Rectifying faults EA and flashing. During operation: flame not detected Check 1. 2. Is the flame present? Is the gas cock open? Action yes: ↓6. no: ↓2. yes: ↓3. no: B Open the gas cock B Press , does appliance restart??? EA? ↓3. 3. Is there air in the supply pipe? yes: B Vent supply pipe. B Press , does appliance restart??? EA? ↓4. 4. Did the thermical security of the gas cock lock out? no: ↓4. yes: B Reset security. B Press , does appliance restart??? EA? ↓5. 5. Natural gas models: does the building have a supply pressure regulator? no: ↓5. yes: B Check that it is fitted correctly and functioning properly and correct if necessary. B Check supply pressure, inform gas company if outside correct range. B Press , does appliance restart??? EA? ↓6. LPG models: is the flow rate of the gas supply to the appliance correct? no: ↓6. yes: ↓6. no: B Is there enough gas in the supply cylinder? B Is there air in the supply pipe? B Is the solenoid valve in the “meter cabinet” opening? B Is the supply pressure OK? (if the supply pressure is too high, check the pressure regulator in the “meter cabinet” and on the LPG supply cylinder). B Press , does appliance restart??? EA? ↓6. 28 7 181 465 347 (01.07)