Download SETUP MANUAL
Transcript
Appendices A-4-5 Method for fabricating the cable for connection to PC When fabricating the cable for connecting with NB-Designer, refer to the following methods: Depending on the type of the RS-232C connector compatible with PCs according to DOS/V, deploy the wiring as shown below: 25-pin Connector NB Unit side COM1 (female) at the NB Unit side Signal Name Pin No. 1 5 Shielded Cable DB25 Serial Port at the PC side Pin No. Signal Name RS232 DB25 (male) at the PC side FG Connector Shield Connector Shield FG 13 25 9 NC SD RD RS (RTS) CS (CTS) DC+5V NC NC SG 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 20 22 FG SD RD RS CS DR SG CD ER RI 14 1 A-4 Fabrication of the Connection Cable 6 9-pin Connector NB Unit side COM1 (female) at the NB Unit side Signal Name Pin No. 1 RS232 DB9 (male) at the PC side Connector Shield FG 5 9 1 2 3 4 5 6 7 8 9 CD RD SD ER SG DR RS CS RI 1 6 Note As to the 2 connection methods introduced above, the No.2, 3 and 9 pins of COM1 on the NB3Q unit side have the same definitions as those described in the above diagram, and the method for connection to a PC is also the same as above. NB-series Programmable Terminals Setup Manual(V107) A-13 A-4-5 Method for fabricating the cable for connection to PC 9 Connector Shield NC 1 SD 2 RD 3 RS (RTS) 4 5 CS (CTS) DC+5V 6 7 NC 8 NC 9 SG FG DB9 Serial Port at the PC side Pin No. Signal Name App 5 6 Shielded Cable