Parameter Description P2041[5] Issue 10/06 CB parameter CStat: CT P-Group: COMM Datatype: U16 Active: first confirm Min: Def: Max: Unit: QuickComm.: No Level 0 0 65535 3 Configures a communication board (CB). Index: P2041[0] : CB parameter 0 P2041[1] : CB parameter 1 P2041[2] : CB parameter 2 P2041[3] : CB parameter 3 P2041[4] : CB parameter 4 Details: See relevant communication board manual for protocol definition and appropriate settings. r2050[4] CO: PZD from CB Datatype: U16 Min: Def: Max: Unit: - P-Group: COMM Level - 3 Displays PZD received from communication board (CB). r2050 [0] [1] [2] [3] r2090 r2091 PZD4 STW2 CB-Frame PZD3 PZD Process data PZD2 HSW PKW Parameter P2041[0] PZD1 STW1 CB-Frame PKW PZD STW HSW Parameter ID value Process data Control word Main setpoint CB telegram CB on COM link PZD mapping to parameter r2050 Index: r2050[0] r2050[1] r2050[2] r2050[3] : : : : Received word 0 Received word 1 Received word 2 Received word 3 Note: The control words can be viewed as bit parameters r2090 and r2091. Restrictions: - If the above serial interface controls the inverter (P0700 or P0719) then the 1st control word must be transferred in the 1st PZD-word. - If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transfered in the 2nd PZD-word, - When P2012 is equal to 4 the additional control word (2nd control word) must transferred in the 4th PZD-word, if the above serial interface controls the inverter (P0700 or P0719). 122 MICROMASTER 420 Parameter List 6SE6400-5BA00-0BP0