain pipe; Wiring; The appliance is not intended for use by persons(including children) with reduced physical,sensory or mental capabilities,or lack of experience and knowledge,unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Test operation. Don’t install the air conditioner in the following locations: There is petrolatum existing. Corrosive environments. There is caustic gas (the sulfide, for example) existing in the air (near a hot spring). The Volt vibrates violently (in the factories). In buses or cabinets. In kitchen where it is full of oil gas. There is strong electromagnetic wave existing. There are inflammable materials or gas. There is acid or alkaline liquid evaporating. Other special conditions. P 1300 306 125 (FREECALL) | F 07 3890 8730 | E [email protected] | A 1/49 Miller Street,Murrarie Qld 4172 3 Installation Manual Indoor Units Dimension 1HZ FRQFUHWH EULFNV Length H-VAV-7 H-VAV-11 H-VAV-15 2YHUKDQJLQJ WKHLQGRRU XQLW 1200 1400 856 2YHUKDQJWKH LQGRRU XQLW RQWR WKH KDQJLQJ VFUHZ EROWV ZLWK EORFN 808 808 3RVLWLRQWKH LQGRRU XQLW LQ D IODW OHYHO E\ XVLQJ WKH OHYHO LQGLFDWRU400 XQOHVV LW PD\ FDXVH OHDNDJH 400 ,QOD\LQJ RU HPEHGGLQJ WKH VFUHZ EROWV 5HIHUWR)LJ Width 808 Hieght 400 %ODGH VKDSH LQVHUWLRQ Weight 6OLGH LQVHUWLRQ Supply Air 51 71 )LJ 305 x 225 905 x 255 Return Air 515 x 345 )RU 2ULJLQDO FRQFUHWHEULFNV Notes 1105 x 255 1200 x 345 2YHUKDQJ SDUW )LJ 6WHHO EDU (PEHGGLQJ VFUHZ EROW 'LDJUDPPDWLF VNHWFK IRU ,QVWDOOLQJ All units split into two parts. 3LSH KDQJLQJ DQG HPEHGGLQJ VFUHZ EROW Supply and Return air sizes are designed for Airtite series plenums.WKH PDLQ ERG\ )LJ Field or installation wiring must be connected as per the connection diagram to ensure the unit performs as it is ,QVWDOOLQJ WKHGXVW SURRIQHW DQG FDQYDV DLUSDVVDJH designed. ,QVWDOO WKH GXVW SURRI QHW DFFRUGLQJWRWKH LQVWDOODWLRQ PDQXDO Installer electrician is to ensure that when an external overload device is fitted, it be calibrated or set to the /6WHHOURRIEHDP VWUXFWXUH ,QVWDOO WKH FDQYDV DLU SDVVDJH XQGHUQHDWK WKH GXVW SURRI QHW maximum amp draw on the rating plate of the motor it is controlling. 3LSH &RQQHFWLRQ ,QVWDOO DQG XVH GLUHFWO\WKH VXSSRUWLQJ DQJOH VWHHO 5HIHUWR )LJ 7KH VWDWLF SUHVVXUH LQWKH RXWVLGH RI WKH XQLW LV 3D PD[LPXP 3D WKH OHQJWK RIWKH DLU SLSH DWWDFKHG LV GHWHUPLQHG E\ WKLV SDUDPHWHU +DQJLQJ VFUHZ EROW +DQJLQJ EROWV 6XSSRUWLQJ DQJOH VWHHO )LJ 7KH SRVLWLRQLQJ RI FHLOLQJKROH DQG LQGRRU XQLW DQGKDQJLQJ VFUHZ EROWV URXWLQH PHWKRG RI LQVWDOODWLRQ WKH VL]H RI LQVWDOODWLRQ IRU LQGRRU XQLW IROORZLQJ WKH )LJ DQG )LJ %WXK %WXK 8QLW PP H-VAV-7 • +DQJLQJ VFUHZ EROW (QWUDQFHV DQG H[LWV IRU FRPPXQLFDWLRQ OLQHV RI LQGRRU DQG RXWGRRU $LU RXWOHW REORQJ VXVSHQWLRQ EROW KROHV (OHFWULFDO SDUWV ER[ $LU RXWOHW GXFW IODQJH KROHV IRU DLU RXWOHW GXFW FRQQHFWLRQ • • • 1000 :DVKHU x 345 8VH HPEHGGLQJ VFUHZ EROG FURFN DQG VWLFN KDUQHVV 5HIHU WR )LJ 84 6FUHZ QXW $LU LQWDNH GXFW IODQJH &RQQHFWLQJ SRLQW RI GUDLQ SLSH KROHV IRU DLU LQWDNH GXFW FRQQHFWLRQ $LU LQWDNH )LJ P 1300 306 125 (FREECALL) | F 07 3890 8730 | E [email protected] | A 1/49 Miller Street,Murrarie Qld 4172LQVWDOODWLRQ PDQXDO 3') SGI)DFWRU\3UR ZZZILQHSULQWFQ 5 4 Installation Manual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| F 07 3890 8730 | E [email protected] | A 1/49 Miller Street,Murrarie Qld 4172 5 Installation Manual 7DEOH 7DEOH model 02'(/ $ 02'(/ A% $ B & % 7kW 895 590 7DEOH 990 624 11kW 02'(/ 940 $ 600% 15kW D ( & ' E ) PP F + ( H 5(0$5. ) + 333 355 302 313 862 PP remark 5(0$5. 366 396 340 354 R410A 966 Fig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ll the pictures thisDQG manual are for purpose $OO WKHinSLFWXUHV LQ WKLV PDQXDO DUHexplanation IRU H[SODQDWLRQ SXUSRVH only RQO\ 0RYLQJ LQVWDOODWLRQ 7KH\ PD\ EH VOLJKWO\ from GLIIHUHQW WKH DLU FRQGLWLRQHU They may be slightly different theIURP air conditioner you \RX 6LQFH WKH JUDYLW\ FHQWHU RIFHQWHU WKH XQLW LV DFWXDO QRW DWLVVKDSH LWV SK\VLFDO SXUFKDVHGGHSHQG RQ PRGHO7KH VKDOO SUHYDLO 6LQFH WKHon JUDYLW\ RIactual WKH XQLW QRW DW LWV SK\VLFDO purchased(depend model).The shape shall prevail. FHQWHU VR SOHDVH EH FDUHIXO ZKHQ OLIWLQJ LW ZLWK D VOLQJ H H NOTE FHQWHU VR SOHDVH EH FDUHIXO ZKHQ OLIWLQJ LW ZLWK D VOLQJ H 1HYHU WKHKROG LQOHW RI WKH RXWGRRU XQLW WR SUHYHQW LW IURP 6.2 Moving and installation KROG 0RYLQJ DQG LQVWDOODWLRQ 1HYHU WKH LQOHW RI WKH RXWGRRU XQLW WR SUHYHQW • $ $ $ % please be careful when lifting it with a sling. 