Download TRP-C24H User`s Manual

Transcript
TRP-C24H
16 channels isolated digital output
(Open Collector) Modbus TCP module.
User’s Manual
Printed Sep. 2014 Rev 1.4
Trycom Technology Co., Ltd
No.35, Zhongxing Rd., Guishan Township, Taoyuan County 333, Taiwan.
Tel : 886-3-350-3351 Fax: 886-3-350-3352
Web: www.trycom.com.tw
Copyright
Copyright Notice: The information in this manual is subject to change without notice to improve reliability, design and
function and does not represent a commitment on the part manufacturer. No part of this manual may be
reproduced, copied, or transmitted in any form, without prior written permission by the manufacturer. Products
mentioned in this manual are mentioned for identification purposes only. In this manual, product names appearing
may or may not be registered trademarks of their respective companies or copyright.
1. Introduction
The TRP-C24H is an Isolated open collector digital outputs Modbus TCP Module, It provides 16 channels output
open collector signal (100mA) to driven your devices on network, It supports 3 communication Protocols, TRP-ASCII,
Modbus RTU / ASCII, It can be easy and convenient to use application supports Modbus.
Software engineers can use the TRP-ASCII or Modbus RTU/ASCII command set quickly and easily integrated into
the self-development program, such as Microsoft VB, VC...
The TRP-C24H built-in independent IP, WEB-browsing more convenient to rewrite the configuration and collect
information through computers, tablet computers, smart phones, will be available!
The TRP-C24H built-in watchdog Hardware ensure the normal operation of the module, and a built-in voltage
monitoring to ensure that the boot, excellent and advanced hardware for harsh environment.
The TRP-C24H can TRP-C26H, 16 remote control directly, do not need to run the software and equipment.
When TRP-C24H and TRP-C26H are paired, they can support 16 channels remote control does not require any
drivers and software support.
The TRP-C24H is also offers the maximum connection 16 host client to link the network server that is easy to
operate in Modscan32 ,Modbus Poll,CAS Modbus Scanner and SCADA ...application uses TCP mode and
Virtual-COM mode.
1-1 Features
 Wide input range DC power supply.
 Automatically determine 3 TRP-ASCII and Modbus RTU/ASCII communication protocol.
 16 TCP Port can be open at the same time.
 Heart Beat function ensures a reliable communicating connection.
 Support Virtual-COM mode.
 IO status can be set in the boot.
 WEB PAGE can be directly output and read IO status.
 Easily update the firmware using the Internet.
 Back to factory configuration by external touch Button.
 Auto reconnection when power or Ethernet fail.
 Digital output signal with 3750Vrms isolation protection.
 Built-In watchdog function prevents system boot fail.
 LED for each I/O channels working status.
 Support Auto-MDIX twisted pair crossover detection and Auto-Correction.
 Power/Link/16 CH DO LED indicator.
 DIN-Rail and panel mount support.
 Dual power input select from screw terminal or DC-Jack.
1-2 Specification.






Power Input Voltage DC +10V to +30V.
Protocol: TRP-ASCII and Modbus RTU/ASCII.
Digital output maximum voltage:+30V.
Digital output maximum current: 100mA.
Digital output isolation: 3750Vrms.
Communication interface: Ethernet RJ45.
2













