Download Mitsubishi PE-12 Service manual
Transcript
OC155-B--1.qxp 7/26/00 4:42 PM Page 1 SPLIT-TYPE, AIR CONDITIONERS No. OC155 REVISED EDITION-B TECHNICAL & SERVICE MANUAL Series PE Ceiling Concealed <Indoor unit> [Model names] [Service Ref.] PE-3EJA2.TH PE-3EJA3.TH PE-4EJSA2.TH PE-5EJSA2.TH PE-6EJSA2.TH PE-3EJA PE-4EJSA PE-5EJSA PE-6EJSA PE-3EJA3.TH added in REVISED EDITION-B. Please destroy OC155 REVISED EDITION-A. This manual does not cover the following outdoor units. When servicing them, please refer to the following service manual and this manual in a set. [Service Ref.] OC152 REVISED EDITION-A PU-3VJA1.TH, 3YJA1.TH PU-4VLJSA1.TH, 4YJSA1.TH PU-5YJSA.TH PU-6YJSA.TH OC127 REVISED EDITION-A PU-3NJA1 PU-4TJSA2 OC199 PU-5TJSA1 PU-6TJSA1 OC206 PU-3VJC.TH, 3YJC.TH CONTENTS Indoor unit TIMER TEMP 12 29 11 28 COOL 10 27 DRY 9 26 8 25 7 24 6 23 5 22 4 21 3 20 2 19 1 18 TIMER/TEMP. POWER FAN UP HIGH LOW ON/OFF MODE SELECT FAN SPEED DOWN AUTO STOP START TIMER MODE MITSUBISHI ELECTRIC Remote controller 1. COMBINATION OF AND OUTDOOR UNIT···3 2. TECHNICAL CHANGE···························3 3. PART NAMES AND FUNCTIONS··········3 4. SPECIFICATIONS ··································5 5. DATA·······················································9 6. OUTLINES AND DIMENSIONS ···········20 7. WIRING DIAGRAM·······························24 8. REFRIGERANT SYSTEM DIAGRAM ········25 9. OPERATION FLOW-CHART················27 10. MICROPROCESSOR CONTROL ········30 11. TROUBLE SHOOTING·························36 12. DISASSEMBLY PROCEDURE·············39 13. PARTS LIST··········································41 14. OPTIONAL PARTS·······························45 OC155-B--1.qxp 7/26/00 4:42 PM Page 2 OC155-B--1.qxp 1 7/26/00 4:42 PM Page 3 COMBINATION OF INDOOR AND OUTDOOR UNITS Change points Service Ref. PE-3EJA2.TH. PE-3EJA3.TH. PE-4EJSA2.TH. PE-5EJSA2.TH. PE-6EJSA2.TH. 2 3 VJA1.TH YJA1.TH VJC.TH YJC.TH — — — — — — — — — — — — — — — — NJA1 — — — Outdoor unit 4 5 6 VLJSA1.TH YJSA1.TH TJSA2 YJSA.TH TJSA1 YJSA.TH TJSA1 — — — — — — — — — — — — — — — — — — — — — — — — — — — — TECHNICAL CHANGE Differences with PE-3EJA2.TH / PU-3VJA1.TH, PU-3YJA1.TH (OC155 REVISED EDITION-A) Change points PE-3EJA2.TH PE-3EJA3.TH COOLING CAPACITY 24,600 Btu/h 7,200 W 25,600 Btu/h 7,500 W OUTDOOR UNIT PU-3VJA1.TH PU-3YJA1.TH PU-3VJC.TH PU-3YJC.TH COMPRESSOR OUTPUT 2.2kW(PU-3YJA1.TH) 2.4kW(PU-3YJC.TH) 3 PART NAMES AND FUNCTIONS ● Indoor (Main) Unit Air intake duct flange Air intake (sucks the air inside the room into the unit) Air outlet Air outlet duct flange 3 OC155-B--1.qxp 7/27/00 8:48 AM Page 4 ● Remote controller Settings remain in effect until changed. Air conditioner can be operated by simply pushing ON /OFF button once settings have been made. Display Panel Operating Panel TIMER / TEMP. ON / OFF button This button is used to change between display of room temperature and display of remaining timer during "AUTO STOP" operation. Green lamps light in selected display mode. Pushing button starts operation. Pushing again stops operation. Green lamp remains lit during operation Lamps display remaining timer time or room temperature. Remaining timer time display TIMER TEMP 12 29 11 28 COOL 10 27 DRY 9 26 FAN 8 25 7 24 6 23 5 22 4 21 3 20 2 19 1 18 TIMER/TEMP. UP POWER HIGH LOW ON/OFF MODE SELECT FAN SPEED DOWN Lamps indicate time remaining until timer stops timed operation. Green lamps corresponding to remaining number of hours light. AUTO STOP START TIMER MODE This button is used to change between cooling, ventilation and DRY operation modes. One of three green lamps lights to indicate mode in effect. FAN SPEED button MITSUBISHI ELECTRIC Room Temperature display Lamps display temperature settings and actual room temperatures. ● Temperature settings; Green lamps light. ● Temperature in room; Green lamps flash. MODE SELECT button This button is used to change between low and high fan speeds. One of two green lamps lights to indicate fan speed in effect. UP and DOWN buttons ● Temperature control (While "TEMP" green lamps is lit.) Use UP and DOWN buttons to set desired temperature between 18 and 29°C. ● Timed operation (While green "TIMER" lamp is lit.) Use UP and DOWN buttons to set timed operation between one and twelve hours. TIMER MODE button Used for selecting timed starting or stopping. Green lamps lights to indicate timer mode selected. (Example display readings are for explanations only ; actual display readings will differ.) Attention : ● Pushing UP and Down buttons together for more than two seconds will initiate "trial run" or "inspection" mode. Avoid pushing these buttons simultaneously during normal operation. Push ON / OFF button to cancel trial run or inspection mode if initiated by accident. ● All green lamps turn off when air conditioner is stopped. ● Avoid operation of buttons with fingernails or other sharp objects. Sharp objects may scratch operating panel. 4 OC155-B--1.qxp 7/26/00 4:43 PM 4 Page 5 SPECIFICATIONS 1. STANDARD SPECIFICATIONS Service Ref. Item 50Hz Cooling capacity W1 60Hz Cooling capacity W2 60Hz Total input (50/60Hz) W3 Service Ref. External finish Fan motor output 50Hz INDOOR UNIT PE-3EJA 2.TH 7,200 24,600 8,100 27,600 6,700 23,000 3.41 / 3.76 PE-3EJA 2.TH kW m3/min CFM m3/min CFM Pa (mmAq) Pa (mmAq) 0.2 19 - 22 671 - 777 22 - 26 777 - 918 49 (5) 69 (7) PE-4EJSA 2.TH 9,800 33,400 10,900 37,200 9,400 32,000 3.59 / 4.69 PE-4EJSA 2.TH Galvanized sheets Airflow Lo - High OUTDOOR UNIT W Btu/h W Btu/h W Btu/h kW 60Hz 0.3 27 - 34 953 - 1,200 27 - 34 953 - 1,200 62 (6.35) 62 (6.35) Remote controller & built-in 46 - 48 54 - 58 48 - 50 54 - 58 R1 R1 785 (31) 1,055 (41-1/2) 690 (27-1/6) 690 (27-1/6) 428 (16-7/8) 428 (16-7/8) 46 (101) 58 (128) W7 PU-3JA type W7 PU-4JSA type Munsell 5Y 7/1 Capillary tube 2.2 2.7 W6 32 / 38 32 / 38 0.085 0.065 + 0.065 50 (1,765) 95 (3,352) 50 (1,765) 95 (3,352) 52 / 53 54 / 55 870 (34-1/4) 870 (34-1/4) 295 + 24 (11-5/8 add 1) 850 (33-7/16) 1,258 (49-1/2) 73 (161) 94 (207) Ex. static pressure at 50Hz Hi - notch 60Hz Operation control & thermostat 50Hz dB Noise level Low - High W5 60Hz dB in. Unit drain thread W mm (in.) D mm (in.) Dimensions H mm (in.) kg (lbs) Weight Service Ref. External finish Refrigerant (R-22) control Compressor output kW Protection devices Crankcase heater W4 50/60Hz W Fan motor output kW 50Hz m3/min(CFM) Airflow 60Hz m3/min(CFM) 50/60Hz Noise level W5 dB W mm (in.) D Dimensions mm (in.) H mm (in.) Weight kg (lbs) NOTE : W1 Rating conditions (JIS B 8616) Indoor : D.B. 27°C (80°F), W.B.19°C (86°F) Outdoor : D.B. 35°C (95°F), W.B. 24°C (75°F) NOTE : W2 Rating conditions (SSA 385, 386) Indoor : D.B. 29°C (84°F), W.B.19°C (86°F) Outdoor : D.B. 46°C (115°F), W.B. 24°C (75°F) NOTE : W3 Total input based on indicated voltage. (Indoor / Outdoor) PE-4EJSA2.TH Service Ref. PE-3EJA2.TH 1ph 220V / 1ph 220V 1ph 220V / 3ph 380V 50Hz 1ph 220V / 1ph 220V 1ph 220V / 3ph 220V 60Hz Rating conditions (JIS B 8616) NOTE : W4 Capacity of crankcase heater (W) based on 220 volts. NOTE : W5 Noise level is measured in an unacoustic room based on JIS conditions. NOTE : W6 V , N ···Inner thermostat, HP switch, LP switch VL ···Inner thermostat, HP switch, LP switch, thermal switch. T, Y···Thermal switch, Reversed - phase protector, HP switch, LP switch NOTE : W7 PU-3JA type···PU-3VJA1.TH, 3YJA1.TH, 3NJA1 PU-4JSA type···PU-4VLJSA1.TH, 4YJSA1.TH, 4TJSA2 5 OC155-B--1.qxp 7/26/00 4:43 PM Page 6 Service Ref. Item 50Hz Cooling capacity W1 60Hz Cooling capacity W2 60Hz Total input (50/60Hz) W3 Service Ref. External finish Fan motor output 50Hz OUTDOOR UNIT INDOOR UNIT Airflow Lo - High 60Hz W Btu/h W Btu/h W Btu/h kW kW m3/min CFM m3/min CFM Pa (mmAq) Pa (mmAq) Ex. static pressure at 50Hz Hi - notch 60Hz Operation control & thermostat 50Hz dB Noise level Low - High W5 60Hz dB in. Unit drain thread W mm (in.) D mm (in.) Dimensions H mm (in.) kg (lbs) Weight Service Ref. External finish Refrigerant (R-22) control Compressor output kW Protection devices Crankcase heater 50/60Hz W Fan motor output kW 50Hz m3/min(CFM) Airflow 60Hz m3/min(CFM) Noise level W5 50/60Hz dB W mm (in.) Dimensions D mm (in.) H mm (in.) Weight kg (lbs) PE-5EJSA2.TH 12,100 41,300 13,500 46,100 11,000 37,500 5.10 / 6.06 PE-5EJSA2.TH Galvanized sheets 0.4 0.4 34 - 42 34 - 42 1,200 - 1,482 1,200 - 1,482 34 - 42 34 - 42 1,200 - 1,482 1,200 - 1,482 62 (6.35) 62 (6.35) 62 (6.35) 62 (6.35) Remote controller & built-in 54 - 58 54 - 58 54 - 58 54 - 58 R1 R1 1,255 (49-7/16) 1,255 (49-7/16) 690 (27-1/6) 690 (27-1/6) 428 (16-7/8) 428 (16-7/8) 72 (159) 72 (159) PU-5YJSA.TH, 5TJSA1 PU-6YJSA.TH, 6TJSA1 Munsell 5Y 7/1 Capillary tube 3.5 4.2/4.0 W6 W6 – – 0.10 + 0.10 0.10 + 0.10 100(3,530) 100(3,530) 100(3,530) 100(3,530) 55 / 55 56/56 970 (38-3/16) 970 (38-3/16) 345 + 24 (13-9/16 add 1) 1,258 (49-1/2) 1,258 (49-1/2) 114 (282) 117 (313) NOTE : W1 Rating conditions (JIS B 8616) Indoor : D.B. 27°C (80°F), W.B. 19°C (86°F) Outdoor : D.B. 35°C (95°F), W.B. 24°C (75°F) NOTE : W2 Rating conditions (SSA 385, 386) Indoor : D.B. 29°C (84°F), W.B. 19°C (86°F) Outdoor : D.B. 46°C (115°F), W.B. 24°C (75°F) NOTE : W3 Total input based on indicated voltage. (Indoor / Outdoor) Service Ref. PE-5/6EJSA2.TH 50Hz 60Hz PE-6EJSA2.TH 14,000 47,800 15,200 51,900 13,400 45,700 5.65 / 6.58 PE-6EJSA2.TH 1ph 220V / 3ph 380V 1ph 220V / 3ph 220V Rating conditions (JIS B 8616) NOTE : W4 Capacity of crankcase heater (W) based on 220 volts. NOTE : W5 Noise level is measured in an unacoustic room based on JIS conditions. NOTE : W6 Y : Inner thermostat, HP switch, Thermal switch T : Inner thermostat, HP switch, LP switch, Thermal switch 6 OC155-B--1.qxp 7/26/00 4:43 PM Page 7 Service Ref. Item 50Hz Cooling capacity W1 60Hz Cooling capacity W2 60Hz Total input (50/60Hz) W3 Service Ref. External finish Fan motor output 50Hz OUTDOOR UNIT INDOOR UNIT Airflow Lo - High 60Hz PE-3EJA 3.TH 7,500 25,600 8,100 27,600 6,700 23,000 3.41 / 3.76 PE-3EJA 3.TH Galvanized sheets 0.2 19 - 22 671 - 777 22 - 26 777 - 918 49 (5) 69 (7) Remote controller & built-in 46 - 48 48 - 50 R1 785 (31) 690 (27-1/6) 428 (16-7/8) 46 (101) PU-3VJC.TH, 3YJC.TH, 3NJA1 Munsell 5Y 7/1 Capillary tube (V)2.2, (Y)2.4 / (N)2.2 W6 32 / 38 0.085 50 (1,765) 50 (1,765) 52 / 53 870 (34-1/4) 295 + 24 (11-5/8 add 1) 850 (33-7/16) 73 (161) W Btu/h W Btu/h W Btu/h kW kW m3/min CFM m3/min CFM Pa (mmAq) Pa (mmAq) Ex. static pressure at 50Hz Hi - notch 60Hz Operation control & thermostat 50Hz dB Noise level Low - High W5 60Hz dB in. Unit drain thread W mm (in.) D mm (in.) Dimensions H mm (in.) kg (lbs) Weight Service Ref. External finish Refrigerant (R-22) control kW Compressor output Protection devices W Crankcase heater W4 50/60Hz kW Fan motor output 50Hz m3/min(CFM) Airflow 60Hz m3/min(CFM) 50/60Hz Noise level W5 dB W mm (in.) D Dimensions mm (in.) H mm (in.) Weight kg (lbs) NOTE : W1 Rating conditions (JIS B 8616) Indoor : D.B. 27°C (80°F), W.B. 19°C (86°F) Outdoor : D.B. 35°C (95°F), W.B. 24°C (75°F) NOTE : W2 Rating conditions (SSA 385, 386) Indoor : D.B. 29°C (84°F), W.B. 19°C (86°F) Outdoor : D.B. 46°C (115°F), W.B. 24°C (75°F) NOTE : W3 Total input based on indicated voltage. (Indoor / Outdoor) Service Ref. PE - 3EJA 3.TH 50Hz 1ph 220V / 1ph 220V, 3ph 380V 1ph 220V / 1ph 220V 60Hz Rating conditions (JIS B 8616) NOTE : W4 Capacity of crankcase heater (W) based on 220 volts. NOTE : W5 Noise level is measured in an unacoustic room based on JIS conditions. NOTE : W6 V , N ···Inner thermostat, HP switch, LP switch Y···Thermal switch, Reversed - phase protector, HP switch, LP switch 7 OC155-B--1.qxp 7/26/00 4:43 PM Page 8 2. POWER SUPPLY & MODEL NAMES Power supply 50Hz 60Hz 1ph. 3ph. 1ph. 3ph. Service Ref.