Parameter List
12.95
PNU
OP1 parameter name
* : Conf.
Description
Value range
[phys. unit]
Selection text
Display
Indices
Factorysetting
See
Modify
(access /
status)
0 to 1818Hex
-
3/ BR
0.0 to 150.0% of
P075
[%]
4
150.0%
3/
3/
ABR
A
-150.0 to 0.0% of
P075
[%]
4
-150.0%
3/
3/
ABR
A
0.01 to 1.00
4
0.15
3/
3/
BR
BR
0.001 to 1.000
[s]
4
0.015
3/
3/
BR
BR
0.10 to 200.00
4
3.00
3/
3/
BR
BR
Par.
5.7
r150
Control
Control Status
Status word of the control
15
7
14
6
13
12
5
4
11
3
10
2
9
1
8
0
Meaning of the individual segments
3
4
11
12
Rectifier current limit reached
Rectifier stability limit reached
Regerating current limit reached
Inverter stability limit reached
Segment bright: corresponding limit reached
Segment dark:
corresponding limit not reached
P160
1
PNU=96Hex; Type=V2;Scaling: 1Hex Motor Curr Limit
Motoring current limit
The rectifier current is limited to the value set here
RDS parameter
P161
**
0.1
PNU=0A0Hex; Type=O2; Scaling: 1Hex Regen Curr Limit
Generating current limit
The regenerating current is limited to the value set here.
RDS parameter
P310
0.1
PNU=0A1Hex; Type=I2; Scaling: 1Hex DC Curr Reg Gain
Proportional gain of the DC link current controller
This parameter is automatically set when circuit identification takes place
(P052=21)
RDS parameter
P311
0.01
PNU=136Hex; Type=O2; Scaling: 1Hex DC Curr Reg Time
Integral-action (reset) time of the DC link current controller
This parameter is automatically set when circuit identification takes place
(P052=21)
RDS parameter
P313
0.001
PNU=137Hex; Type=O2; Scaling: 1Hex DC Volts RegGain
Proportional gain of the DC link voltage controller
This parameter is automatically set when circuit identification takes place
(P052=21)
RDS parameter
0.01
PNU=139Hex; Type=O2; Scaling: 1Hex 5-12
Siemens AG
Rectifier/Regenerating Unit
6SE7087-6AK85-1AA0
Operating Instructions