Configuration mode: Trycom Device Manager, WEB settings.
Matching remote control: with TRP-C26H.
Heart Beat: TCP Port sent string every 5 seconds.
TCP Maximum Connection:1~16.
Module ID :1~255.
Connection type: Screw terminal for maximum AWG 12 wire.
Power supply: Screw terminal, or external DC adapter.
Power consumption 240mA/12V.
Operating environment: 0 to 50℃.
Storage temperature:. -10 to 70℃.
Humidity: 10~90% Non-condensing.
Dimension: 151mm X 75mm X 26mm .
Weight: 395g .
2. Hardware Description
2-1. Panel layout
Notice: The Module provides two type power inputs, optional DC-JACK or Screw Terminal input, not to two used
together!
2-2. Block Diagram
PWR LED: Blinking is ready.
LINK LED: RJ-45 cable connection and data active.
D0~DF LED: Each digital status indication.
DC Jack: Power Input DC +10V to +30V, Please use the 5.5*2.1mm DC JACK.
3
2-3. Factory Button
Hold down the button, and then power on, until the power light flashes, Release the button.
2-4. Factory parameter values
4
2-5. Screw Terminal Pin assignment Description
2-6. Block Diagram
2-7. Pin Description
DO5
Digital output Channel 5
DOF
Digital output Channel F
DO4
Digital output Channel 4
DOE
Digital output Channel E
DO3
Digital output Channel 3
DOD
Digital output Channel D
DO2
Digital output Channel 2
DOC
Digital output Channel C
DO1
Digital output Channel 1
DOB
Digital output Channel B
DO0
Digital output Channel 0
DOA
Digital output Channel A
EXT.PWR
The isolated side power input MAX.30V
DO9
Digital output Channel 9
5
EXT.GND
The isolated side ground
DO8
Digital output Channel 8
DC 10~30V
Input DC 10~30V
DO7
Digital output Channel 7
GND
Power Ground
DO6
Digital output Channel 6
3.Install TRP-C24H Hardware
STEP1: Connect power source with TRP-C24H, the PWR LED will blinking.
STEP2: Connect TRP-C24H with netwotk by RJ45 cable.
If the cable is properly connected the “LINK” LED will light up.
*The TRP-C24H Support Auto-MDIX, A straight-through or crossover RJ45 cable can be used to make a connection
directly to the HUB/Router/PC LAN port.
STEP3: Connect TRP-C24H screw terminal wiring, such as 2-5 picture description.
4. How to configure TRP-C24H
*Please note that the computer's IP segment adjusted with TRP-C24H same section, modify the parameter values in
order to effectively store!
For example:
Computer IP is 192.168.1.xx
TRP-C24H 192.168.1.1
There are 2 ways can change the module parameter values.
A.DSM Software
B. WEB Server
6
4-1. Using DSM Utility
The DSM utility software performs several functions:
A: Searching for TRP-C24H connected to the network.
B: Displaying and changing the configuration.
C: Upgrading the TRP-C24H firmware, Refer the Firmware upgrade help file.
D: Saving and Loading Configuration from external log File or EEPROM.
4-2. Searching TRP-C24H
Once TRP-C24H is connected to the network the DSM software will search it and display it in a window by name, IP
address, Mac….Information.
7
4-3.Configuring Server Properties
Select the “NO.” item and Double click to open the module configuration, after setting then click “Submit” will
save the configuration to memory.
8

Device Name:
Device server name, Maximum 10 chars.

Model Name:
TRP-C24H.

MAC Address
The TRP-C24H MAC address.

DHCP
If DHCP is disabled, it allows user setting the IP address, Subnet mask, Gateway.
If DHCP is enabled, the IP address, Subnet mask, Gateway address will be dynamically configuration by DHCP
server such router.
When DHCP is enabled, but the DHCP server is not available on the network, the TRP-C24H will timeout then back
to factory setting IP=192.168.1.1.

Server Listening IP
The TRP-C24H IP address.

Server Data listening port
TRP-C24H port address.

Client Destination IP
When user using the pair mode, the client setting need to input module IP and port which one need to connect.

Client Destination port
Client port address.
Port: 16 bit number. (1 ~ 65535)

Netmask
The default LAN Netmask is configured for a Class C address. This maybe reconfigured by the user.
9

Gateway
Input the gateway IP address that can be allows users to access the serial server from internet.

DNS
Short for Domain Name System, an Internet service that translates domain names into IP addresses. Because
domain names are alphabetic, they're easier to remember. The Internet however, is really based on IP addresses.
Every time you use a domain name, therefore, a DNS service must translate the name into the corresponding IP
address.


Transmit Timer: This feature is only available to Serial Server TRP-C37 and TRP-C37M.
Maximum Connection: 1~16
The function allows the user to configure the TRP-C24H in Server mode, adjust 1~16 TCP client host connections.

TCP Keep Alive: 1~7 /Minute
When TRP-C24H in Server or Client mode, the TRP-C24H without data over the 1~7 Min setting value,
The TRP-C24H will be disconnecting TCP port.

New Password: 1234
It only accepts value from1000~9999 integer, if input the wrong password over 5 times, the WEB-Page will lock until
the TRP-C24H re-boot.


Firmware Version: ABC
Slave ID:1~255.
ID performs MODBUS RTU / ASCII and TRP-ASCII will use to address.