(Indoor unit) 220, 230, 240V 380/220, 400/230, 415/240V 220V 220V PE - 3EJA 2.TH PU-3VJA1.TH PU-3YJA1.TH PU-3NJA1 — Service Ref.(Outdoor unit) PE - 3EJA 3.TH PE - 4EJSA 2.TH PE - 5EJSA 2.TH PE - 6EJSA 2.TH PU-3VJC.TH PU-4VLJSA1.TH — — PU-3YJC.TH PU-5YJSA.TH PU-4YJSA1.TH PU-6YJSA.TH PU-3NJA1 — — — PU-5TJSA1 PU-4TJSA2 — PU-6TJSA1 NOTE : 1. Power supply key N ········1ph, 220V, 60Hz V (L) ···1ph, 220, 230, 240V, 50Hz Y ··· 3ph, 380 / 220, 400 / 230, T ·········3ph, 220V, 60Hz 415 / 240V, 50Hz, 4wires 2. Primary power supplies for all indoor units are single - phase. 3. ELECTRICAL SPECIFICATIONS Rating conditions — JIS B 8616 Indoor : D.B. 27°C (80°F), W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F), W.B. 24°C (75°F) Series PE Indoor Unit (Single Phase) V : 220V 50Hz V : 230V 50Hz V : 240V 50Hz N : 220V 60Hz PE-3EJA2.TH PE-3EJA2.TH PE-3EJA2.TH PE-3EJA2.TH PE-3EJA3.TH PE-4EJSA2.TH PE-3EJA3.TH PE-4EJSA2.TH PE-3EJA3.TH PE-4EJSA2.TH PE-3EJA3.TH PE-4EJSA2.TH A 1.41 1.07 1.07 1.40 1.07 1.39 1.47 1.95 kW 0.30 0.23 0.24 0.31 0.25 0.32 0.32 0.42 A 2.6 2.4 2.5 2.6 2.6 2.6 2.1 2.6 PU-4 PU-3 PU-3 PU-4 PU-3 PU-4 PU-3 PU-4 Power supply (1 phase) Service Ref. Current Input Starting current Outdoor unit Power supply (1 phase) Y : 220V 50Hz Y : 230V 50Hz Y : 240V 50Hz T : 220V 60Hz Service Ref. PE-5EJSA2.TH PE-6EJSA2.TH PE-5EJSA2.TH PE-6EJSA2.TH PE-5EJSA2.TH PE-6EJSA2.TH PE-5EJSA2.TH PE-6EJSA2.TH Current 2.50 2.50 2.53 2.53 2.58 2.58 1.99 1.99 A Input 0.54 0.54 0.57 0.57 0.60 0.60 0.43 0.43 kW Starting current 4.1 4.1 4.1 4.1 4.1 4.1 3.1 3.1 A Outdoor unit PU-5 PU-6 PU-5 PU-6 PU-5 PU-6 PU-5 PU-6 8 OC155-B--1.qxp 7/26/00 4:43 PM 5 Page 9 DATA 1. PERFORMANCE DATA Cooling capacity 50Hz Service Ref. Temperature Outdoor D.B. 21°C (69.8°F) 25°C (77°F) 30°C (86°F) 32.2°C (90°F) 35°C (95°F) 40°C (104°F) 40.6°C (105°F) 45°C (113°F) 46°C (115°F) 50°C (122°F) 52°C (125.5°F) PE-3EJA2.TH 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C Evaporator airflow (m3/min) Bypass factors S.H.F. at rating conditions Notes : T.C. 7.2 7.7 7.9 8.0 8.2 8.7 7.1 7.5 7.8 7.9 8.0 8.5 6.8 7.3 7.5 7.6 7.7 8.2 6.7 7.1 7.4 7.5 7.6 8.1 6.5 7.0 7.2 7.3 7.4 7.9 6.2 6.7 6.9 7.0 7.1 7.6 6.2 6.6 6.9 6.9 7.1 7.6 5.9 6.4 6.6 6.7 6.8 7.3 5.9 6.3 6.5 6.6 6.7 7.2 5.6 6.0 6.2 6.3 6.5 6.9 5.5 5.9 6.1 6.2 6.3 6.8 Indoor D.B. (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) PE-4EJSA2.TH C.F. (T.I.) 0.81 0.82 0.83 0.83 0.84 0.86 0.84 0.85 0.86 0.86 0.87 0.89 0.90 0.92 0.93 0.93 0.94 0.96 0.93 0.95 0.96 0.97 0.97 0.99 0.96 0.99 1.00 1.00 1.01 1.04 1.03 1.06 1.07 1.08 1.08 1.11 1.04 1.06 1.08 1.08 1.09 1.12 1.10 1.12 1.14 1.15 1.16 1.20 1.11 1.14 1.15 1.16 1.17 1.21 1.16 1.19 1.21 1.22 1.23 1.28 1.19 1.22 1.24 1.25 1.26 1.31 T.C. 9.8 10.5 10.8 10.9 11.1 11.8 9.6 10.2 10.6 10.7 10.9 11.6 9.3 9.9 10.2 10.3 10.5 11.2 9.1 9.7 10.0 10.2 10.3 11.0 8.9 9.5 9.8 10.1 10.1 10.8 8.5 9.1 9.4 9.5 9.7 10.3 8.4 9.0 9.3 9.5 9.6 10.3 8.1 8.6 8.9 9.1 9.3 9.9 8.0 8.6 8.9 9.0 9.2 9.8 7.6 8.2 8.5 8.6 8.8 9.4 7.4 8.0 8.3 8.4 8.6 9.2 22 0.26 0.69 . 3 1. T.C : Total capacity ( ✕ 10 W) ... (Btu / h) =. (W) ✕ 3.4, (kcal / h) = (W) ✕ 0.86 C.F (T.I.) : Correction factors of Total input (Indoor unit input + Outdoor unit input) 2. (°F) = 32 + 9 / 5 (°C) Lower limit ... Indoor : D.B. 21°C (70°F), W.B. 15.5°C (60°F), 3. Guaranteed operating range (cooling) Upper limit ... Indoor : D.B. 35°C (95°F), W.B. 22.5°C (72.5°F), { 9 34 0.21 0.76 Outdoor : D.B. 21°C (70°F) Outdoor : D.B. 52°C (125.5°F) WVL ... Outdoor : D.B. 46°C (115°F) C.F. (T.I.) 0.81 0.82 0.83 0.83 0.84 0.86 0.84 0.85 0.86 0.86 0.87 0.89 0.90 0.92 0.93 0.93 0.94 0.96 0.93 0.95 0.96 0.97 0.97 0.99 0.96 0.99 1.00 1.00 1.01 1.04 1.03 1.06 1.07 1.08 1.08 1.11 1.04 1.06 1.08 1.08 1.09 1.12 1.10 1.12 1.14 1.15 1.16 1.20 1.11 1.14 1.15 1.16 1.17 1.21 1.16 1.19 1.21 1.22 1.23 1.28 1.19 1.22 1.24 1.25 1.26 1.31 OC155-B--1.qxp 7/26/00 4:43 PM Page 10 Cooling capacity 50Hz Service Ref. Temperature Outdoor D.B. 21°C (69.8°F) 25°C (77°F) 30°C (86°F) 32.2°C (90°F) 35°C (95°F) 40°C (104°F) 40.6°C (105°F) 45°C (113°F) 46°C (115°F) 50°C (122°F) 52°C (125.5°F) PE-3EJA3.TH T.C. 7.5 8.0 8.3 8.4 8.5 9.0 7.4 7.8 8.1 8.2 8.4 8.9 7.1 7.6 7.8 7.9 8.1 8.6 7.0 7.4 7.7 7.8 7.9 8.4 6.8 7.3 7.5 7.6 7.7 8.3 6.5 6.9 7.2 7.3 7.4 7.9 6.5 6.9 7.1 7.2 7.4 7.9 6.2 6.6 6.8 6.9 7.1 7.6 6.1 6.5 6.8 6.9 7.0 7.5 5.8 6.3 6.5 6.6 6.7 7.2 5.7 6.1 6.4 6.5 6.6 7.1 Indoor D.B. 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) Evaporator airflow (m3/min) Bypass factors S.H.F. at rating conditions Notes : 22 0.26 0.72 C.F. (T.I.) 0.81 0.82 0.83 0.83 0.84 0.86 0.84 0.85 0.86 0.86 0.87 0.89 0.90 0.92 0.93 0.93 0.94 0.96 0.93 0.95 0.96 0.97 0.97 0.99 0.96 0.99 1.00 1.00 1.01 1.04 1.03 1.06 1.07 1.08 1.08 1.11 1.04 1.06 1.08 1.08 1.09 1.12 1.10 1.12 1.14 1.15 1.16 1.20 1.11 1.14 1.15 1.16 1.17 1.21 1.16 1.19 1.21 1.22 1.23 1.28 1.19 1.22 1.24 1.25 1.26 1.31 . 3 1. T.C : Total capacity ( ✕ 10 W) ... (Btu / h) =. (W) ✕ 3.4, (kcal / h) = (W) ✕ 0.86 C.F (T.I.) : Correction factors of Total input (Indoor unit input + Outdoor unit input) 2. (°F) = 32 + 9 / 5 (°C) Lower limit ... Indoor : D.B. 21°C (70°F), W.B. 15.5°C (60°F), Outdoor : D.B. 21°C (70°F) 3. Guaranteed operating range (cooling) Upper limit ... Indoor : D.B. 35°C (95°F), W.B. 22.5°C (72.5°F), Outdoor : D.B. 52°C (125.5°F) { 10 OC155-B--1.qxp 7/26/00 4:43 PM Page 11 Cooling capacity 50Hz Service Ref. Temperature Outdoor D.B. 21°C (69.8°F) 25°C (77°F) 30°C (86°F) 32.2°C (90°F) 35°C (95°F) 40°C (104°F) 40.6°C (105°F) 45°C (113°F) 46°C (115°F) 50°C (122°F) 52°C (125.5°F) PE-5EJSA2.TH Indoor D.B. 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C Evaporator airflow (m3/min) Bypass factors S.H.F. at rating conditions (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) T.C. 12.1 12.9 13.3 13.5 13.7 14.6 11.9 12.7 13.1 13.2 13.5 14.3 11.4 12.2 12.6 12.8 13.0 13.8 11.2 12.0 12.4 12.5 12.8 13.6 11.0 11.7 12.1 12.3 12.5 13.3 10.5 11.2 11.6 11.7 12.0 12.8 10.4 11.1 11.5 11.7 11.9 12.7 10.0 10.7 11.0 11.2 11.4 12.2 9.9 10.6 10.9 11.0 11.2 12.1 8.9 9.6 9.9 10.0 10.3 10.6 7.9 8.5 8.8 8.9 9.1 9.4 42 0.18 0.82 C.F. (T.I.) 0.81 0.82 0.83 0.83 0.84 0.86 0.84 0.85 0.86 0.86 0.87 0.89 0.90 0.92 0.93 0.93 0.94 0.96 0.93 0.95 0.96 0.97 0.97 0.99 0.96 0.99 1.00 1.00 1.01 1.04 1.03 1.06 1.07 1.08 1.08 1.11 1.04 1.06 1.08 1.08 1.09 1.12 1.10 1.12 1.14 1.15 1.16 1.20 1.11 1.14 1.15 1.16 1.17 1.21 1.16 1.19 1.21 1.22 1.23 1.28 1.19 1.22 1.24 1.25 1.26 1.31 PE-6EJSA2.TH T.C. 14.1 15.0 15.4 15.6 15.9 16.8 13.7 14.6 15.1 15.3 15.6 16.6 13.2 14.1 14.6 14.8 15.0 16.0 13.0 13.9 14.3 14.5 14.8 15.7 12.7 13.5 14.0 14.2 14.5 15.4 12.1 13.0 13.4 13.6 13.8 14.8 12.1 12.9 13.3 13.5 13.8 14.7 11.5 12.4 12.8 13.0 13.2 14.1 11.4 12.2 12.6 12.7 13.0 14.0 10.3 11.1 11.5 11.6 11.9 12.3 9.1 9.8 10.2 10.3 10.5 10.9 42 0.16 0.77 . 3 Notes : 1. T.C : Total capacity ( ✕ 10 W) ... (Btu / h) =. (W) ✕ 3.4, (kcal / h) = (W) ✕ 0.86 C.F (T.I.) : Correction factors of Total input (Indoor unit input + Outdoor unit input) 2. (°F) = 32 + 9 / 5 (°C) Lower limit ... Indoor : D.B. 21°C (70°F), W.B. 15.5°C (60°F), Outdoor : D.B. 21°C (70°F) 3. Guaranteed operating range (cooling) Upper limit ... Indoor : D.B. 35°C (95°F), W.B. 22.5°C (72.5°F), Outdoor : D.B. 52°C (125.5°F) WVL ... Outdoor : D.B. 46°C (115°F) { 11 C.F. (T.I.) 0.81 0.82 0.83 0.83 0.84 0.86 0.84 0.85 0.86 0.86 0.87 0.89 0.90 0.92 0.93 0.93 0.94 0.96 0.93 0.95 0.96 0.97 0.97 0.99 0.96 0.99 1.00 1.00 1.01 1.04 1.03 1.06 1.07 1.08 1.08 1.11 1.04 1.06 1.08 1.08 1.09 1.12 1.10 1.12 1.14 1.15 1.16 1.20 1.11 1.14 1.15 1.16 1.17 1.21 1.16 1.19 1.21 1.22 1.23 1.28 1.19 1.22 1.24 1.25 1.26 1.31 OC155-B--1.qxp 7/26/00 4:43 PM Page 12 Cooling capacity 60Hz Service Ref. Temperature Outdoor D.B. 21°C (69.8°F) 25°C (77°F) 30°C (86°F) 32.2°C (90°F) 35°C (95°F) 40°C (104°F) 40.6°C (105°F) 45°C (113°F) 46°C (115°F) 50°C (122°F) 52°C (125.5°F) Indoor D.B. 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C Evaporator airflow (m3/min) Bypass factors S.H.F. at rating conditions Notes : PE-3EJA2.TH, PE-3EJA3.TH C.F. T.C. (T.I.) 8.1 0.81 8.7 0.82 8.9 0.83 9.0 0.83 9.2 0.84 9.7 0.86 7.9 0.84 8.5 0.85 8.7 0.86 8.9 0.86 9.0 0.87 9.6 0.89 7.7 0.90 8.2 0.92 8.4 0.93 8.5 0.93 8.7 0.94 9.3 0.96 7.5 0.93 8.0 0.95 8.3 0.96 8.4 0.97 8.6 0.97 9.1 0.99 7.3 0.96 7.8 0.99 8.1 1.00 8.2 1.00 8.4 1.01 8.9 1.04 7.0 1.03 7.5 1.06 7.8 1.07 7.9 1.08 8.0 1.08 8.5 1.11 7.0 1.04 7.5 1.06 7.8 1.08 7.9 1.08 8.0 1.09 8.5 1.12 6.7 1.10 7.5 1.12 7.4 1.14 7.5 1.15 8.0 1.16 8.2 1.20 6.6 1.11 7.1 1.14 7.3 1.15 7.4 1.16 7.6 1.17 8.1 1.21 6.3 1.16 6.8 1.19 7.0 1.21 7.1 1.22 7.3 1.23 7.8 1.28 6.2 1.19 6.6 1.22 6.9 1.24 7.0 1.25 7.1 1.26 7.6 1.31 26 0.35 0.67 (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) PE-4EJSA2.TH T.C. 10.9 11.7 12.0 12.2 12.4 13.1 10.7 11.4 11.8 11.9 12.1 12.9 10.3 11.0 11.3 11.5 11.7 12.5 10.1 10.8 11.2 11.3 11.5 12.3 9.9 10.5 10.9 11.0 11.3 12.0 9.4 10.1 10.4 10.6 10.8 11.5 9.4 10.0 10.4 10.5 10.7 11.4 9.0 9.6 10.0 10.1 10.3 11.0 8.9 9.5 9.9 10.0 10.2 10.9 8.5 9.1 9.5 9.6 9.8 10.5 8.3 8.9 9.2 9.4 9.6 10.3 34 0.23 0.74 C.F. (T.I.) 0.81 0.82 0.83 0.83 0.84 0.86 0.84 0.85 0.86 0.86 0.87 0.89 0.90 0.92 0.93 0.93 0.94 0.96 0.95 0.96 0.97 0.97 1.00 0.99 0.96 0.99 1.00 1.00 1.01 1.04 1.03 1.06 1.07 1.08 1.08 1.11 1.04 1.06 1.08 1.08 1.09 1.12 1.10 1.12 1.14 1.15 1.16 1.20 1.11 1.14 1.15 1.16 1.17 1.21 1.16 1.19 1.21 1.22 1.23 1.28 1.19 1.22 1.24 1.25 1.26 1.31 . 