Download Downloading - Beijer Electronics
Transcript
MAEN922.book Page 16 Wednesday, November 7, 2007 9:57 AM Communication Ports 5 Communication Ports COM1, a 9-pin female connector, is used to connect the operator terminal to a controller via RS232 or RS485. COM2, a 25-pin female connector, is used to connect the operator terminal to a controller via RS232, RS422 or RS485. COM3, a 9-pin female connector, is used to connect the operator terminal to a controller via RS422 or RS485. Note: Make sure that the connection is in accordance with the setting of the dip switches, for example RS485 corresponds to SW10 and SW11 = ON. See section 4 Dip Switches. Pin Function Pin Function 1 RS485+ 1 RS422 TX+ (RS485+) 2 RS232 RXD 2 RS422 CTS+ 3 RS232 TXD 3 RS422 CTS- 4 N/A 4 RS422 RX+ 5 Signal ground 5 Signal ground 6 RS485- 6 RS422 TX- (RS485-) 7 RS232 RTS 7 RS422 RTS+ 8 RS232 CTS 8 RS422 RTS- 9 Optional; +5V@100mA output 9 RS422 RX- 16 Beijer Electronics, MAEN922