Download SYSMAC CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2)
Transcript
Section Basic PC Operation and I/O Processes 1-2 The cycle monitor time is used for checking for extremely long cycle times, as can happen when the program goes into an infinite loop. If the cycle time exceeds the cycle monitor setting, a fatal error (FALS 9F) will be generated. Note 1. The units used for the maximum and current cycle times recorded in the AR area (AR 14 and AR 15) are determined by the setting for the cycle monitor time in DM 6618, as shown below. Bits 08 to 15 set to 01: Bits 08 to 15 set to 02: Bits 08 to 15 set to 03: 0.1 ms 1 ms 10 ms 2. If the cycle time is 1 s or longer, the cycle time read from Programming Devices will be 999.9 ms. The correct maximum and current cycle times will be recorded in the AR area. Example If 0230 is set in DM 6618, an FALS 9F error will not occur until the cycle time exceeds 3 s. If the actual cycle time is 2.59 s, the current cycle time stored in the AR area will be 2590 (ms), but the cycle time read from a Programming Device will be 999.9 ms. A “cycle time over” error (non-fatal) will be generated when the cycle time exceeds 100 ms unless detection of long cycle times is disable using the setting in DM 6655. 1-2-7 Minimum Cycle Time Make the settings shown below to standardize the cycle time and to eliminate variations in I/O response time by setting a minimum cycle time. Bit 15 0 DM6619 Cycle time (4 digits BCD) 0000:Cycle time variable 0001 to 9999: Minimum cycle time (Unit: 1 ms) Default: Cycle time variable If the actual cycle time is shorter than the minimum cycle time, execution will wait until the minimum time has expired. If the actual cycle time is longer than the minimum cycle time, then operation will proceed according to the actual cycle time. AR 2405 will turn ON if the minimum cycle time is exceeded. 1-2-8 Input Time Constants Make the settings shown below to set the time from when the actual inputs from the DC Input Unit are turned ON or OFF until the corresponding input bits are updated (i.e., until their ON/OFF status is changed). Make these settings when you want to adjust the time until inputs stabilize. Increasing the input time constant can reduce the effects from chattering and external noise. Input from an input device such as a limit switch Input bit status t t Input time constant The SRM1(-V2) does not have this setting. 19
Related documents
CPM2B-S001M-DRT Programmable Controller - Innovative-IDM
SYSMAC CPM1A Programmable Controllers
FLAMES User Manual
CXM547 User`s Manual
HCA4 User Manual
FQ2-CH Optical Character Recognition Sensor User`s Manual
Operation with sense lines
USER MANUAL - SmartLink International
User`s Manual - Newport Corporation
NB-series Programmable Terminals SETUP MANUAL
Programmable Terminal NTH25/25C
Programmable Controller PROGRAMMING MANUAL