3 1. T.C : Total capacity ( ✕ 10 W) ... (Btu / h) =. (W) ✕ 3.4, (kcal / h) = (W) ✕ 0.86 C.F (T.I) : Correction factors of Total input (Indoor unit input + Outdoor unit input) 2. (°F) = 32 + 9 / 5 (°C) Lower limit ... Indoor : D.B. 21°C (70°F), W.B. 15.5°C (60°F), Outdoor : D.B. 21°C (70°F) 3. Guaranteed operating range (cooling) Upper limit ... Indoor : D.B. 35°C (95°F), W.B. 22.5°C (72.5°F), Outdoor : D.B. 52°C (125.5°F) { 12 OC155-B--1.qxp 7/26/00 4:43 PM Page 13 Cooling capacity 60Hz Service Ref. Temperature Outdoor D.B. 21°C (69.8°F) 25°C (77°F) 30°C (86°F) 32.2°C (90°F) 35°C (95°F) 40°C (104°F) 40.6°C (105°F) 45°C (113°F) 46°C (115°F) 50°C (122°F) 52°C (125.5°F) PE-5EJSA2.TH Indoor D.B. 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C 16°C 18°C 19°C 19.4°C 20°C 22°C Evaporator airflow (m3/min) Bypass factors S.H.F. at rating conditions Notes : T.C. 13.6 14.4 14.9 15.1 15.3 16.2 13.2 14.1 14.6 14.8 15.0 16.0 12.8 13.6 14.0 14.2 14.5 15.4 12.5 13.4 13.8 14.0 14.3 15.2 12.2 13.1 13.5 13.7 13.9 14.9 11.7 12.5 12.9 13.1 13.4 14.3 11.6 12.4 12.9 13.0 13.3 14.2 11.1 11.9 12.3 12.5 12.7 13.6 11.0 11.8 12.1 12.3 12.5 13.5 9.9 10.7 11.1 11.2 11.4 11.8 8.8 9.4 9.8 9.9 10.1 10.5 (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F) (67°F) (68°F) (71.6°F) 42 0.19 0.77 C.F. (T.I.) 0.81 0.82 0.83 0.83 0.84 0.86 0.84 0.85 0.86 0.86 0.87 0.89 0.90 0.92 0.93 0.93 0.94 0.96 0.93 0.95 0.96 0.97 0.97 0.99 0.96 0.99 1.00 1.00 1.01 1.04 1.03 1.06 1.07 1.08 1.08 1.11 1.04 1.06 1.08 1.08 1.09 1.12 1.10 1.12 1.14 1.15 1.16 1.20 1.11 1.14 1.15 1.16 1.17 1.21 1.16 1.19 1.21 1.22 1.23 1.28 1.19 1.22 1.24 1.25 1.26 1.31 PE-6EJSA2.TH T.C. 15.3 16.2 16.8 17.0 17.3 18.3 14.9 15.9 16.4 16.6 16.9 18.0 14.4 15.3 15.8 16.0 16.3 17.4 14.1 15.1 15.5 15.7 16.0 17.1 13.8 14.7 15.2 15.4 15.7 16.7 13.2 14.1 14.6 14.7 15.0 16.0 13.1 14.0 14.5 14.7 15.0 16.0 12.5 13.4 13.9 14.1 14.4 15.3 12.4 13.3 13.7 13.8 14.1 15.2 11.2 12.0 12.4 12.6 12.9 13.3 9.9 10.6 11.0 11.2 11.4 11.8 42 0.19 0.73 C.F. (T.I.) 0.81 0.82 0.83 0.83 0.84 0.86 0.84 0.85 0.86 0.86 0.87 0.89 0.90 0.92 0.93 0.93 0.94 0.96 0.93 0.95 0.96 0.97 0.97 0.99 0.96 0.99 1.00 1.00 1.01 1.04 1.03 1.06 1.07 1.08 1.08 1.11 1.04 1.06 1.08 1.08 1.09 1.12 1.10 1.12 1.14 1.15 1.16 1.20 1.11 1.14 1.15 1.16 1.17 1.21 1.16 1.19 1.21 1.22 1.23 1.28 1.19 1.22 1.24 1.25 1.26 1.31 . 3 1. T.C : Total capacity ( ✕ 10 W) ... (Btu / h) =. (W) ✕ 3.4, (kcal / h) = (W) ✕ 0.86 C.F (T.I) : Correction factors of Total input (Indoor unit input + Outdoor unit input) 2. (°F) = 32 + 9 / 5 (°C) Lower limit ... Indoor : D.B. 21°C (70°F), W.B. 15.5°C (60°F), Outdoor : D.B. 21°C (70°F) 3. Guaranteed operating range (cooling) Upper limit ... Indoor : D.B. 35°C (95°F), W.B. 22.5°C (72.5°F), Outdoor : D.B. 52°C (125.5°F) { 13 OC155-B--1.qxp 7/26/00 4:43 PM Page 14 Cooling capacity correction factors 50Hz Service Ref. PE-3EJA2.TH PE-3EJA3.TH PE-4EJSA2.TH PE-5EJSA2.TH PE-6EJSA2.TH Refrigerant piping length (one way) 5m (16ft) 10m (33ft) 15m (49ft) 20m (66ft) 25m (82ft) 30m (98ft) 35m (115ft) 40m (131ft) 45m (148ft) 50m (164ft) 1.0 0.978 0.962 0.948 0.934 0.921 — — — — 1.0 1.0 1.0 0.984 0.978 0.971 0.974 0.962 0.950 0.964 0.948 0.931 0.954 0.934 0.912 0.944 0.921 0.896 0.935 0.908 0.880 0.926 0.896 0.864 — 0.884 0.850 — 0.875 0.840 Cooling capacity correction factors 60Hz Service Ref. PE-3EJA2.TH PE-3EJA3.TH PE-4EJSA2.TH PE-5EJSA2.TH PE-6EJSA2.TH Refrigerant piping length (one way) 5m (16ft) 10m (33ft) 15m (49ft) 20m (66ft) 25m (82ft) 30m (98ft) 35m (115ft) 40m (131ft) 45m (148ft) 50m (164ft) 1.0 0.971 0.950 0.931 0.913 0.896 — — — — 1.0 1.0 1.0 0.980 0.971 0.960 0.966 0.950 0.933 0.952 0.931 0.908 0.939 0.913 0.885 0.926 0.896 0.894 0.914 0.880 0.845 0.902 0.864 0.828 — 0.850 0.812 — 0.840 0.800 14 OC155-B--1.qxp 7/26/00 4:43 PM Page 15 2. STANDARD OPERATION DATA Service Ref. PE-3EJA 2.TH Total Mode Cooling Cooling Cooling Cooling Capacity W 7,200 8,100 9,800 10,900 Input kW 3.41 3.76 3.59 4.69 PE-3EJA 2.TH Indoor unit Service Ref. Electrical Circuit Phase, Hz 1, 50 1, 60 1, 50 1, 60 V 220 220 220 220 Amperes A 1.07 1.41 1.41 1.95 PU-3VJA1.TH PU-3NJA1 PU-4YJSA1.TH PU-4TJSA2 1, 50 1, 60 3, 50 3, 60 V 220 220 380 220 A MPa (kgf/F) MPa (kgf/F) 15.1 2.04 (20.8) 0.465 (4.7) 17.6 2.20 (22.4) 0.44 (4.5) 5.7 1.91 (19.5) 0.54 (5.5) 12.2 2.14 (21.8) 0.51 (5.2) : 64.1 73.2 77.4 77.5 : 52.4 54.2 50.3 54.9 : 4.5 1.3 9.2 6.7 m 5 5 5 5 D.B. : 27 27 27 27 temperature W.B. : 19 19 19 19 Discharge air temperature D.B. : 13.1 14.2 14.6 15.3 D.B. : 35 35 35 35 temperature W.B. : 24 24 24 24 Outdoor unit Service Ref. Phase, Hz Amperes Refrigerant Circuit PE-4EJSA 2.TH Volts Volts Outdoor side Indoor side PE-4EJSA 2.TH Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Ref. pipe length Intake air Intake air The unit of pressure has been changed to Mpa based on SI (International System of Units) in accordance with I.S.O. (International Organization for Standardization). Of/F F) The conversion factor is : 1(Mpa) =10.2 (O 15 OC155-B--1.qxp 7/26/00 4:43 PM Page 16 Service Ref. PE-5EJSA 2.TH Total Mode Cooling Cooling Cooling Cooling Capacity W 12,100 13,500 14,000 15,200 Input kW 5.10 6.06 5.65 6.58 PE-5EJSA2.TH Indoor unit Service Ref. Electrical Circuit Phase, Hz 1, 50 1, 60 1, 50 1, 60 V 220 220 220 220 Amperes A 2.50 1.99 2.50 1.99 PU-5YJSA.TH PU-5TJSA1 PU-6YJSA.TH PU-6TJSA1 3, 50 3, 60 3, 50 3, 60 V 380 220 380 220 A MPa (kgf/F) MPa (kgf/F) 8.15 1.86 (19.0) 0.48 (4.9) 16.83 1.98 (20.2) 0.43 (4.4) 8.63 1.95 (19.9) 0.44 (4.5) 18.70 2.01 (20.5 ) 0.40 (4.1) : 72.2 78.3 77.8 81 : 49.3 51.9 50.8 52.1 : - 0.9 1.6 1.7 - 0.5 m 5 5 5 5 D.B. : 27 27 27 27 temperature W.B. : 19 19 19 19 Discharge air temperature D.B. : 15.5 14.9 14.5 14.1 D.B. : 35 35 35 35 temperature W.B. : 24 24 24 24 Outdoor unit Service Ref. Phase, Hz Amperes Refrigerant Circuit PE-6EJSA2.TH Volts Volts Outdoor side Indoor side PE-6EJSA 2.TH Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Ref. pipe length Intake air Intake air The unit of pressure has been changed to Mpa based on SI (International System of Units) in accordance with I.S.O. (International Organization for Standardization). Of/F F) The conversion factor is : 1(Mpa) =10.2 (O 16 OC155-B--1.qxp 7/26/00 4:43 PM Page 17 Service Ref. PE-3EJA 3.TH Total Mode Cooling Cooling Capacity W 7,500 8,100 Input kW 3.41 3.76 PE-3EJA 3.TH Indoor unit Service Ref. Electrical Circuit Phase, Hz V 220 220 Amperes A 1.07 1.41 PU-3VJC.TH PU-3NJA1 1, 50 1, 60 V 220 220 A MPa (kgf/F) MPa (kgf/F) 15.1 2.04 (20.8) 0.46 (4.7) 17.6 2.20 (22.4) 0.44 (4.5) : 88.1 73.2 : 52.4 54.2 : 4.5 1.3 m 5 5 : 27 27 : 19 19 : 15.0 14.2 : 35 35 : 24 24 Outdoor unit Service Ref. Phase, Hz Amperes Refrigerant Circuit 1, 60 Volts Volts Outdoor side Indoor side 1, 50 Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Ref. pipe length D.B. Intake air temperature W.B. Discharge air temperature D.B. D.B. Intake air temperature W.B. The unit of pressure has been changed to Mpa based on SI (International System of Units) in accordance with I.S.O. (International Organization for Standardization). Of/F F) The conversion factor is : 1(Mpa) =10.2 (O 17 OC155-B--1.qxp 7/26/00 4:43 PM Page 18 3. FAN PERFORMANCE AND CORRECTED AIRFLOW Service Ref. : PE-3EJA2.TH PE-3EJA3.TH 50Hz 60Hz Recommended range Recommended range 150 150 100 Hi Lo 50 0 16 Hi External static pressure(Pa) (1Pa = 0.1mmAq) External static pressure(Pa) (1Pa = 0.1mmAq) Airflow (m /min) (1m /min = 35.3CFM) 18 20 100 Lo 50 0 22 19 20 22 24 60Hz 1.0 0.95 Capacity Input 0.9 16 18 20 22 Correction factor Correction factor 50Hz 26 1.0 0.95 0.9 19 20 Airflow (m /min) 22 24 Airflow (m /min) Service Ref. : PE-4EJSA 2.TH 50Hz 60Hz Recommended range Recommended range 150 150 External static pressure(Pa) (1Pa = 0.1mmAq) External static pressure(Pa) (1Pa = 0.1mmAq) Hi 100 Lo 50 0 20 22 25 30 35 37 40 Hi 100 Lo 50 0 Airflow (m /min) 20 22 25 60Hz Capacity 0.95 0.9 Input 20 22 25 30 35 37 Airflow (m /min) Correction factor Correction factor 50Hz 1.05 1.0 30 35 37 40 Airflow (m /min) 1.05 1.0 0.95 0.9 20 22 25 30 35 37 Airflow (m /min) 18 26 OC155-B--1.qxp 7/26/00 4:43 PM Page 19 Service Ref. : PE-5EJSA 2.TH 50Hz 60Hz Recommended range Recommended range 150 150 Hi 50 0 External static pressure(Pa) (1Pa = 0.1mmAq) External static pressure(Pa) (1Pa = 0.1mmAq) Hi 100 Lo 27 30 35 40 45 4850 100 Lo 50 0 Airflow (m /min) 27 30 35 1.0 Capacity 0.95 Input 27 30 35 40 45 50 60Hz 45 48 Correction factor Correction factor 50Hz 1.05 0.9 40 Airflow (m /min) 1.05 1.0 0.95 0.9 Airflow (m /min) 27 30 35 40 45 Airflow (m /min) Service Ref. : PE-6EJSA 2.TH 50Hz 60Hz Recommended range Recommended range 150 150 Hi 50 0 External static pressure(Pa) (1Pa = 0.1mmAq) External static pressure(Pa) (1Pa = 0.1mmAq) Hi 100 Lo 27 30 35 40 45 48 50 100 Lo 50 0 Airflow (m /min) 27 30 35 1.05 1.0 Capacity 0.95 Input 27 30 35 40 45 60Hz 45 48 Airflow (m /min) Correction factor Correction factor 50Hz 0.9 40 Airflow (m /min) 1.05 1.0 0.95 0.9 27 30 35 40 Airflow (m /min) 19 45 50 OC155-B--1.qxp 6 7/27/00 10:22 AM Page 20 OUTLINES AND DIMENSIONS Unit : mm (inch) 1. INDOOR UNIT PE-3EJA2.TH PE-3EJA3.TH 672(26 1/ 2) 11 600(24) 339(13 3/8) 20(13/16) 40 155 155 155 22.5 24.5 145 (3·9/16) 90 15 145 25 125 35 125 25 175 15 15 (2 3/4) 70 130 250 20 690(27 3/16) 530(20 7/8) 20 200(7 7/8) 200(7/8) 59 50 44 15 70 11 (2 3/8) 75 60 265(10 1/2) 10(3/8) 418(16 1/2) (4 3/16) 100 (2 3/4) 530(7 7/8) 70 35 20 (13/16) 510(20 