User Manual - PolyGard® MGC - _ _ _ - _ _ -US Page 21 3.5.3 Setup Relay (Sub Menu 1) • Set parameters for each Relay. (Security level 2) R#XX 0 ON OFF s 01 s 01 ⇔⇐ Next Relay Window Setup Relay legend Symbol R#XX 1 Describtion Function Relay number (1 to max. 181) Dependent on the configuration of the System. Set Relay Mode Symbol Set Mode Function 0 0= 1 1= 0 Relay Mode de-energized Relay Mode energized (fail-safe) Selected the operating mode for each relay Set delay Time for ON and OFF Symbol ON s 1 OFF s 1 Set Time Function 1 to 9999 ON = Delay Time ON (sec.) 1 to 9999 OFF = Delay Time OFF (sec.) Set the delay Time for each relay Example: Relay 2 with Delay Time ON and OFF Med ON alarm OFF Relay 2 Display Status Relay 2 ON Gas Concentration -larger Delay Time ON - smaller then Threshold Delay Time OFF OFF 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 PolyGard is a registered trademark of MSR Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com GAMGC_01US Specification subject to change without notice. Printed in USA 030918