LED Display Panel Setting :ON/OFF
The setting will turn on all panels LED or Turn off panel LED.

Polling Setting: High/Low.
Digital High / Low potential settings, Applies only TRP-C26H/C28H

System Mode
Power ON Mode: Digital output state when the TRP-C24H Power On.
Save ON Mode: The digital output state when the TRP-C24H is working, Once this mode is set, the digital output
state cannot be rewritten.
Pair Mode: It can be used as a remote manual remote control, when the TRP-C24H 16 DO and TRP-C26H 16 CH
DI, TRP-C28H 4 D I/O with TRP-C28H 4 D I / O. Without any driver.
Trycom Checksum setting: Disable/Enable.
TRP-ASCII command used bit checksum.

Power On Mode Output: 0000~FFFF.
Digital output state when TRP-C24H Boot!

Save ON Mode Output:0000~FFFF.
Digital output state when watchdog enable!

Digital Output Status
Display last stored in the memory of the digital output state.

Digital Input Status
This feature is only available to TRP-C26H and TRP-C28H,
Display last stored in the memory of the digital input state.

Digital Input CH1~CH16
Display last stored in the memory of the digital input counter value.
10
This feature is only available to TRP-C26H and TRP-C28H.

Submit
Save the setting value to memory.

Save
Save the setting value to external log file.

Load
Load the setting value to external log file.