1/8) 105 900(36) 345(13 5/8) (11 13/16) 300 11 25 85 85 25 381(15) 10(3/8) 730(28 3/4) 650(25 5/8) 40 300(11 13/16) 14 220 (8 7/16) 128 235(9 1/4) (5 1/16) 3.2 40 1 Refrigerant-pipe flared connection [9.52 (3/8) 12 Suspension bolt holes (4-[12 (1/2)) 2 Refrigerant-pipe flared connection [15.88 (5/8) 13 14-[3 (1/8) holes 3 Electrical parts box 14 For air outlet duct connection (12-[3 (1/8) holes) 4 Drainage pan 15 Air outlet 5 Drainage pipe connection R1 (male) 16 Mounting plate 6 Service panel (Indoor coil thermistor) 17 Air outlet duct flange 7 Room temperature thermistor 18 Heat insulator t10 (3/8) 8 Heat insulator t10 (3/8) 19 Service space (opening) in the ceiling 9 Air intake duct flange 20 Service panel (Room temperature thermistor) 10 Air intake 21 Duct earth 11 Wiring entry (2-[22 (7/8) holes) 20 OC155-B--1.qxp 7/27/00 10:22 AM Page 21 Unit : mm (inch) PE-4EJSA 2.TH (11 13/16) 300 600(24) 980(38 9/16) 11 345(13 5/8) 339(13·3/8) 4 65(=260) 39.5 65 15 40 175 200(7/8) 22.5 7 65(=455) 35 15 65 15 22.5 (2 3/4) 70 130 250 530(20 7/8) 20 960(27 3/16) 200(7 7/8) 20 11 (3·9/16) 90 15 65 63 55 40 10(3/8) 418(16·1/2) 20(13/16) 11 65(=715) 70 44 35 (3·9/16) (9 5/8) 245 20 (13/16) 795(31 5/16) 90 (3 3/8) (2 3/4) 85 70 100 (2 3/4) 530(7 7/8) 70 900(36) 11 65 27.5 3 65(=195) 381(15) 40 27.5 10(3/8) 14 250(6 13/16) (3 7/8) 210(8 1/4) 1000(3 15/16) 920(36 1/4) 500(19 11/16) 98 3.2 40 1 Refrigerant-pipe flared connection [9.52 (3/8) 12 Suspension bolt holes (4-[12 (1/2)) 2 Refrigerant-pipe flared connection [19.05 (3/4) 13 34-[3 (1/8) holes 3 Electrical parts box 14 For air outlet duct connection (24-[3 (1/8) holes) 4 Drain pan 15 Air outlet 5 Drain pipe connection R1 (male) 16 Mounting plate 6 Service panel (Indoor coil thermistor) 17 Air outlet duct flange 7 Room temperature thermistor 18 Heat insulator t10 (3/8) 8 Heat insulator t10 (3/8) 19 Service space (opening) in the ceiling 9 Air intake duct flange 20 Service panel (Room temperature thermistor) 10 Air intake 21 Duct earth 11 Wiring entry (2-[22 (7/8) holes) 21 OC155-B--1.qxp 7/27/00 10:22 AM Page 22 PE-5EJSA 2.TH PE-6EJSA 2.TH Unit : mm (inch) (11 13/16) 300 600(24) 1142(44 15/16) 11 339(13 3/8) 40 65 (3 9/16) 90 15 15 175 200(7 7/8) 13 65(=845) 27.5 15 65 15 27.5 (2 3/4) 70 130 250 530(20 7/8) 20 1160(15 11/16) 200(7 7/8) 20 4 65(=260) 39.5 63 55 65 11 14 65(=910) 70 40 10(3/8) 418(16 1/2) 20(13/16) (9 5/8) 245 44 35 70 345(13 5/8) 995(39 3/16) 90 20 (13/16) (3 9/16) (3 3/8) (2 3/4) 85 70 100 530(7 7/8) 900(36) 11 65 27.5 3 65(=195) 35 10(3/8) 40 14 250(6 13/16) (3 7/8) 110(4 5/16) 27.5 381(15) 98 3.2 40 1200(47 1/4) 1120(44 1/8) 900(35 7/16) 1 Refrigerant-pipe flared connection [9.52 (3/8) 12 Suspension bolt holes (4-[12 (1/2)) 2 Refrigerant-pipe flared connection [19.05 (3/4) 13 40-[3 (1/8) holes 3 Electrical parts box 14 For air outlet duct connection (36-[3 (1/8) holes) 4 Drain pan 15 Air outlet 5 Drain pipe connection R1 (male) 16 Mounting plate 6 Service panel (Indoor coil thermistor) 17 Air outlet duct flange 7 Room temperature thermistor 18 Heat insulator t10 (3/8) 8 Heat insulator t10 (3/8) 19 Service space (opening) in the ceiling 9 Air intake duct flange 20 Service panel (Room temperature thermistor) 10 Air intake 21 Duct earth 11 Wiring entry (2-[22 (7/8) holes) 22 OC155-B--1.qxp 7/27/00 10:22 AM Page 23 2. REMOTE CONTROLLER Unit : mm 12 96.5 90.5 3 Upper side wiring arrangement opening 3.6 12 8 6 Rear side wiring arrangememt opening 10 27 9 26 8 25 7 24 6 23 5 22 4 21 3 20 2 19 1 18 TIMER/TEMP. POWER COOL DRY FAN UP HIGH LOW ON/OFF 46 28 MODE SELECT FAN SPEED DOWN AUTO STOP START TIMER MODE 4.6 29 11 83.5 TEMP 12 108 117 69 TIMER 3 75 3 3 11.6 9.2 MITSUBISHI ELECTRIC 108 117 Fixing hole Remote controller cable installation ●For exposed remote controller cable installation ●For recessed remote controller cable installation Exposed remote controller cable Remote controller cable Conduit tube (local arrangement) TIMER TEMP 12 29 11 28 COOL 10 27 DRY 9 26 8 25 7 24 6 23 5 22 4 21 3 20 2 19 1 18 TIMER/TEMP. POWER FAN UP HIGH LOW ON/OFF MODE SELECT FAN SPEED DOWN AUTO STOP START TIMER MODE MITSUBISHI ELECTRIC Switch box (local arrangement) Cable can be connected only to the top of the remote controller. (Right side, left side, and buttom are not possible.) Set screw (match with switch box), local arrangement. Note : The cable for the remote controller has 10m (39ft) length and 12-core with connectors O.D. 5.8. 23 OC155-B--1.qxp 7/26/00 4:43 PM 7 Page 24 WIRING DIAGRAM PE-3EJA2.TH / PE-3EJA3.TH / PE-4EJSA2.TH / PE-5EJSA2.TH / PE-6EJSA2.TH SYMBOL NAME SYMBOL C1 FAN MOTOR CAPACITOR CN120<I.B> REMOTE CONTROLLER TRANSMISSION WIRE CONNECTOR NAME SYMBOL TEMPERATURE / TIMER REMAINING TIME INDICATOR LED LD13-24<R.B> MF1 NAME R.B REMOTE CONTROLLER BOARD T TRANSFORMER TB1 POWER SUPPLY TERMINAL BLOCK TB2 INDOOR / OUTDOOR CONNECTING WIRE TERMINAL BLOCK RT1 ROOM TEMPERATURE THERMISTOR (0°C / 15kΩ, 25°C / 5.4kΩ DETECT) RT2 INDOOR COIL THERMISTOR ( 0°C / 15kΩ, 25°C / 5.4kΩ DETECT) INDOOR FAN MOTOR CN51<I.B> REMOTE INDICATOR CONNECTOR REMOTE CONTROLLER TRANSMISSION WIRE SW1<I.B> CONNECTOR SW2<I.B> FUNCTION SWITCH CNR120<R.B> FI,2<I.B> FUSE (6.3A 250V) SW3<I.B> EMERGENCY OPERATION SWITCH I.B INDOOR CONTROLLER BOARD SW1<R.B> ON / OFF SWITCH LD1<R.B> RUN INDICATOR LED SW2<R.B> OPERATION MODE SWITCH LD3<R.B> COOLING INDICATOR LED SW3<R.B> FAN HIGH / LOW SWITCH X5<I.B> FAN MOTOR AUXILIARY RELAY LD4<R.B> FAN MODE INDICATOR LED SW5<R.B> INDICATOR SWITCH X6<I.B> FAN MOTOR AUXILIARY RELAY LD5<R.B> FAN HIGH INDICATOR LED ZNR<I.B> VARISTOR LD7<R.B> INDICATOR MODE TEMPERATURE LED JR FUNCTION SELECTOR JUMPER RESISTORS LD8<R.B> INDICATOR MODE TIMER LED LD9<R.B> DRY INDICATOR LED LD10<R.B> FAN LOW INDICATOR LED LD11<R.B> OFF TIMER INDICATOR LED LD12<R.B> ON TIMER INDICATOR LED UNIT SWITCH SW6<R.B> TEMPERATURE TIMER SETTING UP SWITCH SW7<R.B> TEMPERATURE TIMER SETTING DOWN SWITCH SW8<R.B> TIMER CONTINUOUS ON / OFF SWITCH TB1 RED BLU GRN/YLW MF1 10.6VAC 220V 230V 240V POWER SUPPLY ~ (1 PHASE) 220-240V 220V 50Hz 60Hz 14.5VAC RED ORN YLW BLK BLU YLW WHT RED ORN 2 3 4 1 5 6 L N T 123 123 1234 JR CN20 INTAKE CN2A TWIN-1 1 2 ON OFF CN21 PIPE 12 1 TO.RC CN120 01 02 03 04 05 06 1 2 3 R.B HEATER CN31 ON OFF SW3 Remote control transmission line DC 12V with 12 core connector LD8 LD7 ORN YLW TIMER CN2 SW2 1 2 3 4 5 DRAIN CN50 SW1 Remote controller RED RED BRN BRN 1 2 3 4 CN4T TRANS ZNR X6 X5 CN2B TWIN-2 CNT TRANS TB2 L.TEST CN28 X5 X6 1 3 OUTDOOR MULTIPLE CN30 CN51 1 2 3 CND 1 3 POWER F2 F1 1 2 C1 FAN1 1 3 5 7 WHT YLW RED BLU BLK BLU Indoor unit I.B 1 2 LD13 LD14 LD15 LD16 LD17 LD18 LD19 LD20 LD21 LD22 LD23 LD24 CNR120 LD1 LD3 LD9 LD4 SW6 LD5 LD10 SW1 SW5 SW2 SW3 SW7 LD11 TO OUTDOOR UNIT SW8 CONNECTING WIRES LD12 RT1 RT2 DC 12V(non-polar) NOTES: 1. Since the indoor transformer (T) is connected with 220V wiring, if 230V or 240V power is used, change the wiring connection as shown fig : 1 w. When power supply is fig w1 240V 240 YELLOW 230 ORANGE 230V 220 RED Since the indoor fan motor (MF1) is connected with 220V 60Hz power, if 200V~240V 50Hz power is used, change the wiring connection as shown fig : 2 w. fig w2 Indoor fan motor (MF1) for 200V ~ 240V 50Hz. BLUE LD 200—220 230—240 YELLOW LD 220 BLUE 2. Be sure to refer the outdoor unit electric wiring diagram before wiring of outdoor side unit. 3. Symbols used in wiring diagram above are. / : Terminal block, : Connector. 4. Emergency operation If remote controller or microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch [SW3<I. B>] on the indoor controller board. [Check items] (1) Compressor and fan. (2) Check the trouble position using self diagnostic function. If the result of self diagnosis indicates protective device such as freeze protection is functioning emergency operation is not possible unless the cause is removed. (3) In emergency operation, the operation made by only ON / OFF circuit breaker manually [ON / OFF with remote controller is not possible]. [Emergency operation procedure] (1) Cooling is possible by setting 1 . 2 ON and 3 OFF for the dip switch (SW3<I.B>) at indoor controller board. (2) Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker in this order. (3) During emergency operation indoor fan runs at high. (4) Thermostat will not function. (5) Do not cooling for more than 10 hours (the indoor unit heat exchanger can freeze). 24 DWG NO. BG79N636H01 OC155-B--1.qxp 7/26/00 4:43 PM 8 Page 25 REFRIGERANT SYSTEM DIAGRAM Unit : mm PE-3EJA2.TH / PU-3VJA1.TH, PU-3YJA1.TH, PU-3NJA1 PE-3EJA3.TH, / PU-3NJA1 Refrigerant pipe [15.88(5/8") (With insulation) option PE-3EJA 2.TH Low pressure switch Frexible tube Ball Valve Indoor heat exchanger High pressure switch Check plug Charge plug Strainer Flared connection Muffier Indoor coil thermistor RT2 PU-3A type Flared connection Outdoor heat exchanger Accumulator Compressor Capillary tube For injection Distributor with strainer Capillary tube (O.D. 3.2 I.D. 1.8 - L800) 2pcs Ball Valve (With service port) Refrigerant pipe [9.52(3/8") (With insulation) option Flow of refrigerant PE-3EJA3.TH / PU-3VJC.TH, PU-3YJC.TH PE-3EJA3.TH Indoor heat exchanger Refrigerant pipe [15.88(5/8") (With insulation) option Low pressure Flexible tube strainer switch Ball valve Indoor heat exchanger Charge pIug PU-3C type High pressure switch Outdoor heat exchanger Check pIug Flared connection strainer Flared connection Indoor coil thermistor RT2 Accumulator Compressor Distributor with strainer Capillary tube (O.D. 3.2 oI.D. 1.8 o L800) o2pcs Ball valve (with service port) Refrigerant pipe [9.52(3/8") (with heat insulator) option Flow of refrigerant 25 D.P.R. (Discharge pressure regulator) OC155-B--1.qxp 7/26/00 4:43 PM Page 26 Unit : mm PE-4EJSA2.TH / PU-4VLJSA1.TH, PU-4YJSA1.TH, PU-4TJSA2 Refrigerant pipe [19.05(3/4") (With insulator) option PE-4EJSA2.TH Low pressure switch Flexible tube Ball Valve Charge plug High pressure switch Check plug Strainer Flared connection Indoor heat exchanger PU-4 type Outdoor heat exchanger Muffler Indoor coil thermistor RT2 Flared connection Accumulator Compressor Capillary tube For injection (Only PU-4TJSA, 4YJSA) Distributor with strainer Ball Valve (With service port) Refrigerant pipe [9.52(3/8") (With insulator) option Capillary tube (O.D.3.2 I.D.1.8 - L1360) 2pcs Flow of refrigerant PE-5EJSA2.TH / PU-5YJSA.TH, PU-5TJSA1 PE-6EJSA2.TH / PU-6YJSA.TH, PU-6TJSA1 INDOOR UNIT PE-5EJSA2.TH PE-6EJSA2.TH OUTDOOR UNIT Refrigerant pipe [19.05 (3/4") (With insulator) option Low pressure switch (only PU-5,6TJSA1) Flexible tube PU-5 type PU-6 type Check plug Charge plug High pressure switch Ball valve Thermal switch Indoor heat exchanger Indoor coil thermistor RT2 Flared connection Outdoor heat exchanger Flared connection Distributor with strainer Accumulator Compressor Capillary tube PU-5Y·TJSA (O.D. 4.0 oI.D. 2.4 – L840)o2pcs PU-6YJSA (O.D. 4.0 oI.D. 2.4 – L1200)o2pcs PU-6TJSA (O.D. 4.0 oI.D. 2.4 – L740)o2pcs Ball valve (with service port) Refrigerant pipe [9.52 (3/8") (With insulator) option Strainer DPR Capillary tube PU-5Y·TJSA (O.D. 4.0 oI.D. 2.4 – L400) PU-6Y·TJSA (O.D. 4.0 oI.D. 2.4 – L200) Flow of refrigerant 26 OC155-B--1.qxp 9 7/26/00 4:43 PM Page 27 OPERATION FLOW-CHART 1. Main operation NO POWER SUPPLY Live YES <Note 1> TIMER MODE button ON YES NO During operation <Note 2> NO Protection device Self hold reset ON/OFF button ON YES YES <Note 3> YES Protection device Self hold Abnormal operation mode NO NO NO AUTO STOP lamp ON AUTO START lamp ON Auto stop timer Press / 1 12Hr up Press / 12 1Hr down Auto start timer Press / 1 12Hr up Press / 12 1Hr down Set time Elapsed time=0 Set time Elapsed time=0 YES POWER lamp ON YES Self-diagnostic function Indicate & Memory EMERGENCY ALL STOP <Note 4> <Note 5> FAN MODE SELECT button DRY COOL FAN OPERATION COOL OPERATION DRY OPERATION Note 1. Refer to page 33 for timer mode details. Note 2. The unit starts operation by pressing the ON / OFF switch when unit is OFF. During operation, the unit stops operation by pressing the ON / OFF switch. In addition, operation can be turned ON / OFF with the centralized remote controller or the remote switch. Note 3. The factors which cause "abnormal operation mode" are as follows. ● Outdoor unit abnormal operation. ● Fault of room temperature thermistor (RT1). ● Fault of indoor coil thermistor (RT2). ● Indoor coil frost protection mode. ● Drain water overflow prevention mode. Note 4. The indoor fan runs on the low speed for 1 minute to eliminate remaining heat. Note 5. The compressor will not start for 3 minutes after the stop to protect the compressor. 27 NO OC155-B--1.qxp 7/26/00 4:43 PM Page 28 2. COOL operation YES 3-minute time delay YES 6-minute time delay NO NO NO NO YES Allowanse Compressor start 3 minutes elapse Coil frost protection check mode 6-minute time delay <Note 7> YES Coil frost protection <Note 8> YES Allowanse set NO Range C NO YES NO Compressor start 10 minutes elapse YES Allowance release NO Indoor coil temperature 10 °C or more Coil frost prevention YES NO Continue 1 minute YES YES Fan speed LOW 3-minute time delay NO <Note 6> Compressor thermostat ON NO YES NO Compressor start 16 minutes elapse Coil frost prevention release YES NO Allowance release Indoor coil temperature 1°C or below Fan speed LOW 5 minutes elapse YES YES Outdoor unit abnormality check mode Coil frost prevention set NO Compressor ON Compressor OFF Note 6. The thermostat is continuously ON during the test run. Note 7. Refer to page 31 for coil frost protection. Note 8. Range A : Indoor coil temperature is more than 5 degrees above room temperature. Range B : Indoor coil temperature is within 5 degrees either way of room temperature. Range C : Indoor coil temperature is more than 5 degrees below room temperature. 28 OC155-B--1.qxp 7/26/00 4:43 PM Page 29 3. DRY operation <Note 10> YES Room temperature 18 C or below NO NO Compressor ON YES YES 3-minute time delay NO Compressor ON 3 min.elapse NO YES NO <Note 6> <Note 6> Compressor themostat ON YES Compressor thermostat ON NO YES NO Compressor ON time completed Compressor OFF 10 minutes completed YES YES <Note 11> Compressor ON time set Compressor OFF 10-minute timer start YES Compressor ON Compressor OFF <Note 12> <Note 12> Fan speed LOW Fan stop Note 10. When the room temperature is 18°C or below, the compressor can not turn ON. When the room temperature rises to 19°C or above, the compressor will start operation after a 3-minute time delay. Note 11. Refer to page 32 for the compressor operation time. Note 12. In DRY operation, the indoor fan runs on the low speed during the compressor ON and stops during the compressor OFF. 29 OC155-B--1.qxp 7/26/00 4:43 PM 10 Page 30 MICROPROCESSOR CONTROL 1. OUTLINE OF MICROPROCESSOR CONTROL REMOTE CONTROLLER INPUT to remote controller OUTPUT to remote controller ● Transmits and receives orders. ● ON-OFF switching. ● COOL-FAN selector switching. ● HIGH-LOW fan speed switching. ● TIMER mode selector switching. ● Thermostat setting. ● Timer setting. ● Self-diagnostic troubleshooting. ● Test run switching. ● Indication lamps lights. 12 TIMER TEMP 12 29 11 28 COOL 10 27 DRY 9 26 FAN 8 25 7 24 6 23 5 22 4 21 3 20 2 19 1 18 TIMER/TEMP. UP POWER HIGH LOW ON/OFF MODE SELECT FAN SPEED DOWN AUTO STOP START TIMER MODE MITSUBISHI ELECTRIC Indoor unit 12V DC Polar, twelve (12) - core cable Maximum length 50m (164ft) INPUT from indoor unit INDOOR CONTROLLER BOARD ● Room temperature thermistor (RT1) ● Indoor coil thermistor (RT2) ● Receives orders from remote controller and temperature data from indoor unit. ● Processes orders and data. ● Transmits the power of indication lamp to remote controller. ● Controls indoor and outdoor operation. ● Self-diagnostic function. W System control operation.<Optional> W Emergency operation. OUTPUT to indoor unit ● Fan : ON-OFF. ● Fan speed : HIGH-LOW. ● Emergency stop. 12V DC Non - polar, two (2) - core cable INPUT from outdoor unit ● Compressor protection device working Outdoor unit OUTDOOR UNIT ● Receives order from indoor controller. ● Emergency stop. OUTPUT to outdoor unit ● Compressor motor and outdoor fan motor : ON - OFF 30 OC155-B--1.qxp 7/26/00 4:43 PM Page 31 2. INDOOR UNIT CONTROL 2-1 COOL operation TIMER TEMP 12 29 11 28 COOL 10 27 DRY 9 26 FAN 8 25 7 24 6 23 5 22 4 21 3 20 2 19 1 18 TIMER/TEMP. UP POWER HIGH LOW <How to operate> 1 Press POWER ON / OFF button. 2 Press MODE SELECT button to set operation mode to COOL. TEMP 3 Check lamp is ON and set desired temperature with UP or DOWN button. ON/OFF MODE SELECT NOTES : 1. When lamp is ON, press DISPLAY SELECT button to change the display to temperature mode. FAN SPEED DOWN 2. Set temperature changes by 1°C in the range 18 ~ 29°C each time UP AUTO STOP START or DOWN button is pressed. 3. The lighting lamp shows the set temperature, and the flashing lamp shows the room temperature. When the room temperature is equal to the set temperature, the lamp keeps lighting, 0.5 seconds brightly and 0.5 seconds faintly. TIMER MODE MITSUBISHI ELECTRIC Steady TIMER Flash OFF <COOL operation time chart> Operation starts by POWER button ON. Room temperature becomes equal to set temperature. Room temperature rises above set temperature. Operation stops by POWER button OFF. ON Thermostat OFF LOW or HIGH LOW or HIGH ON Indoor fan OFF Compressor OFF ON MIN. 3 minutes 1 W1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this period has ended. (1) Compressor control 1 3 minute time delay To prevent overload, the compressor will not start within 3 minutes after stop. 2 The compressor runs when the room temperature is higher than the set temperature. The compressor stops when the room temperature is equal to or lower than the set temperature. 3 The compressor stops in check mode or during protective functions. 4 Coil frost prevention To prevent indoor coil frost, the compressor will stop when the indoor coil thermistor (RT2) reads 1°C or below after the compressor has been continuously operated for 16 minutes or more. The coil frost prevention is released under any of the following conditions. ● The indoor coil thermistor rises to 10°C or above. ● The room temperature becomes equal to or lower than the set temperature. ● COOL mode is stopped or changed to another mode. NOTE : By cutting the jumper wire JRO2 on the indoor controller board, the temperature to start coil frost prevention changes from 1°C to -3°C. 5 Coil frost protection When indoor coil temperature becomes -15°C or below, coil frost protection will proceed as follows. <Start condition> After the compressor has been continuously operated for 3 minutes or more, and the indoor coil temperature has been -15°C or below for 3 minutes, the coil frost protection will start. <Coil frost protection> Compressor stops for 6 minutes, and then restarts. lf the start condition is satisfied again during the first 10 minutes of compressor operation, both the indoor and outdoor units stop, and the remote controller displays this occurrence. <Termination conditions> Coil frost protection is released when the start condition is not satisfied again during the allowance, or when the COOL mode stops or changes to another mode. 31 OC155-B--1.qxp 7/26/00 4:43 PM Page 32 (2) Indoor fan control Indoor fan speed LOW/HIGH depends on the remote controller setting. However, if an outdoor unit abnormality is detected, the indoor fan speed will be LOW, regardless of the remote controller setting. (3) Detecting abnormalities in the outdoor unit After the compressor has been continuously operated for 3 minutes, if the difference between the difference between the indoor coil temperature and room temperature is out of RANGE C, for 1 minute, the indoor fan speed will turn to LOW. Five minutes later, if the difference is in RANGE C, the fan speed will return to the set speed. If the difference is still out of RANGE C, the outdoor unit is deemed abnormal. Thus, the compressor will stop and the trouble location is indicated on the remote controller. RANGE A : Indoor coil temperature is more than 5 degrees above room temperature. RANGE B : Indoor coil temperature is within 5 degrees either way of room temperature. RANGE C : Indoor coil temperature is more than 5 degrees below room temperature. 2-2 DRY operation <How to operate> 1 Press POWER ON / OFF button. 