WLDR ReferenceBook Page 25 Thursday, April 5, 2001 3:36 PM WindLDR™ Reference Manual 9-25 Timer Circuit The preset value 0 – 9999 can be designated using a data register D0 – D99 in the standard mode or D0 – D31 in the high-speed mode. When a data register is used, the information in the data register becomes the preset value. Enter the TIM, TMH, or TMS instruction with the two required addresses. Then, enter the output (OUT) instruction. 100 msec Timer (TIM) I1 • • • • • • T5 D10 Q0 Countdown from the preset value is initiated when the operation results directly before the timer input is on. The timer output turns on when the timed value reaches zero. The timed value returns to the preset value when the timer input is off. The same timer or counter number cannot be programmed more than once. In this event, an error message will result. Timer preset values can be changed without transferring the entire program to the PLC base unit again. If the timer preset value is changed during timedown, the timer remains unchanged for one cycle. The change will be reflected in the next cycle. If the timer preset value is changed to zero, then the timer stops operation and the timer output is turned on immediately. © 2001 IDEC Corporation 9. Editing the Ladder