Upgrade
Upgrade the TRP-C24H firmware.
4-4.Using the WEB Server mode
The Web Server can be used to configure the TRP-C24H from any web browser software (such as I.E).
In Internet Explorer type the IP Address of the TRP-C24H into the address field and press the Enter key. The
following window will appear:
Example:
If TRP-C24H IP is 192.168.1.1 Please Input the 192.168.1.1 then enters at web address, the web-page will
appear.
11
4-5 TRPCOM Test Utility
The TRPCOM test utility may help to use the debugging program development phase, the user can find this
software in our CD internal directory copied to the hard disk, and then directly execute TRPCOM.exe.
TRPCOM utility can automatically detect the model, it will list the corresponding function key,
It helps developers to understand and control the digital state.
12
5. TRP-ASCII Communication Protocol
TRP-C24H supports three modes of communication Protocol TRP-ASCII, Modbus RTU, Modbus ASCII.
TRP-ASCII Command Protocol Description
Command Format :”Leading Code”+”ID Address”+”Command”+”CHK”+(cr) .
at :”Leading Code”+”ID Address”+”Data”+”CHK”+(cr) .
How to calculate the checksum
1. Calculate all characters of the command string to get the ASCII sum, except the character return.
2. Mask the sum of string with 0FFH.
Example:
Send the command is “$06M”.
Sum of string is “$”+”0”+”6”+”M”=“24H”+”30H”+” 4D“=“A1H”……The checksum and [CHK]=“A1”.
Response string with checksum is :” A1“.
TRP-ASCII: ease of use TRP-ASCII integration to develop their own software, such as VB, VC .
Command List
Function Description
Paragraph index
%IDNNPP00DD(CHK)(cr)
Setting module configuration
See 5-1
#IDPPDD (CHK)(cr)
Digital Output Data
See 5-2
$ID6 (CHK)(cr)
Read digital input/output status
See 5-3
$IDF (CHK)(cr)
Read the module’s firmware version
See 5-4
$IDM (CHK)(cr)
Read the module’s name
See 5-5
$01RS(CHK)(cr)
Reset Module
See 5-6
~IDONN (CHK)(cr)
Change the module’s name
See 5-7
~IDLEDA(CHK)(cr)
Set the module’s LED operating mode
See 5-8
~IDWE (CHK)(cr)
Enable watchdog
See 5-9
~IDWD (CHK)(cr)
Disable watchdog
See 5-10
~IDWR (CHK)(cr)
Read watchdog status
See 5-11
~ID4V (CHK)(cr)
Read power on/Safe on mode
See 5-12
~ID5V (CHK)(cr)
Store Power on/ Save on mode
See 5-13
~**(CHK)(cr)
Read Module ID and mode name
See 5-14
#**(CHK)(cr)
Back to factory
See 5-15
13
5-1. Setting module configuration
Command
%IDNNPP00DD(CHK)(cr)
%
First leading code
ID
Address of setting module 00-FF(HEX)
NN
New address of setting from 00-FF(HEX)
PP
The Digital I/O module type define to 40
00
00
DD
Data format
CHK
Checksum
(cr)
Carriage return
!ID(CHK) (cr)
Command valid
?ID (CHK)(cr)
Command Invalid
Syntax
Description
Response
DD: Data Format
Bit
7
6
Function
0
Checksum
1:Enable
0:Disable
5
4
3
2
1
0
0
0
0
0
0
0
EX: Send command:”%0103400000”.
New ID is “03”,D I/O type is “40” ,Checksum setting disable is “00”, Response:”!01”.
14
5-2.Digital Output Data
Command
Syntax
#IDPPDD(CHK)(cr)
#
First leading code
ID
Address of setting module 00-FF(HEX)
PP
D I/O type
description
:0A/ 00
DO0~DO7 low byte data (Multi-Channel)
:0B
:1L/ AL:
high byte data D8-D15(Multi-Channel)
DO0~DO7 low byte data (Single-Channel)
L=0~7
:BL : high byte dataD8-D15(Single-Channel)
L=0~7
Response
DD
DD:00~FF (Milti-Channel) DD:00 or 01 (Single-Channel)
CHK
Checksum
(cr)
Carriage return
>(CHK)(cr)
Command valid
!ID(CHK) (cr)
?ID (CHK)(cr)
Parameter invalid (*Command data error!)
Command Invalid
*Multi-Channel mode (Output control for one BYTE)
EX: Send command :”#010A12”…..Data=”12”:DO0~DO7=“10000100”…1=Output Enable.
Response:”>”……. Command valid.
EX: Send command:”#010B34”…..Data=”34”:DO8~DO15=“110000010” …1=Output Enable.
Response:”>”……. Command valid.
EX: Send command:”#01000G”…Data=“0G”…….Data error!.
Response:”?0”…….Parameter error! .
*Single-Channel mode( Output control for one BIT)