2 Press MODE SELECT button to set operation mode to DRY. TIMER TEMP 12 29 11 28 COOL 10 27 DRY 9 26 FAN 8 25 7 24 6 23 5 22 4 21 3 20 2 19 1 18 TIMER/TEMP. UP POWER HIGH LOW 3 Check ON/OFF AUTO STOP NOTES : 1. When FAN SPEED Flash TIMER lamp is ON, press DISPLAY SELECT button to change the display to temperature mode. 2. Set temperature changes by 1°C in the range 18 ~ 29°C each time UP or DOWN button is pressed. 3. The lighting lamp shows the set temperature, and the flashing lamp shows the room temperature. When the room temperature is equal to the set temperature, the lamp keeps lighting, 0.5 seconds brightly and 0.5 seconds faintly. TIMER MODE MITSUBISHI ELECTRIC Steady lamp is ON and set desired temperature with UP or DOWN but- ton. MODE SELECT DOWN START TEMP OFF (1) Compressor control 1 3-minute time delay To prevent overload, the compressor will not start within 3 minutes after stop. 2 The compressor runs when the room temperature is higher than the set temperature. The compressor stops when the room temperature is equal to or lower than the set temperature. 3 The compressor stops in check mode or during protective functions. 4 The compressor will not start when the room temperature is below 18°C. The compressor starts intermittent operation when the power is turned ON with room temperature above 18°C. The compressor ON / OFF time depends on the thermostat ON / OFF and the room temperature as follows. After 3 minute compressor operation, ● If the room temperature thermistor reads above 28°C with thermostat ON, the compressor will operate for 6 more minutes and then stop for 3 minutes. ● If the room temperature thermistor reads 26 °C ~28 °C with thermostat ON, the compressor will operate for 4 more minutes and then stop for 3 minutes. ● If the room temperature thermistor reads 24°C ~26°C with thermostat ON, the compressor will operate for 2 more minutes and then stop for 3 minutes. ● If the room temperature thermistor reads below 24°C with thermostat ON, the compressor will stop for 3 minutes. ● If the thermostat is OFF, regardless of room temperature, the compressor will stop for 10minutes. 5 Coil frost protection Coil frost protection in DRY operation is the same as in COOL operation. (2) Indoor fan control The indoor fan runs on LOW speed during compressor operation. The fan speed cannot be changed with the remote controller. Also, the indoor fan does not run during compressor OFF. (3) Detecting abnormalities in the outdoor unit An abnormality in the outdoor unit can not be detected in DRY operation. 32 OC155-B--2.qxp 7/26/00 4:45 PM Page 33 2-3 FAN operation <How to operate> 1 Press POWER ON / OFF button. 2 Press MODE SELECT button to set operation mode to FAN. TIMER TEMP 12 29 11 28 10 27 9 26 8 25 7 24 6 23 5 22 4 21 3 20 2 19 1 18 TIMER/TEMP. POWER COOL DRY FAN UP HIGH LOW NOTES : Temperature can not be set in FAN operation. ON/OFF MODE SELECT FAN SPEED DOWN AUTO STOP START TIMER MODE MITSUBISHI ELECTRIC Steady Flash OFF (1) Indoor fan control The indoor fan speed LOW / HIGH depends on the remote controller setting. 2-4 TIMER operation TIMER TEMP 12 29 11 28 COOL 10 27 DRY 9 26 FAN 8 25 7 24 6 23 5 22 4 21 3 20 2 19 1 18 TIMER/TEMP. UP POWER HIGH LOW <Timer function> AUTO STOP ·········Air conditioner stops after the set time lapses. AUTO START ········Air conditioner starts after the set time lapses. <How to operate ● AUTO STOP timer> ● POWER 1 While lamp is lighting, press TIMER MODE button. ON/OFF MODE SELECT and FAN SPEED DOWN AUTO STOP START TIMER MODE MITSUBISHI ELECTRIC Steady Flash OFF TIMER lamps turn ON. 2 Set the time for the AUTO STOP timer with the UP or DOWN button. NOTE : The time setting is in 1 hour units up to 12 hours. 3 With the lapse of time, the timer lamps turn OFF one by one, showing the remaining time. 4 To cancel the AUTO STOP timer and continue operation, press the TIMER MODE button. To cancel the AUTO STOP timer and stop operation, press the POWER ON/OFF button. <How to operate AUTO START timer> POWER 1 While lamp is OFF, press TIMER MODE button. and TIMER lamps turn ON. 2 Set the time for the AUTO START timer with the UP or DOWN button. NOTE : The time setting is in 1 hour units up to 12 hours. 3 With the lapse of time, the timer lamps turn OFF one by one, showing the remaining time. 4 To cancel the AUTO START timer and keep the unit OFF, press the TIMER MODE button. To cancel the AUTO START timer and start operation, press the POWER ON / OFF button. 2-5 Test run The unit starts the test run by pressing both the UP and DOWN buttons simultaneously for more than two seconds during TIMER ● ● ● ● lamp ON or the unit OFF. The test run automatically stops in 2 hours. Set temperature is not displayed during test run. Room temperature is displayed by the flashing green lamp when DISPLAY SELECT button is pressed. The test run can be released by pressing the POWER ON / OFF or the TIMER MODE button. <Initial setting> The units are set as follows by the factory. 1) AUTO START set time : 12hours AUTO STOP set time : 12 hours 2) Initial operation mode : FAN 3) Fan speed : LOW 4) Set temperature : 28°C 33 OC155-B--2.qxp 7/26/00 4:45 PM Page 34 2-6 Self-diagnostic function ! When trouble occurs during operation, the unit stops and displays the trouble location with the timer lamps on the remote controller. All the other lamps are OFF normally. @ To activate the self-diagnostic function for service, press the UP and DOWN buttons simultaneously for more than two TEMP seconds during operation with lamp ON # The timer lamps show the latest trouble. Trouble data is memorized until the next trouble occurs, even when the breaker turns OFF. $ All buttons except the POWER ON/OFF are unavailable during the self-diagnostic mode. % To release the self-diagnostic mode, press the POWER ON /OFF button. 2-7 Emergency operation When the remote controller or microprocessor malfunctions and no other trouble exists, emergency cooling operation is available by setting the dip switch on the indoor controller board. [Check items] ! Make sure the compressor and the fans are running normally. @ Locate the trouble with the self-diagnostic function. If the self-diagnostic function indicates that the protection device (such as coil frost protection) is functioning, the sources must be removed before attempting emergency operation. Emergency operation ON / OFF is activated not with the remote controller but with the circuit breaker. [Emergency operation procedure] ! Cooling operation is available by setting the dip switch (SW3<I.B>) 1 and 2 ON and 3 OFF on the indoor controller board. @ To start emergency operation, turn the outdoor side circuit breaker ON first, and then the indoor side circuit breaker ON. # During emergency operation, the indoor fan runs on HIGH speed, the compressor runs continuously. $ Thermostat will not function. % Do not use emergency cooling operation for more than 10 hours, as the indoor coil may freeze. SW3 ON OFF 1 2 3 34 OC155-B--2.qxp 7/26/00 4:45 PM Page 35 2-8 Function of jumper wire and dip switch on indoor controller board 1. Jumper wire 1 JR1...Jumper wire for the auto vanes. Cut JR01 for the unit WITHOUT auto vanes. 2 JR2...Jumper wire for the temperature to start coil frost prevention Cutting JR02 changes the temperature from +1°C to -3°C. 3 JR3...Jumper wire for set temperature adjustment in HEAT mode. In HEAT operation, heated air stagnates in the upper part of the room. The indoor unit installed in the upper part of the room will detect the air temperature higher than the actual temperature in the living space. This difference is about 4 degrees. Therefore, the temperature detected by the room temperature thermistor should be corrected 4 degrees down. The unit with JR04 attached will make this adjustment. 4 JR4...Jumper wire for the indoor fan speed during thermostat OFF in HEAT mode Cutting JR04 changes the speed from Extra-Low to Low. 5 JR5...Jumper wire for detecting abnormalities in the outdoor unit Cutting JR05 makes this detection unavailable. (Occurrence of abnormality can not be detected. ) 6 JR6...Jumper wire for auto restart function Cutting JR06 makes the auto restart function available. 2. Dip switch 1 SW1 (Function switch) ON OFF 1 2 3 2 SW2 (Unit switch) SW1-1) Switch for power supply ON : 220V OFF : 230V, 240V SW1-2) Switch for single or twin control ON : Twin control OFF : Single control SW1-3) Switch for unit number in twin control (This switch is valid when SW1-2 is ON. ) ON : Unit No. 2 OFF : Unit No. 1 SW2-1) ON OFF 1 2 3 4 SW2-2) SW2-3) SW2-4) Switch for air conditioner with or without electric heater ON : Unit with electric heater OFF : Unit without electric heater Switch for air conditioner with or without heat pump ON : Unit with heat pump OFF : Unit without heat pump Switch for function code ON : 1 OFF : 0 Switch for function code ON : 1 OFF : 0 3 SW3 (Emergency operation switch) Normal operation For emergency cooling 1 2 3 ON OFF 1 2 3 ON OFF 35 OC155-B--2.qxp 11 7/26/00 4:45 PM Page 36 TROUBLESHOOTING 1. SELF-DIAGNOSTIC FUNCTION ! When trouble occurs during operation, the unit stops and enters the self-diagnostic mode, and displays the trouble location with the timer lamps on the remote controller. All the other lamps are OFF. @ To activate the self-diagnostic function for service, press the UP and DOWN buttons simultaneously for more than two TEMP. seconds during operation with lamp ON. ▲ # The timer lamps show the latest trouble. Trouble data is memorized until the next trouble occurs, even when the breaker turns OFF. To clear the memory, press the UP and DOWN buttons simultaneously for more than two seconds during the test run. $ All buttons except the POWER ON/OFF button are unavailable during the self-diagnostic mode. % To release the self-diagnostic mode, press the POWER ON/OFF button. Unit Trouble location TEMP. ▲ TIMER Transmission error in twin control ▲ 29 11 28 10 27 9 26 8 25 7 24 6 23 5 22 4 21 3 20 2 19 1 18 Unit No.2 ● Poor connector contact ● Thermistor malfunction ● Check connector ● Check thermistor ➔ No trouble ➔ replace indoor controller board. ● Poor connector contact ● Thermistor malfunction ● Check connector ● Check thermistor ➔ No trouble ➔ replace indoor controller board. ● Poor connector contact ● Thermistor malfunction ● Check connector ● Check thermistor ➔ No trouble ➔ replace indoor controller board. Drain overflow protection ● Drain pump malfunction ● Drain sensor improperly mounted ● Check drain pump ● Check drain sensor ➔ No trouble ➔ replace indoor controller board. Coil frost or overheat prevention ● Air passage short cycle ● Air filter clogged ● Indoor fan malfunction ● Remove blockage ● Check air filter ● Check indoor fan Indoor coil thermistor (RT2) Unit No.1 Drain sensor (DS) Unit No.2 Unit No.1 Unit No.2 Unit No.1 Unit No.2 ● Check dip switch setting ● Check wiring ● Check wiring ● Check outdoor unit ● Check outdoor coil thermistor Unit Room No.1 temperature thermistor Unit (RT1) No.2 Unit No.1 Measures ● Wrong wiring between indoor/outdoor units ● Outdoor unit abnormality detection ● Malfunction of outdoor coil thermistor ● Reversed phase detected Outdoor unit 12 Cause ● Wrong wiring between No. 1 and No. 2 units ● Poor connector contact } } } } (Indicates that the unit is in self-diagnostic mode) 36 OC155-B--2.qxp 7/26/00 4:45 PM Page 37 2. OTHER TROUBLES AND CAUSES Power ON/OFF button does not work. Indoor/outdoor connecting wire is connected incorrectly. Indoor/outdoor connecting wire shorts. Compressor protector is damaged. Dicer is broken. Transmission wire is damaged. Connector is poorly connected. Remote controller is damaged. Transmission wire is poorly connected. 