Download 3E3EV Multi-function User`s Manual
Transcript
Chapter 4 Preparing for Operation n44 Multi-function Analog Output Setting range 0, 1 Factory setting 0 This constant is used to select the contents of the analog outputs (AM and AC) for monitoring. Value 0 1 Description Output frequency Output current Note The output level can be set with the constant set in n45 for the multi-function analog output gain. n45 Multi-function Analog Output Gain Setting range 0.00 to 2.00 Factory setting 0.30 Unit of setting 0.01 This constant is used to set the ratio between the analog output voltage and output frequency (or output current). Relationship Between Analog Output Voltage and Output Frequency (Output Current) Maximum frequency (or rated current) 100 % Factory setting (n45 = 0.30) n45 = 1.00 3V 4-30 10 V Analog output voltage