EX: Send command:”#011001”….. Data=”01”:DO0=“1”….1=Output Enable.
Response:”>”……. Command valid.
Send command:”#011201”….. Data=“01”:DO2=“1”. ..1=Output Enable.
Response:”>”……. Command valid.
Send command:#01B301……Data=“00”:DO11=“1”... 1=Output Enable.
Response:”>”……..Command valid.
15
5-3.Read digital input/output status
Command
$ID6(CHK)(cr)
$
First leading code
ID
Address of setting module 00-FF(HEX)
6
Read digital output status
CHK
Checksum
(cr)
Carriage return
!IDLLHH(CHK)(cr)
LL=DO0~DO7 status, HH=DO8~DO15 status.
?ID(CHK) (cr)
Command Invalid
Syntax
description
Response
EX: Send command:$016…….Read digital output status .
Response:”!011234”…….DO1,DO5,DO8,DO9 Output Enable.
5-4. Read firmware version
Command
Syntax
$IDF(CHK)(cr)
$
First leading code
ID
Address of setting module 00-FF(HEX)
F
Command for reading module’s version
CHK
Checksum
(cr)
Carriage return
!IDMODDDMMYY(CHK)(cr)
MOD :The module’s model
description
Response
DD: Date
MM: Month
YY : Year
?ID(CHK)(cr)
Command Invalid
EX: Send command:$01F…Read the TRP-C24H’s version.
Response:”!01C24H090113”……. The TRP-C24H’s version date is “01/09/2013”.
16
5-5. Read the module’s name
Command
$IDM(CHK)(cr)
$
First leading code
ID
Address of setting module 00-FF(HEX)
M
Reading module’s name
CHK
Checksum
(cr)
Carriage return
!IDNNNNNNNNN(CHK)(cr)
NNNNNN :The chars from 1~9 chars
?ID(CHK)(cr)
Command Invalid
Syntax
description
Response
EX: Send command:$01M…Read the TRP-C24H’s name.
Response:”!01TRPC24H”……. The module’s name is “TRPC24H”.
5-6. Reset Module
Command
$IDRS(CHK)(cr)
$
First leading code
ID
Address of setting module 00-FF(HEX)
RS
Reset Module
(cr)
Carriage return
!ID (CHK)(cr)
Command valid
?ID(CHK)(cr)
Command Invalid
Syntax
description
Response
EX: Send Command:”$01RS”
Response:” !01”……. . Command valid!
17
5-7. Change Module ‘s name
Command
~IDONN(CHK)(cr)
~
First leading code
ID
Address of setting module 00-FF(HEX)
O
Change Module Name
NN
NN : 1~9 characters char
(cr)
Carriage return
!ID (CHK)(cr)
Command valid
?ID(CHK)(cr)
Command Invalid
Syntax
description
Response
EX: Send Command:”~01O123456789”…Change Name.
Response:” !01”……. . Command valid!
Send command:$01M…Read the TRP-C24H’s name.
Response:”!01123456789”……. The module’s name is “TRPC24H”.
5-8. Set LED operating mode
Command
Syntax description
~IDLEDA(CHK)(cr)
~
First leading code
ID
Address of setting module 00-FF(HEX)
LED
Set the module’s LED operating mode
A
A=1 Turn off all LEDS, when Output Enable= ON.
A=0 Turn on all LEDS, when Output Enable= OFF.
Response
CHK
Checksum
(cr)
Carriage return
!IDNN(CHK)(cr)
NN=ON or OFF Command valid
?ID(CHK)(cr)
Command Invalid
EX: Send command:”~01LED1”….. Turn off all LED, when Channel Enable ON.
Response:”!01OFF”……. . Command valid.
18
5-9 Enable Watchdog
Command
Syntax
~IDWE(CHK)(cr)
~
First leading code
ID
Address of setting module 00-FF(HEX)
WE
Watchdog function
CHK
Checksum
(cr)
Carriage return
!ID(CHK)(cr)
Command valid
?ID(CHK)(cr)
Command Invalid
description
Response
EX: Send Command:”~01WE”……….Enable Watchdog .
.. Response:” !01”……. Command valid.
*The user can not change the digital output state when watchdog enable,
this mode will keep until the watchdog disable.
When the watchdog enable digital output into safe mode.
There are 3 ways you can set the safe mode, command / WEB / DSM.
5-10 Disable Watchdog
Command
~IDWD(CHK)(cr)
~
First leading code
ID
Address of setting module 00-FF(HEX)
WD
Disable Watchdog
(cr)
Carriage return
!ID (CHK)(cr)
Command valid
?ID(CHK)(cr)
Command Invalid
Syntax
description
Response
EX: Send Command:”~01WD”…Watchdog Disable.
Response:” !01”……. . Command valid!
19
5-11 Read Watchdog State
Command
~IDWR(CHK)(cr)
~
First leading code
ID
Address of setting module 00-FF(HEX)
WR
Read Watchdog State
(cr)
Carriage return