37 OC155-B--2.qxp 7/26/00 4:45 PM Page 38 3. How to check the parts PE-EJ(S)A.TH Parts name Check points Room temperature thermistor (RT1) Indoor coil thermistor (RT2) Disconnect the connector, then measure the resistance using a tester. (Surrounding temperature 10°C~30°C) Normal 4.3k'~9.6k' Trans 1 2 3 4 1 2 3 YLW RED CNT(1)-(3) CN4T(1)-(2) CN4T(3)-(4) Fan motor 4 5 6 1 BLK BLU YLW RED ORN WHT BLU 3 BLK 2 Motor terminal or Relay connector WHT-BLK BLK-BLU BLU-YLW YLW-RED Capacito 5 Normal WHT App. 135' BRN App. 0.5~1.0' RED App. 1.0~2.0' Abnormal Open or short Measure the resistance between the terminals using a tester. (Surrounding temperature 20°C) Protector 3 (Refer to the thermistor) Disconnect the connector and measure the resistance using a tester. CNT T CN4T BRN WHT 1 Abnormal Open or short 7 Normal PE-EJ(S)A 4EJSA2 20.63' 8.05' 3.18' 16.02' 3EJA2, 3EJA3 46.38' 17.25' 18.37' (BLU-RED) <Thermistor Characteristic graph> Thermistor for lower temperature Abnormal 5EJSA2, 6EJSA2 15.26' 5.118' Open or short 2.648' 14.49' < Thermistor for lower temperature > 50 Room temperature thermistor(RT1) Indoor coil thermistor(RT2) 40 Rt=15exp { 3480( 0: 10: 20: 25: 30: 40: 1 273+t Resistance (K") Thermistor R0=15k' ± 3% Fixed number of B=3480k' ± 2% 1 )} 273 30 20 15k' 9.6k' 6.3k' 5.2k' 4.3k' 3.0k' 10 0 38 -20 -10 0 10 20 30 Temperature (:) 40 50 OC155-B--2.qxp 7/26/00 4:45 PM 12 Page 39 DISASSEMBLY PROCEDURE PE-3EJA2.TH PE-3EJA3.TH OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS 1. Removing the drain pan ! Unscrew each set screw on the right and left, and remove the drain pan pushing it toward the back. (See Photo 1) Photo 1 Room temperature thermistor Set screw (for drain pan) Drain pan 2. Removing the electrical parts ! Remove the electrical parts cover. (set screw ✕ 2) and the parts as blow ● Indoor controller board ● Transformer ● Run capacitor ● Fuse (6.3A) ● Terminal block ● Room temperature thermistor Photo 2 (See Photo 2) Electrical parts cover Set screw (See Photo 3) Photo 3 Transformer Connector Terminal block 3. Removing the indoor coil thermistor ! Remove the drain pan. Indoor controller board Photo 4 Indoor coil thermistor (See Photo 1) @ Remove the electrical parts cover. (See Photo 2 ) # Remove the set wire of the indoor coil thermistor. (See Photo 4) Fan motor 39 Run capacitor OC155-B--2.qxp 7/26/00 4:46 PM Page 40 OPERATING PROCEDURE PHOTOS 4. Removing the fan Note : Perform the following with the indoor unit lowered down to the floor. ! Remove the drain pan. (See Photo 1) @ Disconnect the connector for the fan motor. (See Photo 3) # Take out the fan after removing the 7 set screws of the fan plate. (See Photo 5 or 6.) $ Unscrew four set screws of the bell mouth and remove the bell mouth. (See Photo 7.) % Loosen the set screw of the fan to pull out the sirocco fan. (See Photo 7.) ^ Unscrew the four set screws of the motor fitting, and remove the fan motor. (See Photo 8.) Photo 5 Fan plate Set screw Photo 6 Fan motor Fan casing Photo 7 Fan plate Photo 8 Fixture set screw Fan casing Set screw Bell mouth Sirocco fan Fan plate Set screw Fixture set screw Fittings 40 Fan motor OC155-B--2.qxp 7/26/00 4:46 PM 13 Page 41 PARTS LIST STRUCTURAL PARTS PE-3EJA 1.TH PE-3EJA 2.TH PE-3EJA 3.TH 9 14 3 4 5 7 2 5 6 8 11 10 12 13 1 Q'ty/set No. Part No. Part Name Specification PE-3 EJA1.TH, EJA2.TH, EJA3.TH Price Wiring RecomDiagram mended (Drawing No.) symbol Q'ty Unit Amount Remarks 1 E07 027 300 2 — CASING 1 (R300B098F04) 3 — BELL MOUTH 1 (R302D730G01) 4 E07 018 500 SIROCCO FAN 1 5 E07 018 808 LEG 2 6 — FAN PLATE 1 7 — CABINET ASSY 1 (BG00T021B01) 8 — AIR OUTLET DUCT FLANGE 1 (BA00H896G08) 9 — AIR INTAKE DUCT FLANGE 1 (BB02R503G10) 10 — FAN MOTOR LEG 1 (R302G070G01) 11 — MOTOR BEAM 1 (BA02L499G04) 12 E07 018 505 RUBBER MOUNT 2 2PCS/SET 13 E07 018 700 DRAIN PAN 1 14 E07 027 620 HEAT EXCHANGER 1 INDOOR FAN MOTOR PA6V205-E8 41 MF1 1 (BA02G745G10) OC155-B--2.qxp 7/26/00 4:46 PM Page 42 STRUCTURAL PARTS PE-4EJSA1.TH PE-4EJSA2.TH 12 14 6 3 9 8 7 9 10 11 5 4 2 13 1 Q'ty/set No. Part No. Part Name Specification PE-4 EJSA1.TH, EJSA2.TH Remarks Wiring RecomDiagram mended (Drawing No.) symbol Q'ty 1 E07 028 300 INDOOR FAN MOTOR 2 E07 018 505 RUBBER MOUNT 2 3 E07 022 500 SIROCCO FAN 1 4 — FAN MOTOR LEG 1 (BB00L212G04) 5 — MOTOR BEAM 1 (BB02T248G02) 6 — BELL MOUTH 1 (R302D730G01) 7 — CASING 1 (BA00N328G08) 8 — CABINET ASSY 1 (BG00T022B01) PA6V305-EA MF1 1 2PCS/SET 9 E07 018 808 LEG 2 10 — FAN PLATE 1 11 — AIR OUTLET DUCT FLANGE 1 (BA00H896G09) 12 — AIR INTAKE DUCT FLANGE 1 (BB02G810G05) 13 E07 022 700 DRAIN PAN 1 14 E07 028 620 HEAT EXCHANGER 1 42 (BB02G686G05) Price Unit Amount OC155-B--2.qxp 7/26/00 4:46 PM Page 43 STRUCTURAL PARTS PE-5EJSA1.TH, 6EJSA1.TH PE-5EJSA2.TH, 6EJSA2.TH 5 6 12 14 8 1 4 2 3 10 9 11 5 13 15 7 16 17 Q'ty/set No. Part No. Part Name Specification PE-5 PE-6 EJSA1.TH EJSA1.TH Price Wiring RecomDiagram mended (Drawing No.) symbol Q'ty Unit Amount Remarks EJSA2.TH EJSA2.TH 1 E07 029 300 1 1 2 — FAN MOTOR LEG 1 1 (BB00L212G04) 3 — MOTOR BEAM 1 1 (BB02L182G04) 4 E07 018 505 RUBBER MOUNT 2 2 INDOOR FAN MOTOR PA6V400-ED MF1 5 — BELL MOUTH 2 2 6 E07 018 500 SIROCCO FAN 1 1 7 E07 023 500 SIROCCO FAN 1 1 8 — CASING 1 1 (R300B098F04) 9 — CASING 1 1 (R300B098F05) 10 — FAN PLATE 1 1 (BA02N472G05) 11 — AIR OUTLET DUCT FLANGE 1 1 (BA00H898G10) 12 E07 018 809 LEFT LEG 1 1 13 E07 018 808 RIGHT LEG 1 1 14 — CABINET ASSY 1 1 15 E07 023 700 DRAIN PAN 1 1 E07 029 620 HEAT EXCHANGER 1 E07 030 620 HEAT EXCHANGER 16 17 — (R302D730G01) (BG00T022B04) 1 AIR INTAKE DUCT FLANGE 1 43 1 (BB02L116G12) OC155-B--2.qxp 7/26/00 4:46 PM Page 44 ELECTRICAL PARTS PE-3EJA1.TH, PE-4EJSA1.TH, PE-5EJSA1.TH, PE-6EJSA1.TH PE-3EJA2.TH, PE-4EJSA2.TH, PE-5EJSA2.TH, PE-6EJSA2.TH PE-3EJA3.TH Q'ty/set Specification Remarks Wiring RecomDiagram mended (Drawing No.) symbol Q'ty EJ(S)A1.TH, EJ(S)A2.TH, EJA3.TH No. Part No. Part Name 1 E07 027 447 INDOOR CONTROLLER BOARD 2 E07 006 382 FUSE 1 F1,2<I.B> 3 E07 018 351 INDOOR FAN CAPACITOR 8.0+/440VAC 1 C1 4 E07 027 339 TRANSFORMER 1 T 5 E07 006 375 TERMINAL BLOCK 3P (L, N, ;) 1 TB1 6 E07 007 375 TERMINAL BLOCK 2P (1, 2) 1 TB2 7 E07 027 308 ROOM TEMPERATURE THERMISTOR 1 RT1 8 E07 027 307 INDOOR COIL THERMISTOR 1 RT2 R.B PE-3,4,5,6 1 250V 6.3A 9 E07 027 426 REMOTE CONTROLLER 1 10 E07 027 088 REMOTE CONTROLLER COVER 1 11 E07 027 089 REMOTE CONTROLLER CABLE 10m 1 12 E07 027 087 0.5m 1 CABLE (FOR BOARD) w1 w1 : [CONTROLLER CASE] is made together with INDOOR CONTROLLER BOARD. 44 I.B Price Unit Amount OC155-B--2.qxp 7/26/00 4:46 PM 14 Page 45 OPTIONAL PARTS 1. REFRIGERANT PIPES Service Ref. : PE-3EJA2.TH / PE-3EJA3.TH Part No. Pipe length Pipe size O.D. Connection method PAC-05FFS-E 5m PAC-07FFS-E 7m Liquid : ø9.52 Indoor unit : Flared Service Ref. : PE-4EJSA 2.TH, PE-5EJSA 2.TH, PE-6EJSA 2.TH Part No. Pipe length Pipe size O.D. Connection method PAC-SC51PI-E 5m PAC-SC52PI-E 7m Liquid : ø9.52 Indoor unit : Flared PAC-10FFS-E 10m Gas : ø15.88 Outdoor unit : Flared PAC-15FFS-E 15m PAC-SC53PI-E 10m Gas : ø19.05 Outdoor unit : Flared PAC-SC54PI-E 15m Note 1. How to connect refrigerant pipes. Factory supplied optional refrigerant piping contains refrigerant at the above atmospheric pressure. As long as connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging. Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow. If piping length exceeds 20m, an additional charge of refrigerant is needed. Note 2. The following main parts are contained in the optional refrigerant piping kit. Heat insulating cover, vinyl tapes, nipples, sleeve, flange (for wall hole). 