'R QRW OHDQ LW PRUHWKDQ DQG GR QRW OD\ LW VLGHORQJ GHIRUPLQJ Never hold the inlet of the outdoor unit to prevent it from 0DNH FRQFUHWH IRXQGDWLRQ DFFRGLQJDFFRGLQJ WR WKH VHSHFLILFDWLRQV RI 0DNH FRQFUHWH IRXQGDWLRQ WR WKH VHSHFLILFDWLRQV RI deforming. • Do not touch the fan with hands or other objects. • Do not FROODSVLQJ lean it more thanRI45, and do not lay it sidelong. FROODSVLQJ LQ FDVH RI FDVH HDUWKTXDNH RU VWURQJ WR LQ HDUWKTXDNH RU ZLQG5HIHU VWURQJ ZLQG5HIHU • so 1HYHU KROGLW PRUHWKDQ WKH LQOHW RIWKH RXWGRRU XQLWLW WR SUHYHQW LW IURP 'R QRW OHDQ DQG GR QRW OD\ VLGHORQJ • • )LJ )LJ LW IURP GHIRUPLQJ GHIRUPLQJ 6LQFH WKH JUDYLW\ FHQWHU RI WKH XQLW LV QRW DW LWV SK\VLFDO 'R QRW WRXFK WKHIDQ ZLWK KDQGV RUKDQGV RWKHU REMHFWV FHQWHU VR center SOHDVH EH FDUHIXO ZKHQ OLIWLQJ LW ZLWK D VOLQJ center, 'R QRW WRXFK WKHIDQ ZLWK RUisRWKHU Since the gravity of the unit not REMHFWV at its physical WKH RXWGRRU 'RXQLWV5HIHUWR)LJ QRW WRXFK WKHIDQ ZLWK KDQGV RU RWKHU REMHFWV WKH RXWGRRU XQLWV5HIHUWR)LJ )DVWHQ WKH IHHW RIOHDQ WKLV ZLWKXQLW EROWV ILUPO\ WRQRW SUHYHQW LWSUHYHQW IURP LW IURP 'R QRWWKH LWXQLW PRUHWKDQ DQG GR OD\WR LW VLGHORQJ )DVWHQ IHHW RI WKLV ZLWK EROWV ILUPO\ WR )LJ )LJ 0DNH FRQFUHWH IRXQGDWLRQ DFFRGLQJ WKHsepecif-ications VHSHFLILFDWLRQV RIof Make concrete foundation accoding to WR the WKH RXWGRRU XQLWV5HIHUWR)LJ outdoor units.(Refer to Fig.6-6) the )DVWHQ WKLVwith XQLW ZLWK EROWV ILUPO\to WRprevent SUHYHQW LWitIURP Fasten the feetWKH of IHHW thisRIunit bolts firmly from FROODSVLQJ LQ FDVH RI HDUWKTXDNH RU VWURQJ ZLQG5HIHU WR collapsing in case of earthquake or strong wind.(Refer toFig.6-6) )LJ % )LJ % )L[ ZLWK EROW )L[ ZLWK EROW )L[ ZLWK EROW )LJ )LJ 127(127( )LJ )LJ NOTE $OO WKH SLFWXUHV LQ WKLV PDQXDO DUH IRU H[SODQDWLRQ SXUSRVH RQO\ 7KH\ PD\ EH VOLJKWO\ GLIIHUHQW IURP WKH DLU FRQGLWLRQHU 12 12 \RX SXUFKDVHGGHSHQG RQ PRGHO7KH DFWXDO VKDSH VKDOO SGI)DFWRU\3UR ZZZILQHSULQWFQ 3') SGI)DFWRU\3UR ZZZILQHSULQWFQ All the pictures in this manual are for explanation purpose only SUHYDLO LQVWDOODWLRQ LQVWDOODWLRQ PDQXDO PDQXDO 3') $OO WKH SLFWXUHV LQ WKLV PDQXDO DUH IRU H[SODQDWLRQ SXUSRVH SXUSRVH $OO WKH SLFWXUHV LQ WKLV PDQXDO DUH IRU H[SODQDWLRQ )LJ RQO\ 7KH\ PD\ EH PD\ VOLJKWO\ IURP WKHIURP DLU FRQGLWLRQHU RQO\ 7KH\ EH GLIIHUHQW VOLJKWO\ GLIIHUHQW WKH DLU FRQGLWLRQHU \RX SXUFKDVHGGHSHQG RQ PRGHO7KH DFWXDO VKDSH \RX SXUFKDVHGGHSHQG RQ PRGHO7KH DFWXDO VKDOO VKDSH VKDOO SUHYDLO SUHYDLO 127( LQVWDOODWLRQ PDQXDO 3') 12 )LJ They may be slightly different from the air conditioner you purchased(depend on model).The actual shape shall prevail. P 1300 306 125 (FREECALL) | F 07 3890 8730 | E [email protected] | A 1/49 Miller Street,Murrarie Qld 4172 SGI)DFWRU\3UR ZZZILQHSULQWFQ 6 ,QVWDOO WKH FRQQHFWLQJ SLSH &$87,21 &KHFN ZKHWKHU WKH KHLJKW GURS EHWZHHQ WKH LQGRRU XQLW DQG RXWGRRU XQLW WKH OHQJWK RI UHIULJHUDQW SLSH DQG WKH QXPEHU RI WKH EHQGV PHHW WKH IROORZLQJ UHTXLUHPHQWV Installation Manual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heck whether theWKH height between indoorDQG and RI dropRI QXPEHU %H VXUH WR ZLWK LQVXODWLQJ PDWHULDOV FRYHU DOO WKH H[SRVHG unitWKH the RXWGRRU XQLW OHQJWK UHIULJHUDQW SLSH XQLWWKH LV WRSIROORZLQJ 7KH PD[ KHLJKW SDUWV RI WKH IODUH SLSH MRLQWV DQG UHIULJHUDQW SLSH RQ WKH WKH EHQGV PHHW UHTXLUHPHQWV outdoor unit, the length of refrigerant pipe, and the number of the SDUWV RI WKH IODUH SLSH MRLQWV DQG UHIULJHUDQW SLSH RQ WKH WKH EHQGV PHHW WKH IROORZLQJ UHTXLUHPHQWV DQG WKHmaterials JDVVLGH (QVXUH WKDW exposed WKHUH LV parts QR JDS GURSP :KHQ RXWGRRU Be sure toOLTXLGVLGH with insulating cover all the of JDS +RZ WR &RQQHFW WKHJDVVLGH SLSHV OLTXLGVLGH DQG WKH (QVXUH WKDW WKHUH LV QR bends meet the following requirements: 7DEOH XQLW LV ERWWRP EHWZHHQ WKHP 7DEOH the flare pipe joints and refrigerant pipe on the liquid-side and the EHWZHHQ WKHP :KHQ RXWGRRU ,QFRPSOHWH PD\ FDXVH ZDWHUthem. FRQGHQVDWLRQ )ODULQJ gas-side. Ensure thatLQVXODWLRQ there is no gap between Incomplete ,QFRPSOHWH LQVXODWLRQ PD\ FDXVH ZDWHU FRQGHQVDWLRQ 7KH OHQJWK RI 02'(/ XQLW LV WRS 7 MODEL 11 15 02'(/ insulation may cause water condensation. UHIULJHUDQW SLSHP :KHQ RXWGRRU RXWGRRU The Max :KHQ When unit is RXWGRRU &XW D SLSH ZLWK D SLSH FXWWHU 5HIHUWR)LJ XQLWLV:KHQ LVWRS ERWWRP 15 35 25 XQLW 7KHHeight PD[ KHLJKW Drop XQLW LV WRS 7KH PD[ KHLJKW top GURSP :KHQ RXWGRRU (m) +RZ WR &RQQHFW WKH WKH SLSHV How to+RZ Connect the Pipes GURSP :KHQ RXWGRRU when outdoor WR &RQQHFW SLSHV 20 XQLW LV ERWWRP 10 25 XQLW LV ERWWRP unit is bottom /HDQ FUXGH EXUU :KHQ RXWGRRU )ODULQJ :KHQ RXWGRRU &$87,21 7KH OHQJWK RI )ODULQJ 1 Flaring OHQJWK RIofXQLW LV WRS The7KH length When XQLW LV WRSunit is UHIULJHUDQW SLSHP :KHQ RXWGRRU 25 30 50 UHIULJHUDQW SLSHP refrig. pipe (m) :KHQ topRXWGRRU • Cut a&XW pipe withZLWK a pipe cutter. (Refer to Fig.7-1) WKDQ ZKHQ OHQJWK RI UHIULJHUDQW PRUH D SLSH D SLSH FXWWHU 5HIHUWR)LJ XQLW LV ERWWRPWKH SLSH WKH P &XW D SLSH ZLWK D SLSH FXWWHU 5HIHUWR)LJ XQLW LV ERWWRP YDOXHwhen RI GXFW VWDWLF SUHVVXUH VKRXOG EH QRW OHVV WKDQ 3D outdoor 25 30 50 WKDW FRQQHW ZLWK VLQJOHSKDVH LQGRRU XQLW unit is bottom )LJ /HDQ FUXGH EXUU /HDQ FUXGH EXUU &$87,21 CAUTION &$87,21 CAUTION ZKHQ3URFHGXUH WKH OHQJWK RI UHIULJHUDQW SLSH PRUH WKDQ P WKH 7KH 3LSHV ZKHQ WKH OHQJWKRI RI &RQQHFWLQJ UHIULJHUDQW SLSH PRUH WKDQ P WKH ,QVHUW D IODUH QXW LQWR D SLSH DQGIODUHWKH SLSH YDOXH RI GXFW VWDWLF SUHVVXUH VKRXOG EH QRW OHVV WKDQ 3D YDOXH RI GXFW VWDWLF SUHVVXUH VKRXOG EH QRW OHVV WKDQ 3D ZLWK VLQJOHSKDVH LQGRRU XQLW When theWKDW pipeFRQQHW matrix is not significant in WKDW FRQQHW ZLWKobserved VLQJOHSKDVH LQGRRU reductions XQLW 5HIHUWR 7DEOH IRU WKH GLPHQVLRQ RIIODUH QXW VSDFHV )LJ )LJ &$87,21 system capacity and longevity should be expected. $OO ILHOG SLSLQJ PXVW EH SURYLGHG E\ D OLFHQVHG WKH 7KH 3URFHGXUH RI &RQQHFWLQJ 3LSHV UHIULJHUDWLRQ WHFKQLFLDQ PXVW FRPSO\ ZLWK 7KH 3URFHGXUH RI DQG &RQQHFWLQJ 3LSHV 7.1 TheUHOHYDQWORFDO Procedure for Connecting Pipes DQGQDWLRQDO FRGHV 7DEOH • Insert a flare nut into a pipe and flare the pipe. ,QVHUW D IODUH QXW LQWR D SLSH)ODUH DQGIODUHWKH SLSH ,QVHUW D IODUH QXW LQWR D SLSHGLPHQVLQ$ DQGIODUHWKH SLSHVKDSH •3LSHRefer to Table 7-2 for the dimension of flare nut )ODUH spaces. JDXJH 7LJKWHQLQJWRUTXH PLQ PP PD[ 5HIHUWR 7DEOH IRU WKH GLPHQVLRQ RIIODUH QXW VSDFHV 1P 5HIHUWR 7DEOH IRU WKH RIIODUH QXW VSDFHV GLPHQVLRQ 'R QRW OHW DLU &$87,21 GXVW RU RWKHU LPSXULWLHV IDOO LQ WKH SLSH NJIFP &$87,21 V\VWHP GXULQJ WKH WLPH RILQVWDOODWLRQ Flare Dimension A 1P 7DEOHPipe $OO ILHOG SLSLQJ PXVW EH SURYLGHG E\ D OLFHQVHG Torque NJIFP 7DEOH $ $OOFRQQHFWLQJ ILHOG SLSLQJ EHQRW SURYLGHG E\ DXQWLO OLFHQVHG Tighten Flare Shape 7KH SLSHPXVW VKRXOG EHFRPSO\ LQVWDOOHG Gauge UHIULJHUDWLRQ WHFKQLFLDQ DQG PXVW ZLWK WKHWKH )ODUH GLPHQVLQ$ UHIULJHUDWLRQ WHFKQLFLDQ DQG PXVW FRPSO\ ZLWK WKH 1P Min)ODUH GLPHQVLQ$ Max )ODUH VKDSH5a LQGRRU DQG RXWGRRU XQLWV KDYH EHHQ IL[HG DOUHDG\ 3LSHJDXJH 7LJKWHQLQJWRUTXH JDXJH UHOHYDQWORFDO )ODUH VKDSH PLQ PD[ PP 3LSH NJIFP 7LJKWHQLQJWRUTXH UHOHYDQWORFDO Drill a hole in theDQGQDWLRQDO wallDQGQDWLRQDO (suitableFRGHV justFRGHV for the size of the wall PLQ PP PD[ Ø 6.35 14.2 17.2 N.m (144 8.3 8.7 1P conduit), setGXVW on theRUfittings such as the wall conduit and LQ its 1P WKH DLU FRQQHFWLQJSLSH DQG GRQRW 1P kgf.cm) 'R.HHS QRW then OHW RWKHUGU\ LPSXULWLHV IDOOOHW LQ PRLVWXUH WKH SLSH 176 NJIFP 'R QRW OHW DLU GXVW RU RWKHU LPSXULWLHV IDOO LQ WKH SLSH NJIFP cover. GXULQJLQVWDOODWLRQ NJIFP V\VWHP GXULQJ WKH WLPH RILQVWDOODWLRQ Ø 9.53 32.7 39.9 N.m(333 12.0 12.4 V\VWHP GXULQJ WKH WLPH RILQVWDOODWLRQ 1P 1P 1P Bind([HFXWH the connecting pipe and the cables together tightly with 407 kgf.cm) NJIFP NJIFP $ KHDW LQVXODWLRQ ZRUN FRPSOHWHO\ RQ ERWK VLGHV NJIFP 7KH FRQQHFWLQJ SLSH VKRXOG QRW EH LQVWDOOHG XQWLO WKH $ binding tapes. 7KH FRQQHFWLQJ SLSHWKH VKRXOG QRW EH LQVWDOOHG XQWLO WKH Ø 12.7 49.5 60.3 N.m(504 1P RI WKH JDV SLSLQJ DQG OLTXLG SLSLQJ 2WKHUZLVH WKLV 15.4 15.8 LQGRRU DQG RXWGRRU XQLWV KDYH EHHQ IL[HG DOUHDG\ 1P 5a LQGRRU DQG RXWGRRU XQLWV KDYH EHHQ DOUHDG\from 616 kgf.cm 5a NJIFP VRPHWLPHV UHVXOWLQ ZDWHU OHDNDJH PassFDQ the bound connecting pipe through the IL[HG wall conduct CAUTION 1. 2. 3. 4. 