1.3.1
“Type 1” unit: Water/water, Heating + DHW
Fig. 1.c
Analogue inputs
No. Description
B1
Ground source circuit outlet temperature
B2
Ground source circuit return temperature
B3
DHW control temperature
B4
Mixed circuit outlet temperature
B5
System return temperature
Analogue inputs via Modbus RS485
No.
Description
Sn.B1 Outside temperature probe
Sn.B2 Outside humidity probe
Up to 6 rooms from Clima
+030220741 Smart HP – rel 2.2 -12/11/2013
Digital inputs
No.
Description
ID1
Flow switch, ground source well side
Comp. 1 overload alarm/Comp. inverter
ID2
alarm
ID3
High pressure switch
ID4
Low pressure switch
ID5
Unit/system pump overload
ID6
DHW storage heater overload
ID7
Integration boiler/heater alarm
ID8
Remote On-Off
10
Analogue outputs
No. Description
Y1
Y2
Modulating ground source pump
Y3
System 3-way valve
Y4
Comp inverter
Digital outputs
No.
Description
NO1
Compressor 1
NO2
Ground source pump
NO3
Primary circuit pump
NO4
DHW/system switching valve
NO5
Mixed circuit pump
NO6
System integ. boiler/heater
NO7
DHW storage integ. boiler/heater
NO8
General alarm