4 10 Digital Filter In certain application the process value is too unstable to be read. To improve this a programmable low pass filter incorporated in the ZEL - 2500 can be used. This is a first order filter with time constant specified by FILT parameter which is contained in setup menu. The default value of FILT is 0.5 sec. before shipping. Adjust FILT to change the time constant from 0 to 60 seconds. 0 second represents no filter is applied to the input signal. The filter is characterized by the following diagram. Menu FILT Filter is used to stabilize the process display. PV1 FILT=0 1 sec FILT=1 Figure 4.7 Filter Characteristics FILT=30 1 sec Time Note The Filter is available only for PV1, and is performed for the displayed value only. The controller is designed to use unfiltered signal for control even if Filter is applied. A lagged ( filtered ) signal, if used for control, may produce an unstable process. 78