Download Trinergy
Transcript
CHLORIDE Trinergy UPS Systems from 200 to 1200 kVA 1 Scope This specification describes a continuous duty three-phase, solid state, full IGBT (Insulated Gate Bipolar Transistor), double conversion uninterruptible power supply (UPS) system. The UPS will automatically provide continuity of electrical power, within defined limits and without interruption, upon failure or degradation of the commercial AC source. The continuity of conditioned electric power will be delivered for the time period defined by the battery system. The rectifier, the inverter, and other mission critical converters within the UPS, are driven by vector control algorithms (covered by patents 95 P3875, 95 P3879 and 96 P3198) running on dedicated digital signal processor (DSP) systems operating in combination with the Trinergy algorithm. 2 General requirements 2.1 Applied standards Chloride operates a Quality Management System which complies with BS EN ISO 9001-2000 for the design, manufacturing, sales, installation, maintenance and service of uninterruptible power supply systems. The Chloride Environmental Policy and Management Systems comply with EN ISO 14 001. Chloride is also committed to implementing a policy of continuous improvement to its production processes and pollution reduction. Trinergy will carry the CE mark in accordance with the European Safety Directive 2006/95 (superseding the 73/23 and successive amendments) and European EMC directive 2004/108 (superseding the 89/336, 92/31 and 93/68). Trinergy is designed and manufactured in accordance with the following international standards: • IEC/EN62040-1-1 general and safety requirements • EN62040-2 EMC requirements • IEC/EN62040-3 operating requirements • Classification according to IEC/EN 62040-3: VFI-SS-111 2.2 Safety In terms of general and safety requirements, the UPS conforms to standard IEC/EN 62040-1-1 governing use in unrestricted access locations. 2.3 EMC and surge suppression Electromagnetic effects will be minimised in order to ensure that computer systems and other similar electronic loads will neither be adversely affected by nor affect the UPS. The UPS will be designed to meet the requirements of EN 62040-2, class C3. The manufacturer and customer in partnership agree to ensure the essential EMC protection requirements for the specific resulting installation. 2.4 Neutral connection and grounding Trinergy output neutral will be electrically isolated from the UPS chassis. The input and output neutral connections are the same, i.e. they are solidly tied together. Therefore the UPS will not modify the state of the upstream neutral, in any operating mode, and the neutral state of the distribution downstream from the UPS is imposed by the mains one. Trinergy will be used in installations with grounded neutral; for further details please contact Chloride Technical Support. 2.5 Materials All materials and components comprising the UPS will be new and of current manufacture. 3 System description 3.1 The system The UPS will provide high quality AC power for electronic equipment loads and will offer the following features: • • • • • Trinergy technology Maximum energy savings Scalability up to 9.6 MW Increased power quality Full input Power Factor Correction (PFC) and very low THDi MKA4CAT0UKTRIN/Rev 1-09/2009/UK • Full compatibility with any TN and IT installation • Full compatibility with any standby power generator • Full compatibility with all types of loads with PF up to 1 without derating • Power blackout protection • Advanced battery care • Transformer free design 02 The UPS will automatically provide continuity of electrical power, within defined limits and without interruption, upon failure or degradation of the commercial AC source. In a single UPS Trinergy can provide a parallel of up to six power modules operating in parallel for capacity or redundancy.