5. outside. Be FRQQHFWLQJSLSH careful of the pipeGU\ allocation to doOHW onPRLVWXUH damage to .HHS WKH DQG GRQRW LQ the .HHS WKH FRQQHFWLQJSLSH GU\ DQG GRQRW OHW PRLVWXUH LQ tubing. GXULQJLQVWDOODWLRQ 16 Ø Connect the pipes. Refer to ZRUN “How toVXFK Connect the pipes” for FRQGXLW WKHQ VHW RQWKH ILWWLQJV DV WKH FRQGXLW ([HFXWH KHDW LQVXODWLRQ FRPSOHWHO\ RQZDOO ERWK VLGHVDQG ([HFXWH KHDW LQVXODWLRQ ZRUN FRPSOHWHO\ RQ ERWK VLGHV details. LWV FRYHU RI WKH JDV SLSLQJ DQG WKH OLTXLG SLSLQJ 2WKHUZLVH WKLV Ø 19 GXULQJLQVWDOODWLRQ 'ULOO D KROH LQ WKH ZDOO VXLWDEOH MXVW IRU WKH VL]H RI WKH ZDOO RI WKH JDV SLSLQJ DQG WKH OLTXLG SLSLQJ 2WKHUZLVH WKLV NJIFP 1P 75.4 &RQQHFW WKH XQLW DW ILUVW 61.8 N.mLQGRRU (630 19.0 WKHQ WKH RXWGRRU 1P 18.6 770 kgf.cm) XQLW NJIFP NJIFP 118.6 1P 97.2 22.9 23.3QRW KDUP WR WKHP N.m(990 1P ZD\ %HQGWKH WXELQJ LQ SURSHU NJIFP 'R 1210 kgf.cm) NJIFP %HQGWKH SLSHZLWKWKXPE FDQ the VRPHWLPHV ZDWHU OHDNDJH Expel with aUHVXOWLQ vacuum pump. Refer to “How to expel the FDQair VRPHWLPHV UHVXOWLQ ZDWHU OHDNDJH %LQGWKH FRQQHFWLQJ DQG WKHOpen FDEOHV WRJHWKHU WLJKWO\ofZLWK air with a vacuum pump”SLSH for details. the stop values the 2 &RQQHFW WKHthe LQGRRU XQLWunit DW ILUVW WKHQthen WKH the RXWGRRU Connect at &RQQHFW WKHindoor LQGRRU XQLW DW first, ILUVW WKHQ WKH RXWGRRU ELQGLQJWDSHV outdoor unit to make the refrigerant pipe connecting the indoor XQLW outdoor unit. XQLW 'ULOO D KROH LQ WKH ZDOO VXLWDEOH MXVW IRU WKH VL]H RI WKH ZDOO unit 3DVV WKH ERXQG FRQQHFWLQJ SLSH WKURXJK WKH ZDOO FRQGXFW theD outdoor unitZDOO in fluent flow.MXVW IRU WKH VL]H RI WKH ZDOO 'ULOO KROH LQ WKH VXLWDEOH with PLQUDGLXV PP FRQGXLW WKHQ VHW %H RQWKH ILWWLQJV VXFK DV WKHDOORFDWLRQ ZDOO FRQGXLW GR DQG %HQGWKH WXELQJ LQ SURSHUusing ZD\ 'R QRW KDUP WR WKHP IURP RXWVLGH WKH SLSH • All bends must be performed appropriate tools. FRQGXLW WKHQ VHWFDUHIXO RQWKH RI ILWWLQJV DV WKH ZDOO WR FRQGXLWRQ %HQGWKH WXELQJ LQ SURSHU ZD\ 'R QRW KDUP WR WKHP 6. Check the leakage. Check all the joints VXFK with the leak detector orDQG )LJ LWV GDPDJH FRYHU WRWKH WXELQJ Deformed bends can reduce system capacity LWV FRYHU %HQGWKH SLSHZLWKWKXPE soap water. %HQGWKH SLSHZLWKWKXPE • The bend angle should not exceed 90. 7KH EHQGLQJ DQJOH VKRXOG QRW H[FHHG %LQGWKH FRQQHFWLQJ DQGWRWKH FDEOHV WRJHWKHU WLJKWO\ ZLWK/IRU &RQQHFW WKHFRQQHFWLQJ 5HIHU +RZ &RQQHFW WKH SLSHV Cover 7. the joints ofSLSHV the SLSH connecting pipe with theWRJHWKHU soundproof %LQGWKH SLSH DQG WKHWR FDEOHV WLJKWO\ ZLWK • Bend position is preferably in the middle of the pipe. The larger ELQGLQJWDSHV GHWDLOV insulating sheath (fittings), and bind it well with the tapes to %HQGLQJ SRVLWLRQ LV SUHIHUDEO\ LQ WKH PLGGOH RI WKH ELQGLQJWDSHV the bend radius the better it is. 3DVV WKH ERXQG FRQQHFWLQJ SLSH WKURXJK WKH ZDOO FRQGXFW prevent leakage. EHQGDEOH SLSHPLQUDGLXV 7KH ODUJHU WKH EHQGLQJ UDGLXV WKH EHWWHU LW 3DVV WKH ERXQG FRQQHFWLQJ SLSH WKURXJK WKH ZDOO FRQGXFW • Do not bend PP the pipe more than three times. PLQUDGLXV PP RXWVLGHDLU%H FDUHIXO RI WKH SLSH 5HIHU DOORFDWLRQ WR GR RQ ([SHO ZLWK D YDFXXP SXPS WR +RZ WRWRH[SHO IURP LV IURPWKH RXWVLGH %H FDUHIXO RI WKH SLSH DOORFDWLRQ GR RQ • When connecting the flare nut, coat the flare)LJ both)LJ inside and GDPDJH WKHGDPDJH DLU WRWKH ZLWK WRWKH DWXELQJ YDFXXP SXPS IRU GHWDLOV WXELQJ QRWeither EHQGWKH SLSH PRUHWKDQWKUHH WLPHV outside 'R with oil or ester oil and initially tighten by hand EHQGLQJ DQJOH VKRXOGfirmly. QRW H[FHHG 3 or 47KH turns before tightening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| E [email protected] | A 1/49 Miller Street,Murrarie Qld 4172 &RYHU WKH MRLQWV RI125 WKH(FREECALL) FRQQHFWLQJ| SLSH ZLWK WKH VRXQGSURRI LQVXODWLQJ VKHDWK ILWWLQJV DQG ELQG LW ZHOO ZLWK WKH WDSHV WR ZZZILQHSULQWFQ SGI)DFWRU\3UR LQVXODWLQJ VKHDWK ILWWLQJV DQG ELQG LW ZHOO ZLWK WKH WDSHV WR SUHYHQW OHDNDJH SUHYHQW OHDNDJH LQVWDOODWLRQ PDQXDO 13 7 )LJ )LJ VHUYLFH SRUW Installation Manual PDLQWHQDQFH QXW VHUYLFH SRUW PDLQWHQDQFH QXW FDS VHUYLFH SRUW VHDO VKDIW FDS PDLQWHQDQFH QXW KH[DJRQ KROH VHDOWKH VKDIW KH[DJRQ KROH 8VLQJ YDFXXP SXPS )LJ &$87,21 )LJ CAUTION Stop operation WKDWWKHUH LVintroduction QR JDV OHDN valve 2SHQLQJ VWRS YDOYH 6WRS YDOYH RSHUDWLRQ LQWURGXFWLRQ WR FKHFN 5HPRYH WKH FDS DQG WXUQ WKH YDOYH VWRS FRXQWHUFORFNZLVH ZLWKZLWK WKH KH[DJRQ ZUHQFK 1 2SHQLQJ Opening stopWKH valve +RZ WR YDOYH H[SHO DLU D YDFXXP SXPS )LJ /RRVHQ DQG UHPRYH WKH PDLQWHQDQFH QXWV RI VWRS YDOYHV $ 8VLQJ WKH YDFXXP SXPS DQG % DQG FRQQHFW WKH FKDUJH KRVH RI WKH PDQLIROG YDOYH WR WKHDQG VHUYLFH SRUW RI PDLQWHQDQFH VWRS $ QXWV %H WKDWYDOYHV VWRS YDOYHV $ VHDOWKH VKDIW YDOYH KH[DJRQ KROHVXUH /RRVHQ UHPRYH RI VWRS $ )LJ DUH ERWKWKH FORVHG DQG %DQG DQG%FRQQHFW FKDUJH KRVH RI WKH PDQLIROG