3 - Product coding
3.2
CONFIGURATION CODING
The configuration code consists of
4 digits that identify the operating characteristic of the controller,
as chosen by the user.
Section 4.5 at pag. 26 reports the
instructions how to set a new configuration code.
I L M N
Input type and range
TR Pt100 IEC751
TR Pt100 IEC751
TC L Fe-Const DIN43710
TC J Fe-Cu45% Ni IEC584
TC T Cu-CuNi
TC K Cromel -Alumel IEC584
TC S Pt10%Rh-Pt IEC584
DC input 0…50 mV, linear
DC input 10…50 mV, linear
Custom input and range
Control mode
2002
P.I.D.
On - Off
2 alarms
indicator
The configuration code can be displayed on the front panel, following the instructions at pag 19 section 4.2.2.
16
-99.9…300.0 °C
-200…600 °C
0…600 °C
0…600 °C
-200 …400 °C
0…1200 °C
0…1600 °C
engineering units
engineering units
-99.9…572.9 °F
-328…1112 °F
32…1112 °F
32…1112 °F
-328…752 °F
32…2192 °F
32…2912 °F
Output configuration
Control OP1 / alarm AL2 on OP2
Control OP2 / alarm AL2 on OP1
Control OP1 / alarm AL2 on OP2
Control OP2 / alarm AL2 on OP1
Alarm AL1 on OP1/ alarm AL2 on OP2
Alarm AL1 on OP2/ alarm AL2 on OP1
Type of control and safety
Reverse (AL1 active low)
Direct (AL1 active high)
Reverse (AL1 active low)
Direct (AL1 active high)
Safety 0%
Safety 0%
Safety 100%
Safety 100%
I
0
1
2
3
4
5
6
7
8
9
L
0
1
2
3
4
5
M
0
1
2
3