!IDWN (CHK)(cr)
N=E Enable
Syntax
description
Response
N=D Disable
?ID(CHK)(cr)
Command Invalid
EX: Send Command:”~01WR”…Read Watchdog state.
Response:” !01WE”……. . Watchdog Enable.
5-12 Read Power on/Safe Mode
Command
Syntax
~ID4V(CHK)(cr)
~
First leading code
ID
Address of setting module 00-FF(HEX)
4
Read power on/safe mode status
V
V=P: Power on
description
V=S: Safe mode
Response
CHK
Checksum
(cr)
Carriage return
!IDLLHH (CHK)(cr)
HH:DO15~DO8
LL:DO7~DO0
?ID(CHK)(cr)
Command Invalid
EX: Send Command:~014P……….Read Power on output status.
.. Response:” !011234”……. . Command valid.
20
5-13 Set the digital output status Power on/Save Mode status
Command
~ID5V(CHK)(cr)
~
First leading code
ID
Address of setting module 00-FF(HEX)
5
Save the current digital output is save or power on mode
V
V=P Power on
Syntax
description
V=S Safe mode
Response
(cr)
Carriage return
!ID (CHK)(cr)
Command valid
?ID(CHK)(cr)
Command Invalid
EX: Send Command:”#010A33”…Digital output DO0~DO7= “11001100”
Send Command:”#010B17”… Digital output DO8~DOF= “10001110”
Send Command: “~015P”…….Save Power on.
Send Command:”~014P” …….Read Power on
Response:”!013317”.
21
5-14 Read Module ID and Model Name
Command
~**(CHK)(cr)
~
First leading code
**
When TCP connected, get online module ID and Model Name.
(cr)
Carriage return
!IDName (CHK)(cr)
ID: Decimal Name: Model Name.
?ID(CHK)(cr)
Command Invalid
Syntax
description
Response
EX: Send Command:”~**”… When TCP connected, get online module ID and model name.
Response:”!001TRP-C24H”.
5-15 Back to Factory
Command
#**(CHK)(cr)
#
First leading code
**
Back to factory.
(cr)
Carriage return
!ID (CHK)(cr)
Command valid
?ID(CHK)(cr)
Command Invalid
Syntax
description
Response
EX: Send Command:”~**”… Back to factory.
Response:”!01”.
22
6. Modbus RTU/ASCII Communication Protocol
* For more modbus RTU / ASCII protocol specification, please download from http://www.modbus.org website.
Obtain more modbus TCP instruction test, we recommend user can be downloaded from the following Web site
Modbus Poll Test utility http://www.modbustools.com/
Modbusscan Test utility http://www.win-tech.com/html/modbus1.htm.
User can use the virtual-com program with TRPCOM.exe for Modbus RTU test; these programs can be found in our
directory of the CD!
Install the Virtual-COM
Step 1. Insert the TRP-Serial CD and find the TRP-C24H folder.
Step 2.Click “Vcomm.exe” icon then install Virtual-COM utility.
*The Virtual COM utility support multi-language, please select which language do you need.
Step3. Click “OK” button and select “VSP run as Client support Server Device”.
Step4. Select “Create virtual serial by device scanner”, then press “OK”
23
Step5. Run VCOMM.exe then click right button select “New Virtual COM”
Step6. Select “Select Serial Port” and input TRP-C24H IP and port then press “OK”.
Step7. If Virtual-Com setting success, the display will appear bellow.
Step8.Run TRPCOM utility then select virtual-com port make a TRP-C24H command.
*If in VCOMM‘s configuration select “Boot with windows”, the virtual-com will Auto-connection when windows start.
24
* TRP-C24H in use the Virtual com mode, the default data format is 9600, N, 8,1, this mode is not allowed to
change.
25
Modbus TCP Command List
Command List
Function Description
C24H Description
ID 01 00 SS 00 NN
Read Coils
Read digital output readback value
6-1
ID 03 00 SS 00 NN
Read Holding Registers
Read the current digital output readback count value
6-2
ID 05 00 NN DD 00
Write Single Coil
Write Single channel output data
6-3
ID 0F 00 SS 00 NN 01 XX
Write Coils
Write multi channel output data
6-4
ID 06 00 SS DD NN 01 XX Write single register
Write single channel counter value
6-5
ID 16 00 SS 00 NN 01
Write multi channel counter value
6-6
Write multiple registers
Index
Additional Modbus TCP Command List