YDOYH WR Using the Vacuum Pump WKH VHUYLFH SRUWWKH RI VWRS YDOYH SXPS $ %H VXUH WKDW VWRS YDOYHV $ 8VLQJ YDFXXP WKH MRLQW RI FKDUJH KRVHnuts ZLWK of WKHstop YDFXXP SXPS % &RQQHFW DUH ERWK FORVHG 1.DQGLoosen and remove theWKH maintenance valves A and /RRVHQ DQG UHPRYH WKH PDLQWHQDQFH QXWV RI VWRS YDOYHV $ B, and connect the charge hose of the manifold valve to the DQG % DQG FRQQHFW WKH PDQLIROG FKDUJH KRVH RIFRPSOHWHO\ WKH PDQLIROG YDOYH WR 2SHQWKH /ROHYHU RIWKH YDOXH &RQQHFW WKH MRLQW RIstop WKH valve FKDUJH ZLWK WKH SXPS service port of A.KRVH (Be sure thatYDFXXP stop valves A and B WKH VHUYLFH SRUW RI VWRS YDOYH $ %H VXUH WKDW VWRS YDOYHV $ are both closed) DQG % FORVHG 7XUQ RQDUH WKHERWK YDFXXP SXPS $W WKH EHJLQQLQJ RI SXPSLQJ 2SHQWKH /ROHYHU RIWKH PDQLIROG YDOXH FRPSOHWHO\ 7RR ODUJH WRUTXH ZLOO KDUP WKH EHOOPRXWKLQJ DQG WRR &$87,21 VPDOO ZLOO FDXVH OHDNDJH 3OHDVH GHWHUPLQH WKH)LJ WRUTXH Too large torque will harm theKDUP bell mouthing and too DQG smallWRR will DFFRUGLQJWR 7DEOH 7RR ODUJH WRUTXH ZLOO WKH EHOOPRXWKLQJ cause leakage. the torque according Table 7-3. VPDOO ZLOOPlease FDXVHdetermine OHDNDJH 3OHDVH GHWHUPLQH WKH to WRUTXH $IWHU WKH FRQQHFWLQJ ZRUN LV ILQLVKHG EH VXUH WR FKHFN DFFRUGLQJWR 7DEOH &$87,21 WKDWWKHUHwork LV QRisJDV OHDN be sure to check that there is After the connecting finished, 7RR ODUJH WRUTXH KDUP WKH FRQQHFWLQJ ZRUN ZLOO LV ILQLVKHG EHEHOOPRXWKLQJ VXUH WR FKHFNDQG WRR no gas $IWHU leak. WKH VPDOO WKDWWKHUH LV QRZLOO JDVFDXVH OHDN OHDNDJH 3OHDVH GHWHUPLQH WKH WRUTXH +RZ WR H[SHO WKH DLU ZLWK D YDFXXP SXPS DFFRUGLQJWR 7DEOH How to expelYDOYH the air with a vacuum pump +RZ WR6WRS H[SHO DLU ZLWKLQWURGXFWLRQ D YDFXXP $IWHU WKH WKHRSHUDWLRQ FRQQHFWLQJ ZRUN LV ILQLVKHGSXPS EH VXUH )LJ FDS 5HPRYH FDS DQGVKDIW WXUQVWRSV'R WKH YDOYH 7XUQ LW XQWLO QRW DSSO\ H[FHVVLYH • Remove theWKH cap andWKH turn the valve counter clock-wise with the 6WRS YDOYH RSHUDWLRQ FRXQWHUFORFNZLVH ZLWK YDOYH WKH LQWURGXFWLRQ KH[DJRQ WR WKH VWRS 'RLQJ VR ZUHQFK PD\ EUHDNWKH YDOYH hexagonIRUFH wrench. VWRS YDOYH DV WKH YDOYH LVDo QRWnot D EDFNVHDW W\SH $OZD\V 7XUQ LWERG\ XQWLO WKH VKDIW VWRSV'R QRW DSSO\ excessive H[FHVVLYH • Turn it2SHQLQJ until the shaft stops. apply force XVH to the WKH VSHFLDO WRRO IRUFH WR WKH VWRS YDOYH 'RLQJ VRWXUQ PD\ EUHDNWKH stop valve. Doing soWKH may break valve body, the valve is 5HPRYH FDS DQGthe WKH YDOYHasYDOYH DV WKHVXUHWRWLJKWHQ YDOYH QRW D ZLWK EDFNVHDW W\SH $OZD\V XVH FRXQWHUFORFNZLVH WKHVHFXUHO\ KH[DJRQ notERG\ abackseat type. LV Always use the special tool.ZUHQFK 0DNH WKH FDS WKH sure VSHFLDO WRRO • Make to tighten the cap securely. 7XUQ LW XQWLO WKH VKDIW VWRSV'R QRW DSSO\ H[FHVVLYH 0DNH VXUHWRWLJKWHQ WKH FDS VHFXUHO\ IRUFH WR YDOYH WKHvalve VWRS YDOYH 'RLQJ VR PD\ EUHDNWKH YDOYH &ORVLQJ VWRS 2 Closing stop ERG\ DV WKH YDOYH LV QRW D EDFNVHDW W\SH $OZD\V XVH 5HPRYH WKH WRRO FDS DQG WXUQ WKH YDOYH FORFNZLVH WKH Remove the cap and turn the valve clockwise with the ZLWK hexagon WKH VSHFLDO • &ORVLQJ VWRS YDOYH KH[DJRQ ZUHQFK wrench. 0DNH VXUHWRWLJKWHQ WKH FDS VHFXUHO\ 5HPRYH WKH FDS DQG WXUQ WKH YDOYH FORFNZLVH • Securely tighten the valve until the shaft contacts theWKH main WKH 6HFXUHO\ WLJKWHQ WKH YDOYH XQWLO WKH VKDIWZLWK FRQWDFWV KH[DJRQ ZUHQFK body seal. PDLQ ERG\VHDO &ORVLQJ VWRS YDOYH • Make sure toWLJKWHQ tighten theYDOYH cap securely. 6HFXUHO\ WKH XQWLO WKH VKDIW FRQWDFWV WKH • ForPDLQ the tightening torque,refer toVHFXUHO\ the below. 0DNH VXUHWRWLJKWHQ WKH FDSWXUQ ERG\VHDO 5HPRYH WKH FDS DQG WKHtable YDOYH FORFNZLVH ZLWK WKH )RU WKHWLJKWHQLQJ WRUTXHUHIHU WR WKHWDEOH EHORZ KH[DJRQ ZUHQFK 0DNH VXUHWRWLJKWHQ WKH FDS VHFXUHO\ Tightening torque N.mWKH (Turn to close) 6HFXUHO\ WLJKWHQ YDOYHclockwise XQWLO WKH VKDIW FRQWDFWV WKH 7DEOH )RU WKHWLJKWHQLQJ WRUTXHUHIHU WR WKHWDEOH EHORZ PDLQ ERG\VHDO Cap Stop Valve Maintenance 7LJKWHQLQJ WRUTXH 1 0 7XUQ FORFNZLVH WR FORVH Shaft (valve Body) (valve 7DEOH Size nut 0DNH VXUHWRWLJKWHQ WKH FDS VHFXUHO\ Lid) 6WRS &DS 6KDIW YDOYH ERG\ )RU WKHWLJKWHQLQJ WRUTXHUHIHU WR WKHWDEOH EHORZ 0DLQWHQDQFH QXW 7LJKWHQLQJ FORVH 9DOYH VL]H WRUTXH 1 0 7XUQ FORFNZLVH WR 9DOYH OLG Ø6.35 6WRS 5.4-6.6 13.5-16.5 Hexagonal &DS 6KDIW 7DEOH 0DLQWHQDQFH QXW Ø9.53 YDOYH ERG\ 9DOYH VL]H 9DOYH OLG +H[DJRQDO wrench 4mm ZUHQFK PP 8.1-8.9WRUTXH 1 0 7XUQ FORFNZLVH 18-22WR FORVH Ø12.7 7LJKWHQLQJ +H[DJRQDO 