Download CHAPTER 1 - - InverterDelta

Transcript
Chapter 6 - Parameter Description [APP]
APP-58: Delay Time before Starting Aux. Motor
APP-59: Delay Time before Stopping Aux. Motor
APP-60, 61: Accel/Decel time when the number of
pumps is increasing/decreasing
APP► Aux Start DT
58
5.0 sec
Factory Default:
58
APP-62: PID Bypass Selection
APP► Regul Bypass
62
No
Factory Default:
5.0
Sets the time the inverter waits before starting the
auxiliary motors.
APP► Aux Stop DT
59
5.0
59
5.0 sec
Factory Default:
APP►Pid AccTime
60
2.0 sec
Factory Default:
60
2.0
2.0
2.0 sec
APP►Pid DecTime
61
2.0 sec
Factory Default:
5.0
5.0 sec
61
2.0
2.0
2.0 sec
Sets the time the inverter waits for the input before
stopping the auxiliary motors.
Output
Frequency
Aux start DT(APP-58)
Frequency rise due to APP-58
Start freq 1
(APP-44)
0
No
Output
Frequency
Max. Freq.
Stop freq1
(APP-51)
Starting
Freq.
0
This is used to bypass the PID operation selected in
APP-02. Select this code to ‘Yes’ when using MMC
function without PID control. The frequency is
determined by actual value (feedback) of control
amount instead of PID controller output. The actual
value is also used as the Start/Stop reference of Aux.
motors.
The following figure shows the running pattern with
this function applied for controlling the flow rate of a
tank. To control the flow rate proportional to the
water level of a tank, divide the water level in the
tank into the region for the number of Aux. motors
plus one, and map each region by staring frequency
to maximum frequency. The inverter increases output
frequency to lower the water level in the tank when
the water level in the tank rises. When reaching
maximum frequency, inverter connects aux. motors
connected directly to commercial line. After
connecting aux. motor, inverter starts again from the
starting frequency. By selecting APP-61 [Regul
Bypass] to ‘Yes’, PID operation is disabled and
Control Mode is changed to ‘V/F’. PID Bypass is
available only when DRV-04 [Freq. Mode] is set to
‘V1’, ‘I’ or ‘Pulse’.
5.0
5.0 sec
62
Frequency drop due to APP-59
Aux stop DT(APP-59)
Start
Aux. Motor
Start/Stop
Stop
Starting
Freq.
Flow
When the flow
increase
When the flow
decrease
[Aux. Motor Start/Stop with MMC]
H-min
H-max
Water Level in
a Tank
RUN
STOP
Main Motor
RUN
STOP
Aux. Motor
[PID bypass with Main motor and Aux. Motor]
APP-60 and APP-61 sets the acceleration/
deceleration time of the Main motor by 0.1 sec when
more/less aux motors are connected.
6-65