Appendix 1 - Troubleshooting FLOWCHART - Cont. 5 - Water alarm Electric system Electrical parts defective 60% Microprocessor Flow switch Temperature sensor Auxiliary relay in chiller control panel Interlock 40% Water system Temperature 40% Check wiring and electric parts of interlock wiring Leaving chilled water temperature too low 70% Temperature control function does not work properly. Wrong operating order. Holding water quantity in the chiller is too low. Entering cooling water temperature too low 20% Ambient temperature is too low. Leaving hot water temperature too low 10% Temperature control function does not work properly. Cooling water temp. control malfunctions. Wrong operating order. Holding water quantity in the chiller is too low. Flow rate 60% Check chilled-water flow switch Air in water system? Strainer in water system is clogged?. Valves in water system opened properly? 48