9 Settings setpoint plus the value set here. The setting -5°C results in the intermedi ate circuit pump being switched on as soon as the boiler temperature is 5°C below the boiler setpoint . Excess interm circ temp del (5151) Control of the burner output on the charging temperature is activated if the time set here has elapsed since switching on the intermediate circuit pump. 9.2.17 Configuration Temps / mode CH1 (5710),Temps / mode CH2 (5715) andTemps / mode CH3 (5721) The heating circuits can be switched on or off using this setting. Heating circuit parameters are hidden in the deactivated state. Note This adjustment only affects the heating circuits directly and has no influence on operation. Hot water sensor (5730) None: No DHW sensor available. Hot water sensor B3: There is a DHW storage tank sensor available. The controller calculates the switching points with the corresponding switching difference from the DHW setpoint and the measured DHW storage tank temperature. Thermostat: Control of domestic hot water temperature as a function of the switching status of a thermostat connected to DHW sensor B3. Note No reduced mode is possible when a DHW thermostat is used. This means if reduced mode is active, the DHW preparation is blocked with the thermostat. Caution No frost protection for DHW! The domestic water frost protection cannot be guaranteed. Hot water ctrl elem Q3 (5731) No charging request: DHW charging disabled via Q3. Charging pump: DHW charging via the connection of a charging pump to Q3/Y3. Diverting valve: DHW charging via the connection of a diverting valve to Q3/Y3. Basic pos HW div valve (5734) The base position of the diverting valve is the position in which the divert ing valve (DV) is in if no request is active. Last request: The diverting valve (DV) remains after the last request has ended in this last position. Central heating: The diverting valve (DV) goes into the heating circuit position after the last request has ended. Hot water: The diverting valve (DV) goes into the DHW position after the last request has ended. Hot water separate circuit (5736) The DHW separate circuit can only be used in a boiler cascade. Off: The DHW separate circuit function is disabled. Each available boiler can feed the DHW storage tank. On: The DHW separate circuit function is enabled. The DHW charging is only done from the boiler defined for this. Note The DHW actuator Q3 must be set under prog. no. 5731 to "Di verting valve" for a DHW separate circuit to become effective. 7636047 - 02 - 24082015 109