USER MANUAL - OPTIMA UPS 1K-3K (ENGLISH) _________________________________________________________________________________________________________________________________ 4. INSTALATION WARNINGS FOR FULL BRIDGE MODELS: (1KF to 3KF) & (1KF-CN to 3KF-CN) FULL BRIDGE MODELS: For all full-bridge models (1KF-3KF & 1KF-CN to 3KF-CN), It is not allowed to connect output Neutral line to input Neutral line. This practice can damage UPS. This kind of damage is not covered by warranty. FIG-1 FULL BRIDGE MODELS: For all full-bridge models (1KF-3KF & 1KF-CN to 3KF-CN) it is not allowed to connect output Neutral to system Ground. This practice will generate internal damage in the UPS. In full-bridge UPS output Neutral is not same than input Neutral so a floating voltage will be generated between N-G at output side of the UPS. This voltage is not harmful for your equipment connected to UPS. If you need 0Vac in N to G for your equipment, please check recommendation of FIG 3. HALF BRIDGE models allow connection of their output Neutral line with system ground (G). FIG-2 www.xmart-ups.com 150610-OPTIMA 1K-3K - 7