BEIJING EPSOLAR TECHNOLOGY CO., LTD.
7. Protection
Tel: +86-10-82894112 / 82894962
9. Technical Specifications
 PV Reverse Polarity
Item
Fully protection against PV reverse polarity, no damage to the controller will result.
Correct the miswire to resume normal operation.
 Battery Reverse Polarity
Fully protection against battery reverse polarity, no damage to the controller will result.
Correct the miswire to resume normal operation.
 Battery Over Voltage
When the battery voltage reaches to the set point of Over Voltage Disconnect Voltage,
the controller will stop charging the battery to protect the battery from being over
charged to break down.
 Battery Over Discharge
When the battery voltage reaches to the set point of Low Voltage Disconnect Voltage,
the controller will stop discharging the battery to protect the battery from being over
discharged.
 Battery Overheating
The controller detect the environment temperature through the external temperature
sensor. If the environment temperature exceeds 65 ºC, the controller will automatically
start the overheating protection to stop working, and recover below 50 ºC.
 Load Short Circuit
Load will be switched off when load short circuit (≥4 times rated current) happens.
Controller will automatically attempt to reconnect load for 5 times. If short circuit
protection still exist after controller’s 5 times attempts, user have to clear short
circuit ,then disconnect and restart the controller or wait for one night-day cycle (night
time>3 hours).
 Damaged Local Temperature Sensor
If the temperature sensor short-circuited or damaged, the controller will be charging or
Nominal system
voltage
Rated charge
current
Max. PV open circuit
voltage
Battery input
voltage range
Max. output power
Max. output Current
Output voltage
range
Load open circuit
voltage
Maximum output
efficiency
Output current
control accuracy
Battery Type
Self-consumption
Charge Circuit
Voltage Drop
Temperature
compensation
coefficient
Communication
distance of IR
Communication
angle of IR
Working
environment
temperature
Enclosure
Overall dimension
LS101240EPLI
LS102460EPLI
LS2024100EPLI
12VDC
12/24VDC Auto
12/24VDC Auto
10A
10A
20A
30V
50V
50V
9~16V
9~32V
40W
2.6A
30W/12V;60W/24V
2.0A
Mounting dimension
discharging at the default temperature 25℃ to prevent the battery damaged from
PV is protected against small high voltage surge. In lightning prone areas, additional
external suppression is recommended.
PV
array disconnection
Battery
LED
indicator green Fast
Flashing
Battery over voltage
Battery
indicator red
Battery
over discharged
Powering
on
normally, the load is
off
The
dimming
function is invalid
Parameter settings
fail
Net weight
≤30mA
Sealed(Default) / Gel / Flooded / User
≤9.1mA(12V);≤7.0mA(24V)
≤0.16V
-3mV/℃/2V
≤6m
≤15°
-35℃~+55℃
IP68(1.5m,72h)
107x68x20mm
108.5x88x25.6 mm
100mm
100.5mm
Φ5
PV/BAT:12AWG(4.0mm2)
LOAD:18AWG(1.0mm2)
0.23kg
Battery charging setting
Possible reasons
Min.9V can start up
the controller.
All the LED indicator
flashing(battery red
indicator flashing)
96%
0.39kg
24V system)
No LED indicator
Battery Status LED
indicator
red
flashing
60V
Battery Voltage Parameters (parameters is in 12V system at 25℃, please use X 2 in
8. Troubleshooting
LED
Max. Battery Voltage +2V~60V
PV/BAT:14AWG(2.5mm2)
LOAD: 18AWG(1.0mm2)
Power cable
 High Voltage Transients
9~32V
50W/12V;100W/24V
3.3A
Φ4
Mounting hole size
overcharging or over discharged.
Faults
Charging
LED
indicator off during
daytime
when
sunshine falls on PV
modules properly
Website:www.epsolarpv.com/www.epever.com
Battery Overheating
System voltage error
① The connecting
wires are error or
virtual connection
② Load mode is
wrong
③ The controller
does not match with
the LED light.
④ Output
short
circuit
The controller does
not match with the
LED light source.
This product is a
step-up
current
control,
If input
voltage is lower than
the rated voltage, it
is not working.
Infrared
communication error
Troubleshooting
Confirm that PV and battery wire
connections are correct and tight
Measure
battery
voltage
with
multi-meter. Min.9V can start up the
controller.
① Disconnect the solar array and
measure the battery voltage whether is
too high; ②Change the controller; ③
Change the battery
When the battery voltage is restored to
or above setpoint (low voltage
reconnect voltage), the load work
The controller will automatically stop
working. When the temperature is
below 50 ºC, the controller will resume
to work.
Check whether the battery voltage
match with the controller working
voltage. Please change to a suitable
battery or reset the working voltage
Over Voltage Disconnect
Voltage
Charging Limit Voltage
Over Voltage Reconnect
Voltage
Equalize Charging Voltage
Boost Charging Voltage
Float Charging Voltage
Boost Reconnect Charging
Voltage
Low Voltage Reconnect
Voltage
Under Voltage Warning
Reconnect Voltage
Under Voltage Warning
Voltage
Low Voltage Disconnect
Voltage
Discharging Limit Voltage
Equalize Duration
Boost Duration
Sealed
Gel
Flooded
User
16.0V
16.0V
16.0V
9~17V
15.0V
15.0V
15.0V
9~17V
15.0V
15.0V
15.0V
9~17V
14.6V
14.4V
13.8V
——
14.2V
13.8V
14.8V
14.6V
13.8V
9~17V
9~17V
9~17V
13.2V
13.2V
13.2V
9~17V
12.6V
12.6V
12.6V
9~17V
12.2V
12.2V
12.2V
9~17V
12.0V
12.0V
12.0V
9~17V
11.1V
11.1V
11.1V
9~17V
10.6V
120min
10.6V
——
10.6V
120min
9~17V
0~180min
120min
120 min
120min
10~180min
NOTE:
①Check the connecting cables
②Check the load mode and parameter
③The voltage of LED light source is
not in the output voltage range of
controller
④Check the connecting cables and
LED light source
1) The default battery type is Sealed, For Sealed, Gel, Flooded battery type, the
voltage point is fixed, unable to modify it. The adjusting range of equalize duration
is 0 to180min and boost duration is 10 to180min.
2) User type is the user defined battery type. The default value is the same as sealed
type. When modify it, please follow the below logistic relation:
a ) Over Voltage Disconnect Voltage>Charging Limit Voltage ≥Equalize Charging Voltage
≥Boost Charging Voltage ≥ Float Charging Voltage >Boost Reconnect Charging
①Replace the LED light
②Reduce system rated voltage grade
and replace the product model
For example 24V system change to
12V system, and replace the
corresponding controller.
See handheld the user device manual
Voltage.
b ) Over Voltage Disconnect Voltage>Over Voltage Reconnect Voltage.
c) Low Voltage Reconnect Voltage>Low Voltage Disconnect Voltage ≥ Discharging Limit
Voltage.
d ) Under Voltage Warning Reconnect Voltage>Under Voltage Warning Voltage ≥
Discharging Limit Voltage.
e ) Boost Reconnect Charging voltage>Low Voltage Disconnect Voltage.
Any changes without prior notice!
3
4
Version number:V2.2