Download Worcester_GreenstarSi_Installation

Transcript
PRE-INSTALLATION
3.8
FLUE OPTIONS
CAUTION: Non accessible flue systems:
Plume management kits are available for the
60/100 horizontal flue system.
Refer to the manual supplied with the plume
management kits for complete installation
instructions
B Where a flue system is not going to be
accessible, provision must be made for
service and inspection.
B Voids containing concealed flues must
have at least one inspection hatch no less
than 300mm square.
FLUE LENGTHS
The flue systems have different maximum flue lengths
B Flue joints within the void must not be
more than 1.5M from the edge of the
inspection hatch.
The Greenstar series has the option of two horizontal
60/100 RSF (telescopic and extended telescopic) and
two horizontal 80/125 RSF (telescopic and extended
telescopic) flue systems and two vertical RSF (60/100 or
80/125) flue systems:
B Inspection hatches should be located at
changes of direction.
B If this is not possible, bends should be
viewable from both directions.
The next page shows various fluing options.
NOTICE: Effective flue lengths:
Refer to the Flue options in table 18 for the straight flue
lengths required to achieve the maximum flue length.
B each 90° bend used is equivalent to
2 metres of straight flue
B each 45° bend used is equivalent to
1 metre of straight flue
25Si and 30Si boilers
Maximum total
flue length (mm)
FLUE TYPE
60/100
80/125
1
Telescopic horizontal flue assembly
570
1,070
2
Horizontal flue extension
4,600
13,000
3
Horizontal flue with 1 x 90° bend
2,600
11,000
4
Horizontal flue with 2 x 90° bends
N/A
9,000
5
High level horizontal flue
4,600
13,000
6
High level horizontal flue with 2 x 90° bends
2,600
11,000
7
High level horizontal flue with 3 x 90° bends
N/A
9,000
8
Vertical balanced flue assembly
6,400
15,000
9
Vertical balanced flue with 2 x 90° bends
2,400
11,000
10
Vertical balanced flue with 2 x 45° bends
4,400
13,000
Tab. 18 Flue options
20
6 720 643 895a (2010/10)