Chapter 6 - Parameter Description [FU2]
Note: There are WDOG error, EEP error, and
ADC Offset for the inverter Hardware Fault, and
the inverter will not reset when H/W fault occurs.
Repair the fault before turning on the power.
6.3 Function 2 Group [FU2]
FU2-00: Jump to desired code #
FU2►
00
Jump code
1
Factory Default:
1
1
Jumping directly to any parameter code can be
accomplished by entering the desired code number.
This code is available only with LCD keypad.
FU2-01: Last trip 1
FU2-02: Last trip 2
FU2-03: Last trip 3
FU2-04: Last trip 4
FU2-05: Last trip 5
FU2-06: Erase Trips
01
nOn
nOn
□
□
□
Factory Default:
None
0
0
No
This function erases all fault histories of FU2-01 to
FU-05 from the memory.
However, FU2-83 [Last Trip Time] cannot be reset.
FU2► Dwell time
07
0.0 sec
None
FU2► Last trip-5
05
None
Factory Default:
06
FU2-07: Dwell Time
FU2-08: Dwell Frequency
FU2► Last trip-1
01
None
Factory Default:
FU2► Erase trips
06 --- No ---
Factory Default:
0.0
0.0
0.0 sec
FU2► Dwell freq
08
5.00 Hz
Factory Default:
05
07
5.00
08
5.00
5.00 Hz
Note: If the dwell time is set at ‘0’, this function is
not available.
Note: Do not set the Dwell frequency above
frequency command. Otherwise, it may lead to
operation fault.
Note: this function is disabled in Sensorless
control.
nOn
nOn
This code displays up to five previous fault (trip)
status of the inverter. Use the PROG, ▲ and ▼ key
before pressing the RESET key to check the fault
content(s) such as output frequency, output current,
and whether the inverter was accelerating,
decelerating, or in constant speed at the time of the
fault occurred. Press the ENT key to exit.
FU2-83 [Last Trip Time] is the time elapsed after last
trip occurs. User can count the last trip time from this
value.
Output freq.
FU2-08
FU2-07
RUN
6-24
Time