Download Form A6188 - Well Control User Program

Transcript
ROC300 Protocol Emulation Program User Manual
4.2.7
Point Type 7: AGA Flow Parameters
Point Type 7: AGA Flow Parameters
Parm
#
ReadWrite
Data Type
Length
0
R/W
AC
10
Point Tag Identification
1
R/W
FLP
4
2
R/W
FLP
3
R/W
BIN
ROC800 Point
Type
ROC800 Parameter
113/115
0/0
Full
Latitude
112
20
Full
4
Elevation
112
19
Full
1
Calculation Method
N/A
N/A
None – returns 0
Bit 6 – RBX Set
0 = Disabled
1 = Active
113/115
6/5
Full
Bit 5 – RBX on Clear
0 = Disabled
1 = Active
113/115
5/4
Full
Bit 4 – ALM Enable
0 = Disabled
1 = Log Alarms
113/115
4/3
Full
Bit 3 – US or Metric
0 = US Units
1 = Metric Units
112
4
Full
Bit 2 – AGA3 Algorithm
0 = 1985 Algorithm
1 = 1992 Algorithm
112
2
Partial –always returns 1
Bit 1 – Flow Calculation
Method
0 = AGA3
1 = AGA7
N/A
N/A
Partial – Fills requests for
logical instances of AGA points
with orifice points first, and
then turbine points, so this is
R/O
Bit 0 – Compressibility
Method
0 = NX19
1 = AGA8
N/A
N/A
Partial – always returns 1
Description
Support
Bit 7 – Manual Mode
0 = Normal
1 = Manual
Rev. Jan-09
33