Download Brake Unit Overview
Transcript
Contacting SD type The thick continuous lines in the circuit diagram below represent main circuit. Use conductor of approx. 0.75 mm2. The thin continuous lines represent signal circuit. Use conductor of size approx. 0.3 mm2. The thick continuous lines in the circuit diagram below represent main circuit. Use conductor of approx. 0.75 mm2. The thin continuous lines represent signal circuit. Use conductor of size approx. 0.3 mm2. • DZ9102 and DZ9202 standard electrical diagram (reversible motor) • DZ9302 fundamental electrical wiring diagram (3-phase motor) SW3 RUN BRAKE CW R1 SW2 SW4 RUN 3 6 RUN BRAKE C1 C1 White RUN 8 RUN Gray RUN BRAKE Black SW3 RUN RUN RUN SW5 CW R1 Ry5 6 NFB SW3 Ry4 Ry5 DV0P008 (option) Motor 25 W or smaller 40 W or larger 100 V supply system 0Ω 30 Ω (approx. 100 W) 200 V supply system 0Ω 100 Ω (approx. 100 W) 4 5 Pin No. R6 If Ry4 4 Vcc 5 Ry5 Vocw Vocw RUN LOAD White Gray R2 Black Capacitor R5 NFB SSR Black R2 Vcc Motor R6 R5 SW3 C1 Ry2 Ry1 Ry2 White Braking R1+C1 SW1 SW2 SW4 SW5 RUN BRAKE RUN SW3 RUN BRAKE RUN Motor Black Ry3 Ry2 Ry1 C1 Gray RY1, RY2 Run ON CW R1 SW1, SW6 AC250 V 10 A min. Accessory Braking 3ø AC200V Pin No. DC10 V 10 mA DV0P008 (option) R4 S T R BRAKE 7 R4 RY3 BRAKE Relay HP/HG (Panasonic Electric Works Co.,Ltd.) or equivalent DV0P008 (option) Accessory Twin contact or Au-clad contact relay Braking Run SW1 Braking Run ON T1 [Notes] 1. When SW2, SW3 and SW4 are switched from RUN to BRAKE, electric brake is applied for approx. 0.5 sec (T1) causing the motor to stop quickly. 2. Do not place these switches to RUN position while the electric braking is applied (T1). 3. A massive amount of current will flow through SW2, SW4 and SW5. Use a disconnecting device (switch or relay) rated at 10 A or more. When using a relay, use HP/HG (Panasonic Electric Works Co.,Ltd.) or equivalent. Capacitor SW6 RUN Ry2 ON ON Ry3 ON ON Ry1 Electric brake BRAKE RUN BRAKE ON ON T1 T1 [Notes] Ry1 and Ry2 should be interlocked to avoid simultaneous “ON”. Control signal Vocw Pin No. • When using power relay Voccw RUN BRAKE BRAKE SSR R6 RY1 Relay HP/HG (Panasonic Electric Works Co.,Ltd.) or equivalent NFB SW1 AQP107 (Panasonic Electric Works Co.,Ltd.), or equivalent 1 2 R4 6 R1 C1 Ry1 SW1 Vocw Voccw Electric brake RUN Braking Run ON White BRAKE BRAKE RUN T1 Gray 7 4 RUN BRAKE T1 R5 Vcc Ry1 If 5 RUN BRAKE RUN BRAKE Motor [Notes] 1. Use 0 Ω R5 when Vcc is below 6 VDC. When Vcc is 6 VDC or higher, determine the value of R5 according to the equation shown below. Ripple of Vcc should be 5% or below. (Internal resistance 220 Ω) • Resistance of R5 RUN Vo Pin No. Vo C1 Black Braking SW1 Braking Run ON CW R1 C1 Braking Run 3ø AC200V R1 Ry1 10 Ω Run S T R Ry1 * Please read your User's manual carefully so that you will understand the operation and safety precautions before attempting to operate the system. C-50 Ry2 C1 R1 AC250 V 10 A min. R1+C1 If [Notes] 1. Use 0 Ω R5 when Vcc is below 6 VDC. When Vcc is 6 VDC or higher, determine the value of R5 according to the equation shown in description for induction motor. Ripple of Vcc should be 5% or below. (Internal resistance 220 Ω) 2. Ry4 and Ry5 should be relay or electromagnetic contactor with the rated voltage two or more times the power supply voltage and the rated current 3 A or more. 3. Do not place Vocw and Voccw in RUN at the same time. 4. Be sure to use resistor R6 to protect relay, SSR and capacitor. Current will flow through R6 - 2 A 90 W; 1.7 A 60 W; 1 A 40 W; 0.6 A 25 W; 0.4 A 15 W. 5. Also refer to SSR handling precaution (see contactless relay catalog). R4 Ry1 Run AC100V LOAD INPUT SW6 RUN R1 Ry2 SW4, SW5 R1+C1 1 2 7 8 Gray R2 8 7 DC10 V 10 mA SW1 INPUT Ry1 Gray SW1, SW2 SSR Motor 7 3 6 C1 T1 • When using contactless relay (SSR) (Cannot be used for DZ9202) White R2 Motor Black SW4, SW5 200 V supply system 5 A or more at 250 VAC C1 C1 BRAKE SW1, SW2 100 V supply system 5 A or more at 125 VAC R1 Ry4 RUN Ry3 White T1 Rated voltage input Connection for DZ9202 C1 NFB SW1 1 2 Electric brake • When using power relay SW1 R4 CW R1 RUN Pin No. Control signal 1 2 C1 BRAKE Index CCW T1 R2 SW4 • For application using inching motion frequently If SW2 and SW5 emit long sparks, use of the following circuit is recommended. CW Electric brake [Notes] 1. When SW2 (SW4) and SW3 are switched from RUN to BRAKE, electric brake is applied for approx. 0.5 sec (T1) causing the motor to stop quickly. 2. Never place both SW2 and SW4 in RUN position at the same time. 3. Never select RUN while electric brake is applied (T1). 4. When using DZ9202, do not operate SW5 while the electric brake is being applied (T1). 5. The wattage of R2 should be determined based on frequency of start and stop operations. First check the power dissipation. R1 RUN R1 BRAKE Capacitor SW2 BRAKE 3 6 SW4 R2 Pin No. RUN Braking BRAKE 3ø AC200V SW3 BRAKE SW5 SW2 7 Run ON SW1 CCW R2 Braking Run Motor SW5 CW Clockwise T R CCW Counterclockwise R1 S 1 2 Options BRAKE Connection for DZ9202 CW NFB SW1 Rotating direction viewed from shaft end Rated voltage input Brake Unit NFB SW1 1 2 Speed controller Brake Unit BRAKE R5 = Vcc – 6 V at If = 15 to 20 mA If • Example Vcc = 24 V If = 20 mA 24 – 6 R5 = = 900 Ω = 1 kΩ 20 x 10–3 * Please read your User's manual carefully so that you will understand the operation and safety precautions before attempting to operate the system. C-51