Command List
Function Description
ID 46 00 00
Read the module’s name
6-7
ID 46 04 IP 00 00 00
Setting module new ID
6-8
ID 46 07 00
Read the module’s Firmware
6-9
ID 46 0B WS 00
Enable/Disable watchdog.
6-10
ID 46 0C 00
Read watchdog status
6-11
ID 46 0D 0S 00
Set up LED ON/OFF
6-12
Index
6-1. Read Coils
Read digital output readback value
Command
Syntax
Description
Response
Error
Response
ID 01 00 SS 00 NN
ID
1Byte
Address of setting module 1~247
01
1 Byte
Function Code
00 SS
2 Bytes Start channel number, 0x0000~0x000F
00 NN
2 Bytes Output channel number,0x0001~0x0010
ID 01 BC LL HH
ID=1~247
01:Function Code
5 Bytes BC: Byte counter
LL HH: Digital output read back value
ID=1~247
81 :Function Code
ER=00 Syntax error
ID 81 ER
3 Bytes ER=01 Data Format error
ER=02 Start channel error
ER=03 I/O out of range
Example:
Send command :” 01 01 00 00 00 10”…..Read DO0~DOF Output read back value.
Response:” 01 01 02 21 43”….. 2bye,DO7~DO0=21,DOF~DO8=43.
26
6-2. Read Holding Registers
Read the current digital output readback count value
Command
Syntax
Description
Response
Error
Response
ID 03 00 SS 00 NN
ID
1Byte
Address of setting module 1~247
03
1 Byte
Function Code
00 SS
2 Bytes Start channel number, 0x0000~0x000F
00 NN
2 Bytes Output channel number,0x0001~0x0010
ID 03 BC NN NN
ID=1~247
03:Function Code
5 Bytes BC: Byte counter
NN NN: Digital output read back value
ID=1~247
83 :Function Code
ER=00 Syntax error
ID 83 ER
3 Bytes ER=01 Data Format error
ER=02 Start channel error
ER=03 I/O out of range
Example:
Send command :” 01 03 00 00 00 03 ”…..Read DO0~DO3 read back counter value.
Response:” 01 03 06 00 12 00 06 03 0A ”….. Byes Counter=6.
CH0 Counter Value=12, DO1 Counter Value=06, DO3 Counter Value=778.
6-3. Write Single Coil
Write Single channel output data
Command
Syntax
Description
Response
Error
Response
ID 05 00 SS DD 00
ID
1Byte
Address of setting module 1~247
05
1 Byte
Function Code
00 SS
2 Bytes Start channel number, 0x0000~0x000F
DD 00
2 Bytes
ID 05 00 SS DD 00
5 Bytes Command Line
Write output data DD=00 Output Disable
DD=FF Output Enable
ID=1~247
85 :Function Code
ER=00 Syntax error
ID 85 ER
3 Bytes ER=01 Data Format error
ER=02 Start channel error
ER=03 I/O out of range
Example:Send command :” 01 05 00 06 FF 00 ”…..DO6 Output Enable.
Response:” 01 05 00 06 FF 00“…Command Valid.
27
6-4. Write Coils
Write multi channel output data
Command
Syntax
Description
Response
Error
Response
ID 0F 00 SS 00 NN BC LL HH
ID
1Byte
Address of setting module 1~247
0F
1 Byte
Function Code
00 SS
2 Bytes Start channel number, 0x0000~0x000F
00 NN
2 Bytes Output channel number=0x0001~0x0010
BC
1 Bytes Byte counter
LL HH
2 Bytes
ID 0F 00 SS 00 NN
6 Bytes Command Line
Write output data LL=00~FF
HH=00~FF
ID=1~247
8F :Function Code
ER=00 Syntax error
ID 8F ER
3 Bytes ER=01 Data Format error
ER=02 Start channel error
ER=03 I/O out of range
Example:
Send command:”01 0F 00 00 00 10 02 12 34”…Output DO Data DO0~DO7=21,DO8~DOF=43,Byte Counter=02
Response:”01 0F 00 00 00 10”…Command Valid.
6-5. Write single register
Write single channel counter value
Command
Syntax
Description
ID 06 00 SS DD DD
ID
1Byte
Address of setting module 1~247
06
1 Byte
Function Code
00 SS
2 Bytes Start channel number, 0x0000~0x000F
DD DD
2 Bytes Write Counter Vaile DDDD=0x0000~0xFFFF
ID 06 00 SS DD 00
6 Bytes Command Line
Response
ID 86 :Function Code
ER=00 Syntax error
ID 86 ER (CRC)
4 Bytes
ER=01 Data Format error
ER=02 Start channel error
ER=03 I/O out of range
Example:Send command :” 01 06 00 09 1A 37 ”…..Write DO9 Counter Value=1A37.
Response:”01 06 00 09 1A 37 ”….. Command Valid.
28
6-6. Write multiple registers
Write multi channel counter value
Command
Syntax
ID 10 00 SS 00 CN BC DD DD
ID
1Byte
Address of setting module 1~247
10
1Byte
10=Function Code
00 SS
2 Bytes
