ROC300 Protocol Emulation Program User Manual
Point Type 1: Discrete Input
Parm
#
ReadWrite
Data Type
Length
3 (cont’d)
ROC800 Point
Type
ROC800 Parameter
Bit 2 – Filter Interval
0 = 250 ms (50 ms for
built-in DI) – ROC300series & FloBoss 407
0 = 100 ms – FloBoss
500-series, FloBoss
103, & RegFlo
1 = 15 seconds (3 sec
for built-in DI)
N/A
N/A
Bit 1 – Latch Enable
0 = Disable
1 = Enable
101
5
Full
Bit 0 – Invert Enable
0 = Disabled
1 = Enable
101
4
Full
Alarm Code
Bit 7 – Manual Mode
Bit 6 – Not Used
Bit 5 – Status Change
Bit 4 – TDI Rate Alarm
Bit 3 – TDI High Alarm
Bit 2 – TDI High High
Alarm
Bit 1 – TDI Low Alarm
Bit 0 – TDI Low Low
Alarm
101
12
Partial – Bits 7 and 5 are
supported; all others are set to
0
Description
Support
None – returns 0
4
R/O
BIN
1
5
R/W
UINT 32
4
Accumulated Value
101
6
Full
6
R/W
UINT 32
4
On Counter
101
7
Partial – ROC800 On Time in
seconds (FLP) converts to 50
ms periods (UINT32)
7
R/W
UINT 32
4
Off Counter
101
8
Partial – ROC800 Off Time in
seconds (FLP) converts to 50
ms periods (UINT32)
8
R/W
INT 16
2
0% Pulse Width
N/A
N/A
None – returns 0
9
R/W
INT 16
2
100% Pulse Width
N/A
N/A
None – returns 0
10
R/W
UINT 16
2
Max time between pulses /
Max Count
N/A
N/A
None – returns 0