3.5.3 Setup Relay (Sub Menu 1)
• Set parameters for each Relay.
(Security level 2)
R#XX
0
ON OFF
s 01 s 01
⇔⇐
Next Relay
Window Setup Relay legend
Symbol
R#XX
1
Describtion
Function
Relay number (1 to max. 181)
Dependent on the configuration of the System.
Set Relay Mode
Symbol
Set Mode
Function
0 0=
1 1=
0
Relay Mode de-energized
Relay Mode energized (fail-safe)
Selected the operating mode for each relay
Set delay Time for ON and OFF
Symbol
ON s 1
OFF s 1
Set Time
Function
1 to 9999 ON = Delay Time ON (sec.)
1 to 9999 OFF = Delay Time OFF (sec.)
Set the delay Time for each relay
Example:
Relay 2 with Delay Time ON and OFF
Med ON
alarm OFF
Relay 2
Display
Status
Relay 2
ON
Gas Concentration -larger
Delay
Time ON
- smaller then Threshold
Delay
Time OFF
OFF
0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0
