Download Manual - Solectria
Transcript
PVI 60KW, PVI 82KW, PVI 95KW green: yellow: Installation and Operation Manual AC VOLTAGE TOO HIGH (alternating green & red LED) AC Grid Voltage above UL limits (>228V if 208VAC, >528V if 480VAC) feeding grid MPP or constant voltage mode normal daytime operation red: green: yellow: red: green: de-rating mode or inverter at full power reduction of power fed to the grid yellow: due to increased temperature of the red: heatsink or inverter is at full rated power green: GFDI fuse failure GFDI fuse is defective see chapter 5 green: Contactor Failure yellow: (one blink) Contactor timer run out before successful open or close yellow: red: red: green: Vsense Failure yellow: (two blinks) DSP board cannot communicate with vsense board red: green: Thermal Overshot yellow: (three blinks) Contactor open during power operation because of thermal overshot red: green: Current Sensor Failure yellow: (Four blinks) Current sensor failed self-calibration during the unit wakeup red: green: Temperature Sensor Failure yellow: (five blinks) Temperature sensor read below -30C green: Desat Failure Power stage desaturation failure yellow: (one blink (pause) two blinks) red: red: green: IGBT over temperature yellow: (one blink (pause) three blinks) Power stage junction temperature over limit (125C) Utility Failure A failure of the Utility (i.e. a blackout or red: green: yellow: brownout) has occurred red: Unit will restart 5 min after grid (AC) restored green: 5 minute wait for re-start Utility required 5 minute wait for restart yellow: (alternating green, yellow & red LEDs in process since grid (AC) restored red: in sequence) green: Wong AC Phase Sequence yellow: DOC-020099 rev 041 Switch two phase wires for correct clockwise sequence 21