REPORT
Reference
2013-06-11 3P03701
Page
2 (22)
controller to different valules, thus resulting in testing the unit at heating capacity less than the
unit’s maximum capacity.
The Combi Control unit was placed in the calorimeter chamber in various positions (both
positions in accordance to the user guide and positions not following the instructions in the
user guide) and the heat pump was supervised as it reacted to the Combi Control’s controlling
commands.
The Combi Control app was installed on a mobile phone using Android.
Direct commands to the Combi Control unit was sent both from an Android mobile phone as
well as an iOS mobile phone.
Installation and configuration
The installation of the SIM-card and installation of the app on the Android mobile phone was
performed by following the instructions in the Quick start guide, found here:
http://combicontrol.net/wp-content/uploads/2012/05/Combi-quick-setup.pdf
The Combi Control app version used was 1.0.33. The app was downloaded on the 6th of May
2013.
The operation of the app and SMS-commands was performed in accordance to descriptions in
the user manual, found here:
http://combicontrol.net/wp-content/uploads/2012/05/cc_manual_web_eng_fin_swe_nok_4.pdf
Equipment
Calorimeter chamber, LL1
Outdoor climate chamber, LV2
Electrical power meters, Inv. Nr. 200452, 200453, 202655
Data logging equipment, Inv. Nr. 201553, 202681
Air temperature sensors, Pt 100 and thermocouple
Heat pump, Toshiba. Indoor unit model no.: RAS-25N3KVP-ND. Outdoor unit model no.:
RAS-25N3AVP-ND
Mobile phone HTC One S
Mobile phone iPhone 4
Uncertainty of measurement
The results from the test are based on measurements. The total uncertainty of measurement of
the results in the report has been calculated in accordance with the following estimates of
uncertainties of measurement and calculation. The estimates are those of the total
uncertainties, including both systematic and random uncertainties.
Temperatures, test points
Tvbin_m
Thermocouple
± 0.2 K
± 1.0 K
Other quantities
PEvpa
± 0,5 %
SP Technical Research Institute of Sweden