Download Benchmark 2500 - 3000 Boilers
Transcript
Benchmark 2500 - 3000 Boilers CHAPTER 10. BOILER SEQUENCING TECHNOLOGY 10.3.3 Option 3 - Outdoor Reset with DIRECT WIRED Header Sensor AND DIRECT WIRED Outdoor Sensor NOTE: Both Header Sensor AND Outdoor Sensor must be wired. See the C-More Controller User Manual, OMM-0032, GF-112 and ProtoNode User Manual, OMM-0080, GF-129 for more information. Step 1 - Direct Wired Header Sensor Wiring 1. On the MASTER Unit, connect the Header Temperature Sensor (AERCO PN 61040) to the Feed Forward (FFWD) terminals on the P-1 Harness Via the terminal block labeled “Header Temp sensor” in the I/O Box. NOTES: The header sensor must be installed between 2 and 10 feet downstream of the LAST boiler in the plant’s supply water header. Shielded pair 18 - 22 AWG cable is recommended for header sensor wiring. There is no polarity to be observed. The ground for the shield is at the “SHLD” terminal in the I/O the Box. The sensor end of the shield must be left free and ungrounded. Temp Sensor PN 61040 Header Temp Sensor I/O Box Step 2 - Direct Wired Outdoor Sensor 1. On the MASTER Unit, Connect the Outdoor Temperature Sensor (AERCO PN 123525) to the “OUT” and “COM” terminals in the I/O Box. NOTES: • Twisted shielded pair 18 - 22 AWG cable is recommended for header sensor wiring. There is no polarity to be observed. The ground for the shield is at the “SHLD” terminal in the I/O the Box. The sensor end of the shield must be left free and ungrounded. • When mounting the Outdoor sensor, it must be located on the North side of the building where an average outside air temperature is expected. The sensor must be shielded from direct sunlight as well as impingement by the elements. The outdoor sensor may be wired up to 200 feet from the boiler. Temp Sensor PN 123525 OMM-0094_0E GF-137 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Ph.: 800-526-0288 Page 123 of 204 03/20/2014