2. REMOTE CONTROLLER EXTENSION CABLE When installing the remote controller at a distance from the air conditioner, use the designated extension cable with connector. Part No. Length PAC-905EC 12m PAC-906EC 20m PAC-918EC 30m PAC-919EC 50m 3. TIMER When using a program timer, a program timer adapter (PAC-825AD) is also needed. Part No. Model Name PAC-SK65PT (with set back function) Program timer 3-1 Program timer specifications Part name Part No. Exterior dimensions Installation Type of clock Clock accuracy Display - Time - Week - Timer Program cycle Timer setting unit No. of set points Power rating Set back function Program timer PAC-SK65PT 120 x 120 x 15mm Wall mount Quartz ±50s / month Liquid crystal display Liquid crystal display Liquid crystal display 24 hours 30 minutes 48 / day 5V DC Provided 3-2 Feature of program timer (1) Daily timer function Daily timer can be set in 30 minute units up to 24 hours. Each unit can be set for unit ON, unit OFF, or setback operation. (2) Setback operation. (PAC-SK65PT) Set back operation is useful for reducing running costs e.g. : At a hotel with a 24-hour system 8:00~23:00 Cooling operation with set temperature at 26°C 23:00~8:00 Setback operation with 2 degrees of setback As shown in the chart on the right, the set temperature rises 2 degrees automatically during the setback operation. When the setback operation ends, normal operation will begin. (3) Weekly timer function Daily timer function can apply to each day of the week. 45 28˚C 26˚C 8:00 Normal operation 23:00 Setback operation 8:00 Normal operation OC155-B--2.qxp 7/26/00 4:46 PM Page 46 3-3 How to connect program timer ! Install the program timer next to the remote controller the same way as the remote controller is installed. @ Connect the program timer and the remote controller with a 6-wire cable as shown in the figure below Connect to indoor unit 2-wire cable Centralized Remote controller Connect to CN1 Use 6-wire cable NOTE : While the program timer is connected to the remote controller, the 24-hour ON / OFF timer on the remote controller will not operate. Program timer Connect to CN1 3-4 Names and functions Mode selector button : Use this button to select "MONITOR" or <PAC-SK65PT> "SET" mode. "MONITOR" : Indicates the current timer setting. All buttons except SET/MONITOR will not work. This is the normal status. "SET" : "SET" is used to set the time, change of day of the week, and program the daily and weekly timer. Mode display Current time display Current day display Weekly timer display SET MONITOR BACK ON Clock adjustment button : Used to adjust the current time. Press AHEAD button to advance the time. Each time the button is pressed the time advances by 1 minute, and pressing continuously advances 1 minute at a 0. 5 second interval. When the lower digit of the minutes becomes 0 the indication advances in 10 minute units. BACK button is used for reversing the time. Each time the button is pressed the time reverses by 1 minute, and pressing continuously reverses the time by 1 minute at a 0. 5 second interval. When the lower digit of the minute becomes 0 the indication reverses in 10 minutes units. BACK ON AHEAD OFF AHEAD OFF MITSUBISHI ELECTRIC Day setting button : Used to set the day of the week. Pressing button changes the day. light displays in the order of S ➝ M ➝ T ➝ W. ▼ Daily timer display NOTE : display above is only an example. Weekly timer button : Used to set the weekly timer. Set back button : Used to set the set back amount. Set back can be set in the range of 1 to 9°C in 1°C unit. Daily timer button : Used to set the daily timer in 30 minute units. 46 OC155-B--2.qxp 7/26/00 4:46 PM Page 47 4. CENTRALIZED REMOTE CONTROLLER Allows individual or combined control of up to 16 units. Part No. PAC-805RC 4-1 Dimensions Unit : mm 113 56.5 12 23.5 POWER ON/OFF ENGAGED 11 POWER ON/OFF ENGAGED GROUP PROGRAM TIMER DUAL CENTRAL CONTROLLER OPERATION BACK AHEAD ACTIVE BYPASS 1 2 3 4 5 6 7 8 9 10 DUAL CENTRAL GROUP SELECTION ACTIVE BYPASS PROGRAM TIMER DUAL CENTRAL CONTROLLER OPERATION BACK AHEAD ACTIVE BYPASS 113 ACTIVE BYPASS GROUP 8 GROUP SELECTION 117 1 2 3 4 5 6 7 8 9 10 DUAL CENTRAL MITSUBISHI ELECTRIC 10 9 8 7 6 5 4 3 2 1 117 4-2 Names and Functions POWER ON/OFF switch Operation ON/OFF switch. "ENGAGED" indicator When this indicator is lit, transmission is in progress and all switches are inoperative. DUAL/CENTRAL switch This change-over switch controls the operation of the accessory remote controller. ▲BACK ▼AHEAD buttons These buttons are used to designate the attached unit(s). (They designate the unit to be centrally controlled.) POWER ON/OFF ENGAGED GROUP 1 2 3 4 5 6 7 8 9 10 "DUAL" Instructions from both the accessory remote controller and the centralized remote controller are valid. (Priority is given to the last instruction received.) GROUP SELECTION ACTIVE BYPASS PROGRAM TIMER DUAL CENTRAL CONTROLLER OPERATION "CENTRAL" ON/OFF switching by the accessory remote controller is invalidated. Operation is controlled by the centralized remote controller only. Initial setting is "DUAL". BACK AHEAD ACTIVE BYPASS DUAL CENTRAL MITSUBISHI ELECTRIC LCD Matrix Display This display indicates the operational status of all connected units either by steady lighting or by flashing. ●When group “00” is designated; collective ON/OFF instruction is sent to all units. ●When group ¨01¨ - ¨16¨ is designated; ON/OFF instruction is sent only to the designated units. ACTIVE/BYPASS switch This change-over switch for the program timer. (It selects the timer operation on the program timer.) Use “BYPASS” when a program timer is not connected. “ACTIVE” The switch turns ON / OFF commands given from the program timer automatically. “BYPASS” ON / OFF Operation is controlled by the centralized remote controller only. Initial setting is “BYPASS”. Independent “DUAL / CENTRAL” and “ACTIVE / BYPASS” setting of all the groups is possible. When power supply to the centralized remote controller is cut, due to a power failure, for example all settings return to original “DUAL” and “BYPASS”. 47 OC155-B--2.qxp 7/26/00 4:46 PM Page 48 4-3 Connection method (1) Connections in the power supply cord. 1. Connect the power supply cord to the power supply terminal-block and fix it in-place with a tie-lap. Connect a single phase 200V AC (220, 230, 240V) to L N. As E is the GND terminal, be sure to ground the earth wire. 2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-lap. Use a Ø1.6 (AWG 14) or above two-wire cable for the transmission line. CAUTION : Never connect the power supply cord to the transmission terminal-block. TERMINAL-BLOCK FOR TRANSMISSION TERMINAL-BLOCK OF POWER SUPPLY Transmission L T N (Y) 240 230 Tle-lap (O) 220 (R) 200 E (W) (BN) 5A TRANSFORMER Fuse(5A) L POWER SUPPLY N Tie-lap E Wiring has to be change when a 200,230 or 240 power is used. (2) Connection method of centralized remote controller and power supply board. 1. Connect the centralized remote controller and power supply board with a non-polar, two-wire cable. Power supply board box To adaptor's terminal-block POWER ON/OFF ENGAGED GROUP 1 2 3 4 5 6 7 8 9 10 GROUP SELECTION ACTIVE BYPASS PROGRAM TIMER DUAL CENTRAL CONTROLLER OPERATION BACK AHEAD ACTIVE BYPASS DUAL CENTRAL 10 9 8 7 6 5 4 3 2 1 Centralized remote controller To adaptor's terminal-block Non-polar, two-wire cable 2. Wiring diagram 3. Set the max. address number with the dip switch SW17 of the centralized remote controller. POWER ON/OFF ENGAGED GROUP 1 2 3 4 5 6 7 8 9 10 Centralized remote controller GROUP SELECTION ACTIVE BYPASS PROGRAM TIMER DUAL CENTRAL CONTROLLER OPERATION BACK AHEAD ACTIVE BYPASS DUAL CENTRAL Power supply board 10 9 8 7 6 5 4 3 2 1 48 Dip switch SW17 OC155-B--2.qxp 7/26/00 4:46 PM Page 49 5. PROGRAM TIMER ADAPTER This adapter is needed when a program timer (PAC-SK65PT) or the centralized remote controller (PAC-805RC) is used. Part No. PAC-825AD 5-1 Parts included ➀ ADAPTER··························1P ➁ 3-core cable ···························1P ➂ 3-core cable ···························1P Length : 2m (6' 7") Length : 2m (6' 7") ➃ 4-core cable ···························1P ➄ 5-core cable ···························1P Length : 2m (6' 7") Length : 2m (6' 7") 5-2 Connection method Connection and wiring methods differ with the type of the indoor unit used. Confirm the type before carrying out the work. (1) Connections in the adapter Box 1. Connect the power supply cord to the terminal-block and fix it in-place with a tie-lap. Connect a single phase 200V AC (220, 230, 240V) to L N. As ; is the GND terminal, be sure to ground the earth wire. 2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-lap, when a centralized remote controller is being used. CAUTION : Never connect the power supply cord to the transmission terminal-block fig.1 fig.2 CN22 SW1 SW1 CN22 TRANS Dip switch CN1 (AG) CN21 CN51 CN30 CN42 CN50 CN40 L Transmission N Tie-lap TERMINAL BLOCK FOR POWER SUPPLY T (W) (B) (Y) 220 -240 TRANS 200 TERMINAL BLOCK FOR TRANSMISSION E 5A L N Tie-lap Transmission cord Fuse(5A) POWER SUPPLY CORD TRANSFORMER 49 POWER SUPLLY OC155-B--2.qxp 7/26/00 4:46 PM Page 50 (2) Set the address number (from SW1-1 to SW1-6) in the dip switch when a centralized remote controller is being used. The address is the control number of each unit in the centralized control system. As the address serves as a time-delay device as well, sequential starts (all units are triggered collectively by one single ON instruction)must be set with different address numbers (greater than 0) for each adapter. 10 9 8 7 6 5 4 3 2 1 ON SW1 Levers No. 1-6 can set the following addresses respectively with binary notations. Toggle No.6 ON No.5 ON No.4 ON No.3 ON No.2 ON No.1 ON Address 32 16 8 4 2 1 (Ex.1) 3 = 2 + 1 (Ex.2) 9 = 8 + 1 (Ex.3) 15 = 8 + 4 + 2 + 1 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 ON ON (3) Connection from adaptor ON 40 80 40 27 18 65 12 120 86 Fixing screw hole 4- 5.5 5-core cable 5 ho 15 le 27 35 Remote controller Indoor unit Max. length of each calbe is 10m. 35 2 2- 2.9 8 7 74 CN2 CN51 15 22 22 3-core cable 2 95 220 CN30 CN50 230 200~240V AC 70 Adaptor 15 5-3 Dimensions Fig. 4 Fig.3 To program timer or centralized remote controller 30 200 6. TIMER ADAPTER This adapter is needed for system control and for operation via external contacts. Part No. PAC-SA89TA-E ORN 1 BRN 2 RED 3 7. REMOTE INDICATION ADAPTER This adapter is used for remote indication (operation / check). PAC-559AD Part No. BRN RED ORN YLW GRN JST XHP-3 + BRN <Wiring> - RED CN51 + ORN - YLW - GRN 5 GREEN X1 The maximum distance between indoor boared and relay is 10m. 5 5+ - 2 50 RL X1 X2 YELLOW X2 ORANGE 1 connector (5P) RED BROWN Electrical insulation is needed Optional multiple display Local wiring adapter GL Power supply OC155-B--2.qxp 7/26/00 4:46 PM Page 51 OC155-B--2.qxp 7/26/00 4:46 PM Page 52 HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO100-8310 TELEX J24532 CABLE MELCO TOKYO CCopyright 1997 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Issued in Jul. 2000. No. OC155 REVISED EDITION-B 1540 Issued in Dec.1997. No. OC155 REVISED EDITION-A 670 Issued in Sep.1997. No. OC155 860 Printed in Japan. New publication, effective Jul. 2000. Specifications subject to change without notice.