Contacting SD type
The thick continuous lines in the circuit diagram below represent main circuit. Use conductor of approx. 0.75 mm2.
The thin continuous lines represent signal circuit. Use conductor of size approx. 0.3 mm2.
The thick continuous lines in the circuit diagram below represent main circuit. Use conductor of approx. 0.75 mm2.
The thin continuous lines represent signal circuit. Use conductor of size approx. 0.3 mm2.
• DZ9102 and DZ9202 standard electrical diagram (reversible motor)
• DZ9302 fundamental electrical wiring diagram (3-phase motor)
SW3
RUN
BRAKE
CW
R1
SW2
SW4
RUN
3
6
RUN
BRAKE
C1
C1
White
RUN
8
RUN
Gray
RUN
BRAKE
Black
SW3
RUN
RUN
RUN
SW5
CW
R1
Ry5
6
NFB
SW3
Ry4 Ry5
DV0P008 (option)
Motor
25 W or smaller
40 W or larger
100 V supply system
0Ω
30 Ω (approx. 100 W)
200 V supply system
0Ω
100 Ω (approx. 100 W)
4
5
Pin No.
R6
If
Ry4
4
Vcc
5
Ry5
Vocw
Vocw
RUN
LOAD
White
Gray
R2
Black
Capacitor
R5
NFB
SSR
Black
R2
Vcc
Motor
R6
R5
SW3
C1
Ry2
Ry1
Ry2
White
Braking
R1+C1
SW1
SW2
SW4 SW5
RUN
BRAKE
RUN
SW3
RUN
BRAKE
RUN
Motor
Black
Ry3 Ry2 Ry1
C1
Gray
RY1, RY2
Run
ON
CW
R1
SW1, SW6 AC250 V 10 A min.
Accessory
Braking
3ø
AC200V
Pin No.
DC10 V 10 mA
DV0P008 (option)
R4
S
T
R
BRAKE
7
R4
RY3
BRAKE
Relay HP/HG (Panasonic Electric Works
Co.,Ltd.) or equivalent
DV0P008 (option)
Accessory
Twin contact or Au-clad contact relay
Braking
Run
SW1
Braking
Run
ON
T1
[Notes]
1. When SW2, SW3 and SW4 are switched from RUN to
BRAKE, electric brake is applied for approx. 0.5 sec (T1)
causing the motor to stop quickly.
2. Do not place these switches to RUN position while the
electric braking is applied (T1).
3. A massive amount of current will flow through SW2, SW4
and SW5. Use a disconnecting device (switch or relay)
rated at 10 A or more. When using a relay, use HP/HG
(Panasonic Electric Works Co.,Ltd.) or equivalent.
Capacitor
SW6
RUN
Ry2
ON
ON
Ry3
ON
ON
Ry1
Electric
brake
BRAKE
RUN
BRAKE
ON
ON
T1
T1
[Notes]
Ry1 and Ry2 should be interlocked to avoid
simultaneous “ON”.
Control signal
Vocw
Pin No.
• When using power relay
Voccw
RUN
BRAKE
BRAKE
SSR
R6
RY1 Relay HP/HG (Panasonic Electric Works Co.,Ltd.) or equivalent
NFB
SW1
AQP107 (Panasonic Electric Works
Co.,Ltd.), or equivalent
1
2
R4
6
R1
C1
Ry1
SW1
Vocw
Voccw
Electric
brake
RUN
Braking
Run
ON
White
BRAKE
BRAKE
RUN
T1
Gray
7
4
RUN
BRAKE
T1
R5
Vcc
Ry1
If
5
RUN
BRAKE
RUN
BRAKE
Motor
[Notes]
1. Use 0 Ω R5 when Vcc is below 6 VDC.
When Vcc is 6 VDC or higher, determine the value of R5
according to the equation shown below.
Ripple of Vcc should be 5% or below.
(Internal resistance 220 Ω)
• Resistance of R5
RUN
Vo
Pin No.
Vo
C1
Black
Braking
SW1
Braking
Run
ON
CW
R1
C1
Braking
Run
3ø
AC200V
R1
Ry1
10 Ω
Run
S
T
R
Ry1
* Please read your User's manual carefully so that you will understand the operation and safety precautions before attempting to operate the system.
C-50
Ry2
C1
R1
AC250 V 10 A min.
R1+C1
If
[Notes]
1. Use 0 Ω R5 when Vcc is below 6 VDC.
When Vcc is 6 VDC or higher, determine the value of R5 according
to the equation shown in description for induction motor.
Ripple of Vcc should be 5% or below. (Internal resistance 220 Ω)
2. Ry4 and Ry5 should be relay or electromagnetic contactor with the
rated voltage two or more times the power supply voltage and the
rated current 3 A or more.
3. Do not place Vocw and Voccw in RUN at the same time.
4. Be sure to use resistor R6 to protect relay, SSR and capacitor.
Current will flow through R6 - 2 A 90 W; 1.7 A 60 W; 1 A 40 W; 0.6
A 25 W; 0.4 A 15 W.
5. Also refer to SSR handling precaution (see contactless relay
catalog).
R4
Ry1
Run
AC100V
LOAD INPUT
SW6
RUN
R1
Ry2
SW4, SW5
R1+C1
1
2
7
8
Gray
R2
8
7
DC10 V 10 mA
SW1
INPUT
Ry1
Gray
SW1, SW2
SSR
Motor
7
3
6
C1
T1
• When using contactless relay (SSR)
(Cannot be used for DZ9202)
White
R2
Motor
Black
SW4, SW5 200 V supply system 5 A or more at 250 VAC
C1
C1
BRAKE
SW1, SW2 100 V supply system 5 A or more at 125 VAC
R1
Ry4
RUN
Ry3
White
T1
Rated voltage
input
Connection for
DZ9202
C1
NFB
SW1
1
2
Electric
brake
• When using power relay
SW1
R4
CW
R1
RUN
Pin No.
Control signal
1
2
C1 BRAKE
Index
CCW
T1
R2
SW4
• For application using inching motion frequently
If SW2 and SW5 emit long sparks, use of the
following circuit is recommended.
CW
Electric
brake
[Notes]
1. When SW2 (SW4) and SW3 are switched from RUN to
BRAKE, electric brake is applied for approx. 0.5 sec (T1)
causing the motor to stop quickly.
2. Never place both SW2 and SW4 in RUN position at the
same time.
3. Never select RUN while electric brake is applied (T1).
4. When using DZ9202, do not operate SW5 while the
electric brake is being applied (T1).
5. The wattage of R2 should be determined based on
frequency of start and stop operations. First check the
power dissipation.
R1
RUN
R1
BRAKE
Capacitor
SW2
BRAKE
3
6
SW4
R2
Pin No.
RUN
Braking
BRAKE
3ø
AC200V
SW3
BRAKE
SW5
SW2
7
Run
ON
SW1
CCW
R2
Braking
Run
Motor
SW5
CW
Clockwise
T
R
CCW Counterclockwise
R1
S
1
2
Options
BRAKE
Connection for
DZ9202
CW
NFB
SW1
Rotating direction viewed
from shaft end
Rated voltage
input
Brake Unit
NFB
SW1
1
2
Speed controller
Brake Unit
BRAKE
R5 = Vcc – 6 V at If = 15 to 20 mA
If
• Example Vcc = 24 V If = 20 mA
24 – 6
R5 =
= 900 Ω = 1 kΩ
20 x 10–3
* Please read your User's manual carefully so that you will understand the operation and safety precautions before attempting to operate the system.
C-51