Important Safety Instructions This manual contains important instructions that should be closely followed during installation and maintenance of this unit. Read all safety and operating instructions before attempting to operate the MicroDC. Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions. This product is designed for commercial / industrial use only. This product is not intended for use with life support. Maximum heat load or weight load must not exceed those shown on the rating label. Operate this product in an indoor environment at an ambient temperature of 00°C to 60°C with a relative humidity of 20% to 85% (no condensing). Install in a clean environment, free from dust, moisture, flammable liquids, gases, and corrosive substances. Where applicable, this product must be permanently connected and powered from a suitable single-phase AC supply rated in accordance with the equipment data plate. It must be suitably grounded and protected by a circuit breaker or fuse. A residual current device (commonly known as differential relay) must be present in order to protect any engineer while installing, maintaining or operating the MicroDC. Ensure the MicroDC has proper ventilation. Never block or insert objects into the ventilation holes or other openings. Maintain a minimum clearance of 500mm in front, rear and top of the MicroDC for proper air flow and cooling. www.canovate.com l [email protected] l P. +90 216 484 2222 Technical Manual of Micro Data Center l 7