Download LG_BACnet_Gateway_PQNFB17C1

Transcript
152
Functional Specifications ACP BACnet
Operation Mode (Status)
ENGLISH
‡ Point number: 8
‡ Object name: ModeStatus_XXX (XXX: Indoor/Vent/AHU address)
‡ Object type: Multistate Input
‡ Meaning: This object is used to monitor the operation modes of the air conditioner.
‡ Present_Value property:
+PFQQT
8GPV
1 : Cool
HEX
2 : Dry
Auto
3 : Fan
Normal
4 : Auto
-
5 : Heat
-
Swing (Setting)
‡ 3RLQWQXPEHU
‡ Object name: SwingCommand_XXX (XXX: Indoor address)
‡ Object type: Binary Output
‡ Meaning: This object is to set the air direction of the indoor unit.
‡ Present_Value property:
‡ ACTIVE: Run
‡ INACTIVE: Stop
Swing (Status)
‡ Point number: 10
‡ Object name: SwingStatus_XXX (XXX: Indoor address)
‡ Object type: Binary Input
‡ Meaning: This object is to monitor the air direction of the A/C.
‡ Present_Value property:
‡ ACTIVE: Swing_On
‡ INACTIVE: Swing_Off