9V TERMINAL AND REMOTE TEST & HUSH
The use of an unsuitable relay and base could also lead to an electric shock risk.
The wiring between the Smoke Alarm and the relay must be installed in accordance
with the relevant requirements of the SAA Wiring Rules, AS3000, for low voltage
(240V) conductors.
1
FIRE INDICATOR
PANEL
LOCAL ALARM PANEL
ORANGE
BLUE
WHITE
YELLOW
See installation manual
for isolation relay RK10A/9
9V
A SW N
LOOP
A SW N
LOOP
9V
SW N
9V
24V
16
LOOP
A SW N
CONNECTION TO A
MAXIMUM OF 24 SMOKE ALARMS
24
2
9V
FUSE ON
CIRCUIT
BREAKER
RED
ORANGE
BLUE
WHITE
YELLOW
RED
Wiring Instruction Showing Smoke Alarms Interconnected
and Used as part of an Early Warning Indicator System