Download CHAPTER 1 - - InverterDelta
Transcript
Chapter 6 - Parameter Description [APP] APP-58: Delay Time before Starting Aux. Motor APP-59: Delay Time before Stopping Aux. Motor APP-60, 61: Accel/Decel time when the number of pumps is increasing/decreasing APP► Aux Start DT 58 5.0 sec Factory Default: 58 APP-62: PID Bypass Selection APP► Regul Bypass 62 No Factory Default: 5.0 Sets the time the inverter waits before starting the auxiliary motors. APP► Aux Stop DT 59 5.0 59 5.0 sec Factory Default: APP►Pid AccTime 60 2.0 sec Factory Default: 60 2.0 2.0 2.0 sec APP►Pid DecTime 61 2.0 sec Factory Default: 5.0 5.0 sec 61 2.0 2.0 2.0 sec Sets the time the inverter waits for the input before stopping the auxiliary motors. Output Frequency Aux start DT(APP-58) Frequency rise due to APP-58 Start freq 1 (APP-44) 0 No Output Frequency Max. Freq. Stop freq1 (APP-51) Starting Freq. 0 This is used to bypass the PID operation selected in APP-02. Select this code to ‘Yes’ when using MMC function without PID control. The frequency is determined by actual value (feedback) of control amount instead of PID controller output. The actual value is also used as the Start/Stop reference of Aux. motors. The following figure shows the running pattern with this function applied for controlling the flow rate of a tank. To control the flow rate proportional to the water level of a tank, divide the water level in the tank into the region for the number of Aux. motors plus one, and map each region by staring frequency to maximum frequency. The inverter increases output frequency to lower the water level in the tank when the water level in the tank rises. When reaching maximum frequency, inverter connects aux. motors connected directly to commercial line. After connecting aux. motor, inverter starts again from the starting frequency. By selecting APP-61 [Regul Bypass] to ‘Yes’, PID operation is disabled and Control Mode is changed to ‘V/F’. PID Bypass is available only when DRV-04 [Freq. Mode] is set to ‘V1’, ‘I’ or ‘Pulse’. 5.0 5.0 sec 62 Frequency drop due to APP-59 Aux stop DT(APP-59) Start Aux. Motor Start/Stop Stop Starting Freq. Flow When the flow increase When the flow decrease [Aux. Motor Start/Stop with MMC] H-min H-max Water Level in a Tank RUN STOP Main Motor RUN STOP Aux. Motor [PID bypass with Main motor and Aux. Motor] APP-60 and APP-61 sets the acceleration/ deceleration time of the Main motor by 0.1 sec when more/less aux motors are connected. 6-65