6WRS &DS Hexagonal 11.5-13.9 QXW ZUHQFK PP 6KDIW YDOYH ERG\ Ø16 VL]H 13.5-16.5 23-27 +H[DJRQDO 0DLQWHQDQFH 9DOYH 9DOYH OLG wrench 6mm ZUHQFK PP Ø22.2 Hexagonal +H[DJRQDO +H[DJRQDO +H[DJRQDO ZUHQFK ZUHQFK PP Wrench 36-44 27-33 ZUHQFK PP Ø 25.4 PP 10mm +H[DJRQDO ZUHQFK +H[DJRQDO PP ZUHQFK PP 2. Connect the joint of the charge hose with the vacuum pump. ORRVHQ WKH PDLQWHQDQFH QXW RI VWRS YDOYH % D OLWWOH WR FKHFN 3. Open the Lo-lever of the manifold valueZLWK completely. &RQQHFW WKHDLU MRLQW RI WKH KRVH WKHSXPS YDFXXP SXPS ZKHWKHU WKH FRPHV LQFKDUJH WKH RI WKH FKDQJHV 7XUQ RQ WKH YDFXXP SXPS $W WKH VRXQG EHJLQQLQJ RI SXPSLQJ 4. When the pumping has finished, PHWHU close the Lo-lever of the DQGWKH LQGLFDWRU RI FRPSRXQG WXUQV EHORZ ]HUR7KHQ ORRVHQ WKH PDLQWHQDQFH QXW RI VWRS YDOYH % D OLWWOH WR FKHFN valve completely and turn off the vacuum pump. 2SHQWKH /ROHYHU PDQLIROG YDOXH FRPSOHWHO\ manifold IDVWHQWKH PDLQWHQDFH QXW ZKHWKHU WKH DLU FRPHV LQ RIWKH WKH VRXQG RI WKH SXPS FKDQJHV Evacuate to 500 DQGWKH LQGLFDWRU RI microns FRPSRXQG PHWHU WXUQV EHORZ ]HUR7KHQ 7XUQ RQremove WKH YDFXXP $W valves WKH EHJLQQLQJ RI open SXPSLQJ Loosen 5.IDVWHQWKH and theKDV capSXPS of stop AWKH and/ROHYHU B to stop :KHQ WKH SXPSLQJ ILQLVKHG FORVH RI WKH PDLQWHQDFH QXW ORRVHQ PDLQWHQDQFH QXWfasten RIDQG VWRS YDOYH % DWKH OLWWOH YDFXXP WR FKHFN valve A and WKH B YDOYH completely, then the cap. PDQLIROG FRPSOHWHO\ WXUQ RII ZKHWKHU WKHSXPSLQJ DLU WKH VRXQG RI WKHport SXPS FKDQJHV SXPS0DNH IRU LQ from PLQXWHV RU /ROHYHU PRUH DQG FKHFN WKDW 6.:KHQ Disassemble the charge hose theWKHservice stop WKH SXPSLQJ KDVFRPHV ILQLVKHG FORVH RIof WKH DQGWKH LQGLFDWRU RI FRPSRXQG PHWHU WXUQV EHORZ ]HUR7KHQ WKH FRPSRXQG PHWHU LQGLFDWHV FP+J; 3D valve A, and fasten the nut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lways use a charge forKRVH service port connection. PP $OZD\V XVH Dhose FKDUJH IRU VHUYLFH SRUW FRQQHFWLRQ /ROHYHU )LJ /ROHYHU )LJ &$87,21 9DFXXP SXPS /ROHYHU After tightening the cap, check thatFKHFN noSRUW refrigerant are present. $IWHU WKH WKDW QR leaks UHIULJHUDQW OHDNV $OZD\V XVH DWLJKWHQLQJ FKDUJH KRVH IRUFDS VHUYLFH FRQQHFWLRQ )LJ DUHSUHVHQW $IWHU WLJKWHQLQJ WKH FDS&$87,21 FKHFN WKDW QR UHIULJHUDQW OHDNV DUHSUHVHQW $OZD\V XVH D FKDUJH KRVH IRU VHUYLFH SRUW FRQQHFWLRQ P 1300 306 (FREECALL) | F 07 8730 | E OHDNV [email protected] | A 1/49 Miller Street,Murrarie Qld 4172 $IWHU WLJKWHQLQJ WKH125 FDS FKHFN WKDW QR3890 UHIULJHUDQW LQVWDOODWLRQ PDQXDO 14 DUHSUHVHQW 3') SGI)DFWRU\3UR ZZZILQHSULQWFQ LQVWDOODWLRQ PDQXDO 14 ) SGI)DFWRU\3UR ZZZILQHSULQWFQ 8 8. $GGLWLRQDO 5HIULJHUDQW &KDUJH &$87,21 7.2 Additional Refrigerant Charge XQWLO 5HIULJHUDQW FDQQRW EH FKDUJHG FRPSOHWHG Manual CONNECTTHE DRAIN Installation PIPE ,QVWDOO WKH GUDLQSLSH RI WKHLQGRRU XQLW ILHOG ZLULQJ KDV EHHQ 8. CONNECT THE PIPE 7KH RXWOHW KDV 37, DRAIN VFUHZ EUHDG 3OHDVH XVH VHDOLQJ PDWHULDOV 8.1 Install theVKHDWKILWWLQJ drainpipeZKHQ of the indoor39& unitSLSHV DQG SLSH FRQQHFWLQJ CAUTION The outlet has PTI screw thread, Please use easy clean drain trap 5HIULJHUDQW PD\ RQO\ EH FKDUJHG DIWHU SHUIRUPLQJWKH OHDN WHVW supplied with the unit. PIPE DQGWKH YDFXXP SXPSLQJ $GGLWLRQDO 5HIULJHUDQW &KDUJH 8. CONNECTTHE DRAIN &$87,21 Refrigerant cannot be charged until field wiring has WKDW been :KHQ FKDUJLQJ D V\VWHP FDUH VKDOO EH WDNHQ LWVcompleted. PD[LPXP RI ,QVWDOO SHUPLVVLEOH FKDUJH LV QHYHU H[FHHGHG LQ YLHZ RI WKH GDQJHU WKH RILQGRRU WKHLQGRRU XQLW 7KHGUDLQSLSH GUDLQ SLSH RI XQLW PXVW EH KHDW LQVXODWHG RU LW ZLOO Refrigerant may only&$87,21 be charged after performing the leak test and OLTXLG KDPPHU FRQGHQVH GHZ DV ZHOO CAUTION DV WKH FRQQHFWLRQV RIWKH LQGRRU XQLW 5HIULJHUDQW FDQQRW EH FKDUJHG XQWLO ILHOG ZLULQJ KDV EHHQ the vacuum pumping. 