UPS Systems from 200 to 1200 kVA
1 Scope
This specification describes a continuous
duty three-phase, solid state, full IGBT
(Insulated Gate Bipolar Transistor),
double conversion uninterruptible power
supply (UPS) system. The UPS will
automatically provide continuity of
electrical power, within defined limits
and without interruption, upon failure or
degradation of the commercial AC
source.
The continuity of conditioned electric
power will be delivered for the time
period defined by the battery system.
The rectifier, the inverter, and other
mission critical converters within the
UPS, are driven by vector control
algorithms (covered by patents 95
P3875, 95 P3879 and 96 P3198) running
on dedicated digital signal processor
(DSP) systems operating in combination
with the Trinergy algorithm.
2 General requirements
2.1 Applied standards
Chloride
operates
a
Quality
Management System which complies
with BS EN ISO 9001-2000 for
the design, manufacturing, sales,
installation, maintenance and service
of uninterruptible power supply
systems. The Chloride Environmental
Policy and Management Systems
comply with EN ISO 14 001. Chloride is
also committed to implementing a
policy of continuous improvement to
its production processes and pollution
reduction. Trinergy will carry the
CE mark in accordance with the
European Safety Directive 2006/95
(superseding the 73/23 and successive
amendments) and European EMC
directive
2004/108
(superseding
the 89/336, 92/31 and 93/68). Trinergy
is designed and manufactured
in accordance with the following
international standards:
• IEC/EN62040-1-1 general and safety
requirements
• EN62040-2 EMC requirements
• IEC/EN62040-3 operating requirements
• Classification according to IEC/EN
62040-3: VFI-SS-111
2.2 Safety
In terms of general and safety
requirements, the UPS conforms to
standard IEC/EN 62040-1-1 governing
use in unrestricted access locations.
2.3 EMC and surge suppression
Electromagnetic effects will be minimised
in order to ensure that computer systems
and other similar electronic loads will
neither be adversely affected by nor affect
the UPS. The UPS will be designed to
meet the requirements of EN 62040-2,
class C3. The manufacturer and customer
in partnership agree to ensure the
essential EMC protection requirements
for the specific resulting installation.
2.4 Neutral connection and grounding
Trinergy output neutral will be electrically
isolated from the UPS chassis. The input
and output neutral connections are the
same, i.e. they are solidly tied together.
Therefore the UPS will not modify the
state of the upstream neutral, in any
operating mode, and the neutral state of
the distribution downstream from the
UPS is imposed by the mains one.
Trinergy will be used in installations with
grounded neutral; for further details
please contact Chloride Technical Support.
2.5 Materials
All materials and components comprising
the UPS will be new and of current
manufacture.
3 System description
3.1 The system
The UPS will provide high quality AC
power for electronic equipment loads
and will offer the following features:
•
•
•
•
•
Trinergy technology
Maximum energy savings
Scalability up to 9.6 MW
Increased power quality
Full input Power Factor Correction
(PFC) and very low THDi
MKA4CAT0UKTRIN/Rev 1-09/2009/UK
• Full compatibility with any TN and
IT installation
• Full compatibility with any standby
power generator
• Full compatibility with all types of
loads with PF up to 1 without
derating
• Power blackout protection
• Advanced battery care
• Transformer free design
02
The UPS will automatically provide
continuity of electrical power, within
defined limits and without interruption,
upon failure or degradation of the
commercial AC source.
In a single UPS Trinergy can provide a
parallel of up to six power modules
operating in parallel for capacity or
redundancy.