Download Group I Operating Manual - Eagle Eye Power Solutions
Transcript
OPERATING THE AT10.1 2.4.4. Check temperature compensation probe (optional) If you are using the optional temperature compensation probe, make sure that the probe (A10) is securely installed. Make sure the connectors and the wiring from the probe to the AT10.1 are in satisfactory condition. If there is a failure of the temperature compensation probe, or the wiring, the AT10.1 displays the error code E 08. 2.4.5. Measuring the output ripple voltage (filtered models only) If your AT10.1 is a filtered model, measure the ac ripple at the battery terminals at least once a year. Use an rms responding ac voltmeter.1 If the battery Ampere-hour capacity is at least four (4) times the output current rating of the AT10.1, the ripple voltage should be no higher than the value featured in the specifications in Appendix A on page 70. If you suspect that the output ripple voltage is too high, see "Output ripple voltage too high" of the Troubleshooting Chart in Section 3.4, page 53. 2.4.6. Viewing the voltage and alarm settings You can review the parameter settings in the AT10.1 by pressing the EDIT/ENTER key on the front instrument panel. Each time you press the key, a different parameter displays, in the following order: • • • • • • 1 Float voltage Equalize voltage Equalize time (in hours) High dc voltage alarm setting Low dc voltage alarm setting Current Limit (in Amperes) Do not use a dc voltmeter. The ripple voltage on a battery is a very small ac voltage. 41