Download Control Panel - 230V
Transcript
12.Example application for barriers When control panel is used for barriers operations: - set RF=5 (MAX); - set TM=MAX; - set JR6=ON; - select the proper opening direction by means of DIP2. 1 3 4 5 (Example 1). Connect opening and closing limit switches N.C. contacts to plug 12-0-11. 2 DIP2=OFF RF=5 MAX ON ON 1 2 3 4 1 2 3 4 R1 TC TM 12 0 11 JR6 DIP2=ON 12 11 0 1 5 6 8 9 41 ON (Example 2). Control N.C. 1-6 (safety stop) can be changed into control N.O. 1-4 (closing) setting 6→4=OFF. To have the barrier close again soon after transit between the photocells (or other safeties connected to 1-8), set DIP3=OFF. 6>4 Limit switch Limit switch 1 2 3 4 DIP3=OFF ON 1 2 3 4 R1 TC TM 12 0 11 JR6 Opening Closing 12 11 0 1 5 6 8 9 41 13.Application example for rolling shutters <MAX <MAX ON 1 2 3 4 12 0 11 R1 TC TM JR6 N C U W V Limit switch com When the control panel is used in applications for rolling shutters: - set JR6=ON - connect the N.C. limit switches in succession to the motor phases - make a jumper with the terminals 0-11-12. M1 1~ IP2045EN - 2013-03-26 i NOTE: if the control panel is used in the hold to run mode, disconnect terminal 9 (see example 1 in Section 14). 13 12 11 0 1 5 6 8 9 41