Download JW-22CM User`s Manual

Transcript
[4] F-206, F-207
F-206 Open channel 1
EOP1 (1 layer: Specify the station number in octal notation)
F-207 Open channel 2
EOP2 (1 layer: Specify the station number in hexadecimal notation)
(1) Installed in a JW30H
The F-206 and F-207 instructions when the JW-22CM is installed in a JW30H are as follows.
Symbol
Function
F-206
UN1,CH ST1
EOP1
F-207
ST2
EOP2
UN2
file N
n
Specify the target station for inter-PLC data communications to be performed across the
satellite net (JW-22CM, JW-20CM). F-206 (EOP1) are used in conjunction with the F-207
(EOP2), F-204 (SEND) or F-205 (RCV) instructions.
UN1
Use range 0 to 6: Module no. of module starts from SEND/RECEIVE instructions.
UN2
Use range 0 to 7: Module no. of module from relay station 2 of SEND/RECEIVE
instructions. Note: When the relay station 2 is JW50H/70H/100H, it
becomes slot number.
CH
Use range 0 to 3: Channel no. of module starts from SEND/RECEIVE instructions.
ST1
Use range 00 to 77(8): The relay station 1st station number of SEND/RECEIVE instructions.
ST2
Use range 00 to 77(8): The relay station last station number of SEND/RECEIVE instructions.
file N
Use range 0 to 3, 10 to 2C(H) (JW30H), 0 to 7 (JW50H/70H/100H): File number in the last
station of
SEND/RECEIVE
*1
instructions.
n
Condition
Flag
Use range 000000 to 177777(8): File address in the last station of SEND/RECEIVE
instructions.
When an input signal is ON. (Not limited to changing from OFF to ON)
Unchanged
*1: If the communication target is a JW300, change "FILE F, n" used with the JW300 to "file N, n" used with
the JW30H. => Refer to page 10-5.
Relay 1
Last station
Start point
Relay 2
10
U
N
1
CH
U
N
2
N
n
ST1
(2) Installed in a JW300
The F-206 and F-207 instructions when the JW-22CM is installed in a JW300 are as follows.
Please note that the function, UN2, CH, ST1, ST2, operating condition, and flag items are the
same as described above (when installed in a JW30H).
Symbol
UN1
FILE F
n
F-206
UN1,CH ST1
EOP1
UN2
F-207
ST2 FILE F
EOP2
n
Use range 0 to 7 : Module no. of module that starts SEND/RECEIVE instructions.
Use range 0 and 1: File address in the last station of SEND/RECEIVE instructions.
*2
Use range 00000000 to 37777777(8): File address in the last station of
SEND/RECEIVE instructions.
*2: If the communication target is a JW30H and JW50H/70H/100H, change "file N, n" used with the
JW30H etc. to "FILE F, n" used with the JW300. => Refer to page 10-5.
Make sure to use only the three instructions: F-206, F-207, and F204, or the three instructions; F-206,
F-207, and F-205.
10-8