Start channel number, 0x0000~0x000F
00 CN
2 Bytes
Counter Number =0x0001~0x0010
BC
1 Byte
Byte Counter
DD DD…….
2~32 Bytes
Counter Vaile DDDD=0000~FFFF
ID 10 00 SS 00 CN
6 Bytes
Command Line
Description
Response
ID 90 :Function Code
ER=00 Syntax error
ID 90 ER
3 Bytes
ER=01 Data Format error
ER=02 Start channel error
ER=03 I/O out of range
Send command:” 01 10 00 00 00 03 06 00 0A 00 14 00 1E ”… Write DO 1~3 Counter Value.
Response:”01 10 00 00 00 03”….. Command Valid.
6-7.Read the module’s name
Command
Syntax
Description
Response
ID 46 00 00
ID
Address of setting module 1~247
46
Function code
00
Read module’s name
00
Reserved code
ID 46 00 00 0C 24 00
ID 46 00 00 ….Module command Line
0C 24 :Module’s Name is C24
ID C6 00
ID C6 C6:Function Code 00: Reserved code
EX: Send Command:”01 46 00 00”…….Read the TRP-C24’s name.
Response:”01 46 00 00 0C 24 00 “……Module’s name is C24.
Error Response: “01 C6 00”……Error code.
29
6-8. Setting module new ID
Command
ID 46 04 IP 00 00 00
ID
Address of setting module 1~247
46
Function Code
04
Setting module ID
IP
New module’s ID
00 00 00
Reserved code
ID 46 04 00 00
ID 46 04 00 00 ….Command valid
ID C6 00
ID C6 C6:Function Code 00: Reserved code
Syntax
Description
Response
EX: Send Command:”01 46 04 08 00 00 00”…….Set up the new ID is “03”.
Response:”01 46 04 00 00 “……New ID is 08.
Error Response: “01 C6 00”……Error code.
6-9.Read the module’s Firmware
Command
Syntax
Description
ID 46 07 00
ID
Address of setting module 1~247
46
Function Code
07
Read module’s Firmware
00
Reserved code
ID 46 07 YY MM DD 00
ID 46 07 ……Module command Line
YY:Year MM :Month DD:Date
00 : Reserved code
Response
ID C6 00
ID C6 C6:Function Code 00: Reserved code
Example:
Send Command:”01 46 07 00”…….Read Firmware Version.
Response:”01 46 07 13 01 10 00“…Firmware Version 01/10/2013.
Error Response: “01 C6 00”……Error code.
30
6-10.Enable/Disable watchdog
Command
ID 46 0B WS 00
ID
Address of setting module 1~247
46
Function Code
0B
Setting Watchdog Status
WS
WS=00 Watchdog Disable
WS=01 Watchdog Enable
00
Reserved code
ID 46 0B 00
00 ID 46 0B 00 ……Command valid
ID C6 00
ID C6 C6:Function Code 00: Reserved code
Syntax
Description
Response
Example:
Send Command:”01 46 0B 01 00”…….Watchdog Enable.
Response:”01 46 0B 00“…Command valid.
Error Response: “01 C6 00”……Error code.
6-11.Read watchdog status
Command
Syntax
Description
Response
ID 46 0C 00
ID
Address of setting module 1~247
46
Function Code
0C
Read watchdog status
00
Reserved code
ID 46 0C WT
ID 46 0C ……Module command line
WT=00 Watchdog Disable
WT=01 Watchdog Enable
ID C6 00
ID C6 C6:Function Code 00: Reserved code
Example:
Send Command:”01 46 0C 00”…Read watchdog status.
Response:”01 46 0C 01 ….Watchdog enable.
Error Response: “01 C6 00”…Error code.
31
6-12.Set up LED ON/OFF
Command
Syntax
ID 46 0D 0S 00
ID
Address of setting module 1~247
46
Function Code
0D
Set Up LED Status Value
0S
S = 0 Turn on all LED when DIO enable off
S = 1 Turn off all LED when DIO enable on
00
Reserved code
ID 46 0D 00
ID 46 0D ……Command valid
ID C6 00
ID C6 C6:Function Code 00: Reserved code
Description
Response
Example:
Send Command:”01 46 0D 01 00.
Response:”01 46 0D 00.
Error Response: “01 C6 00”…Error code.
7. Pair Mode
TRP-C24H support pairing mode with the TRP-C26H, Applied to 16 digital channels input and 16 digital output with
over the network, without any driver with computer hardware.
All digital LED flashes in pairing mode until successfully paired will stop blinking; TRP-C24H sustained in connection
automatically, regardless of any party the power to re-open or network disconnection to ensure normal transmission.
product application are as follows:
32
7-1 Parameter setting example
Perform DSM utility to change the parameters

TRP-C24H parameter setting
33

TRP-C26H parameter setting
34
8. Application
35