Download 1 Introduction
Transcript
2 Installation 2.6.2 Cx Series The Cx-series models do not contain any RS485 interfaces and need to be retrofitted. Please contact in this case the installer or manufacturer. 2.6.3 E Series The E-series models have no communication interfaces, which means an interface has be fitted before being able to attach to the SolarLog. Please follow the installation instructions that are attached to the relevant interface. Pay particular attention to the proper setting of the RS485/RS232 Jumpers and the terminating resistance on the interface card (See manual of the interface card). Each inverter needs to have a separate communication address assigned to it. It is advisable for the addresses to start at 1, i.e. 1, 2, 3, etc. Again, this setting will be carried out via the operation display. Follow the appropriate instructions in the SolarMax manual. 2.6.4 Wiring Use the RJ45 format for attaching and connecting the RS485 data cable plug to the inverter. These are the same plugs as in conventional network patch cables. Warning! The SolarLog also has an RJ45 socket. Please under no circumstances connect this socket to the RJ45 socket of the inverter. This could destroy the SolarLog! Note: We recommend the prefabricated SolarMax data cable, which is available as an accessory. If the cable is custom-made, then use the following termination circuit: 8 1 RJ45-plug from the front RJ45 Pin 1 2 3 4 5-unused 6-unused 7 8 24 SolarLog RS485 2 2 3 3 1 4