7KH RXWOHW KDV 37, VFUHZ EUHDG 3OHDVH XVH VHDOLQJ PDWHULDOV FRPSOHWHG DQG SLSH VKHDWKILWWLQJ FRQQHFWLQJ SLSHV +DUG 39&ZKHQ ELQGHU PXVW EH39& XVHG IRU SLSH FRQQHFWLRQ DQG PDNH &KDUJLQJ ZLWK DQ care XQVXLWDEOH VXEVWDQFH PD\itsFDXVH H[SORVLRQV When charging a system, shall be taken that maximum DQG DFFLGHQWV VR DOZD\V HQVXUH WKDW WKH DSSURSULDWH UHIULJHU 5HIULJHUDQW PD\ RQO\ EH FKDUJHG DIWHU SHUIRUPLQJWKH OHDNdanger WHVW permissible charge is never exceeded, in view of the of liquid DQWYDFXXP LV FKDUJHG DQGWKH SXPSLQJ hammer. • The outlet has PTI screw bread, Please use sealing materials and VXUHWKHUH LV QR OHDNDJH pipe sheath(fitting) when connecting PVC pipes. • :LWKdrain WKH FRQQHFWLRQ SDUWunit WR WKH LQGRRU XQLW SOHDVH QRWHG QRW The pipe of indoor must be insulated, or EH it will &$87,21 :KHQ5HIULJHUDQW FKDUJLQJ V\VWHP FDUH VKDOO WKDW LWV PD[LPXP FRQWDLQHUV VKDOOEHEHWDNHQ RSHQHG VORZO\ WR LPSRVHdew, SUHVVXUH RQWKH VLGH RI LQGRRU XQLW SLSHV condense as well as the connections of the indoor unit. Charging with an Dunsuitable substance may cause explosions and SHUPLVVLEOH FKDUJH LV QHYHU H[FHHGHG LQ YLHZ RI WKH GDQJHU RI 7KH GUDLQ SLSH RI LQGRRU XQLW PXVW EH KHDW LQVXODWHG RU LW ZLOO accidents, so always ensure that the appropriate refrigerant is • PVC solvent must be used for pipe connection, and make sure OLTXLG $OZD\V KDPPHU XVH SURWHFWLYH JORYHV DQG SURWHFW \RXU H\HV ZKHQ FRQGHQVH GHZ:KHQ DV ZHOOWKH DV WKH FRQQHFWLRQV GHFOLYLW\ RI WKHRIWKH GUDLQLQGRRU SLSH XQLW GRZQZDUGV LV RYHU charged. FKDUJLQJ UHIULJHUDQW there is no leakage. WKHUH VKRXOG QRW EH DQ\ ZLQGLQJ XQLWLQGRRU XQLW FRQQHFWLRQ must be installed to prevent winding. &KDUJLQJ ZLWK DQ XQVXLWDEOH VXEVWDQFH PD\ FDXVH H[SORVLRQV +DUG 39& ELQGHU PXVW EH XVHG IRU SLSH FRQQHFWLRQ DQG PDNH • With the connection part to the indoor unit, please be noted not Refrigerant containers shall be opened DQG DFFLGHQWV VR DOZD\V HQVXUH WKDW WKH slowly. DSSURSULDWH UHIULJHU VXUHWKHUH LV QR OHDNDJH WRWDO OHQJWK RI WKH SLSHofZKHQ SXOOHG WUDYHUVHO\ VKDOO to7KH impose pressure on GUDLQ the side indoor unitRXW pipes. K H R X W G R R U X Q L W L V I D F W R U\ F K D U J H G ZL W K U H I UL J H U D Q W DQW LV 7 FKDUJHG Always use protective gloves and protect your eyes when charging QRW H[FHHG P ZKHQXQLW WKHSOHDVH SLSH LVEHRYHU ORQJ D SURS VWDQG PXVW :LWK WKH•FRQQHFWLRQ SDUW WR WKH LQGRRU QRWHG QRW &DOFXODWH WKH DGGHG UHIULJHUDQW DFFRUGLQJ WR WKH GLDPHWHU The total length of the drain pipe when pulled out transversely refrigerant. EH LQVWDOOHGWR ZLQGLQJ 5HIULJHUDQW FRQWDLQHUV VKDOORIWKH EH RSHQHG VORZO\ WR LPSRVH SUHVVXUH RQWKH VLGHSUHYHQW RI LQGRRU XQLW SLSHV DQGWKH OHQJWK OLTXLG VLGH SLSH RIWKH RXWGRRU shall not exceed 20m, when the pipe is over long, a prop stand $OZD\V XVH SURWHFWLYH JORYHV DQG SURWHFW \RXU H\HV ZKHQ :KHQ WKH GHFOLYLW\ RI WKH GUDLQ SLSH GRZQZDUGV RYHU RIWKH SLSHV 5HIHUWRWKH XQGHUILJXUHV IRU WKHLVLQVWDOODWLRQ FKDUJLQJ UHIULJHUDQW EH to DQ\the ZLQGLQJ • QRW Refer under figures for the installation of the pipes The outdoor unit is factory charged with refrigerant. CalculateWKHUH VKRXOG 7DEOH the added refrigerant according to the diameter and the 7KH WRWDO OHQJWK RI WKH GUDLQ SLSH ZKHQ SXOOHG RXW WUDYHUVHO\ VKDOO 7 K H R X W G R R U X Q L W L V'PP I D F W R U\ F K D U J H G ZL W K U H I UL J H U D Q W length ofWKH the liquid side pipe of the outdoor unit/indoor unit QRW H[FHHG P ZKHQ WKH SLSH LV RYHU ORQJ D SURS VWDQG PXVW 5J &DOFXODWH DGGHG UHIULJHUDQW DFFRUGLQJ WR WKH GLDPHWHU EH LQVWDOOHGWR SUHYHQW ZLQGLQJ PaP DQGWKH OHQJWK RIWKH OLTXLG VLGH SLSH RIWKH RXWGRRU connection. /P XQLWLQGRRU XQLW FRQQHFWLRQ 5HIHUWRWKH XQGHUILJXUHV IRU WKH LQVWDOODWLRQ RIWKH SLSHV L/HVVWKDQ (m) / P 2QHZD\ 7DEOH R(G) / 'PPØ6.35 Ø9.53 Ø12.7 5J $GGHG 5HIULJHUDQW:KHQ JP/ JP/ D(mm) JP/ /P 2YHU P 2QHZD\ Less than 5m -------------- -------------- -------------- ,QVXODWLQJ 'RZQZDUG GHFOLYLW\ PDWHULDO ORZHU WKDQ PaP /HVVWKDQ P 2QHZD\ 5J $GGLWLRQDO UHIULJHWDQW WR EH FKDUJHG Added /P 7KHwhen OHQJWK RI WKH UHIULJHUDQW SLSHRQHZD\ 30g/m°—(L-5) 60g/m°—(L-5) 11g/m°—(L-5) refrigerant 'PP 5/LTXLG 6LGH 3LSLQJ 'LDPHWHU $GGHG 5HIULJHUDQW:KHQ over m JP/ JP/ JP/ ,QVXODWLQJ 'RZQZDUG GHFOLYLW\ PDWHULDO ORZHU WKDQ 2YHU P 2QHZD\ R(g): Additional refrigerant to be charged %HQG 5J $GGLWLRQDO UHIULJHWDQW WR EH FKDUJHG &KHFN WKH /HDNDJH L(m): length ofUHIULJHUDQW the refrigerant pipe(one-way) /P 7KHThe OHQJWK RI WKH SLSHRQHZD\ 'PP /LTXLG 6LGH 3LSLQJ 'LDPHWHU 6 VKDSH &KHFN WKHMRLQWV ZLWK WKHOHDN GHWHFWRURU VRDS ZDWHU D(mm): LiquidDOOSide Piping Diameter 6HH )LJ DV D UHIHUHQFHLOOXVWUDWLRQ 7.3 &KHFN Check the Leakage WKH /HDNDJH &KHFNSRLQW RI LQGRRU XQLW ' %HQG & 6 VKDSH Check all the joints with the leak detector or soap water. &KHFN DOO WKHMRLQWV ZLWK WKHOHDN GHWHFWRURU VRDS ZDWHU 3XW DV GHHS DV SRVVLEOH DERXW FP 6HH )LJ DV D UHIHUHQFHLOOXVWUDWLRQ ' &KHFNSRLQW RI LQGRRU XQLW & % &KHFNSRLQW RI RXWGRRU XQLW &KHFNSRLQW RI RXWGRRU XQLW % 3XW DV GHHS DV SRVVLEOH DERXW FP $ 'RZQZDUG GHFOLYLW\ ORZHUWKDQ $ 'RZQZDUG GHFOLYLW\ ORZHUWKDQ 8.1 Drain Test )LJ 127( Note )LJ In the figure ,QWKHILJXUH 127( $/RVWRS YDOYH A......Lo-stop valve %+LVWRS YDOYH ,QWKHILJXUH B......Hi-stop valve YDOYH $/RVWRS &'-RLQWV RI WKH FRQQHFWLQJ SLSHWRWKH LQGRRU XQLW C,D..Joints of the connecting pipe to the indoor unit. %+LVWRS YDOYH &'-RLQWV RI WKH FRQQHFWLQJ SLSHWRWKH LQGRRU XQLW 1. 