Download LG_BACnet_Gateway_PQNFB17C1
Transcript
190 Functional Specifications ACP BACnet * Supported COV service is shown in the follow table ENGLISH Service Object Product On/Off (status) Binary Input object property Indoor / vent Lock On/Off (status) Binary Input object property Indoor / vent Mode Lock (status) Binary Input object property Indoor Wind Flow Lock (status) Binary Input object property Indoor Set Upper Temperature (status) Analog Input object property Indoor Set Lower Temperature (status) Analog Input object property Indoor Operation mode (status) Multistate Input object property Indoor / vent Swing (status) Binary Input object property Indoor Filter Sign Binary Input object property vent Fan Speed (status) Multistate Input object property Indoor / vent Set Room Temperature Analog Value object property Indoor Room Temperature Analog Input object property Indoor Alarm Binary Input object property Indoor / vent Error Code Analog Input object property Indoor / vent User mode Multistate Input object property vent