93 93 )LJ Check whether the drainpipe is unhindered. )LJ 2.Newly built homesWHVW should have this test done before sheeting 'UDLQDJH the ceiling. 'UDLQDJH WHVW &KHFN ZKHWKHU WKH GUDLQSLSHLVXQKLQGHUHG 1HZ EXLOW KRXVH VKRXOG KDYH WKLV WHVW GRQH EHIRUH SDYLQJ WKH FHLOLQJ &KHFN ZKHWKHU WKH GUDLQSLSHLVXQKLQGHUHG 1HZ EXLOW KRXVH VKRXOG KDYH WKLV WHVW GRQH EHIRUH SDYLQJ WKH FHLOLQJ 9 P 1300 306 125 (FREECALL) | F 07 3890 8730 | E [email protected] | A 1/49 Miller Street,Murrarie Qld 4172 LQVWDOODWLRQ PDQXDO 3') SGI)DFWRU\3UR ZZZILQHSULQWFQ LQVWDOODWLRQ PDQXDO 15 15 Installation Manual POWER SPECIFICATION Type Indoor Unit Power Outdoor Unit Power H-INV-7 + H-VAV-7 H-INV-11 + H-VAV-11 H-INV-15 + H-VAV-15 Phase Frequency & volt Power Wiring (mm2) Circuit Breaker (A) Phase Frequency & volt Power Wiring (mm2) 1 phase 220-240V~, 50hz 1 phase 220-240V~, 50hz 1 phase 220-240V~, 50hz 3x1.0 3x1.0 3x1.0 10 1 phase 220-240V~, 50hz 10 1 phase 220-240V~, 50hz 10 1 phase 220-240V~, 50hz 3x2.5 3x2.5 3x2.5 Circuit Breaker (A) 20 25 32 3-core shielded wire - 3 x 0.5 3-core shielded wire - 3 x 0.5 3-core shielded wire - 3 x 0.5 Indoor/Outdoor Connecting Wiring (Weak Electric Signal) (mm2) 10.3 Wiring Figure Indoor Unit Outdoor Unit System Communication Bus System Communication Bus Connect Controller Zone Communication Bus Central Controller Chatterbox HVAC P 1300 306 125 (FREECALL) | F 07 3890 8730 | E [email protected] | A 1/49 Miller Street,Murrarie Qld 4172 10 Installation Manual Outer Coil Sensor T2B Mid Coil Sensor T2 4 CN1 ALARM CN2 Return Air Sensor T1 CN4 Outdoor Unit Data Interconnect 3 core shielded 3 x 0.5 mm2 Y X P E Q CN3 ON/OFF E 4 S2 S1 SW1 ENC1 ENC2 10 M Outdoor Unit Power Interconnect 5 3 x 1.0 mm2 Zoning Module Transformers Power Interconnect Zoning System Data Interconnect RJ12 - 6p6c Return Air Sensor T3 Supply Air Sensor T4 H-VAV-07: INSTALLATION NOTES PRIOR TO splitting indoor unit for installation DISCONNECT Indoor coil and return sensors - T1, T2, T2B and T3 P 1300 306 125 (FREECALL) | F 07 3890 8730 | E [email protected] | A 1/49 Miller Street,Murrarie Qld 4172 11 Installation Manual Outer Coil Sensor T2B Mid Coil Sensor T2 4 CN1 ALARM CN2 Return Air Sensor T1 CN4 Outdoor Unit Data Interconnect 3 core shielded 3 x 0.5 mm2 Y X P E Q CN3 ON/OFF E 4 4 S2 S1 SW1 ENC1 ENC2 10 M M 5 5 Outdoor Unit Power Interconnect 3 x 1.0 mm2 Zoning Module Transformers Power Interconnect Zoning System Data Interconnect RJ12 - 6p6c Return Air Sensor T3 Supply Air Sensor T4 H-VAV-11: INSTALLATION NOTES PRIOR TO splitting indoor unit for installation DISCONNECT Indoor coil and return sensors - T1, T2, T2B and T3 P 1300 306 125 (FREECALL) | F 07 3890 8730 | E [email protected] | A 1/49 Miller Street,Murrarie Qld 4172 12 Installation Manual Outer Coil Sensor T2B Mid Coil Sensor T2 4 CN1 ALARM CN2 Return Air Sensor T1 CN4 Outdoor Unit Data Interconnect 3 core shielded 3 x 0.5 mm2 Y X P E Q CN3 ON/OFF E 4 4 S2 S1 SW1 ENC1 ENC2 10 M M 5 Outdoor Unit Power Interconnect 5 3 x 1.0 mm2 Zoning Module Transformers Power Interconnect Zoning System Data Interconnect REACTOR RJ12 - 6p6c Return Air Sensor T3 Supply Air Sensor T4 H-VAV-15: INSTALLATION NOTES PRIOR TO splitting indoor unit for installation DISCONNECT Indoor coil and return sensors - T1, T2, T2B and T3 P 1300 306 125 (FREECALL) | F 07 3890 8730 | E [email protected] | A 1/49 Miller Street,Murrarie Qld 4172 13 Installation Manual Notes P 1300 306 125 (FREECALL) | F 07 3890 8730 | E [email protected] | A 1/49 Miller Street,Murrarie Qld 4172 14 Installation Manual Notes P 1300 306 125 (FREECALL) | F 07 3890 8730 | E [email protected] | A 1/49 Miller Street,Murrarie Qld 4172 15 Installation Manual Livezi Phone 1300 306 125 Fax 07 3890 8734 Web: www.livezi.com.au Email: [email protected] P 1300 306 125 (FREECALL) | F 07 3890 8730 | E [email protected] | A 1/49 Miller Street,Murrarie Qld 4172 16