PowerFlex® DC TECHNICAL DATA DIGITAL DC DRIVE PowerFlex DC Technical Data 2 PowerFlex DC Technical Data Product Description The PowerFlex Digital DC drive provides digital control for precise speed and current regulation, easy programmability, extensive diagnostics, non-regenerative and regenerative operation, and is easily interfaced for integration into larger drive systems. PowerFlex DC drives are well suited to a variety of applications including extruding operations, finishing, drawing, and coating processes, applications exhibiting shock loads, high inertia, rapid accel/decel or continuous regeneration, and is an excellent choice for existing DC machinery upgrades. The compact design of this drive includes a fully contained power module and a common control structure for the entire range of horsepower. And, to make connectivity even easier, the PowerFlex DC drive provides a standard DPI interface that is compatible with all PowerFlex DPI communication products. The standard hardware offering consists of an open type enclosure, armature converter, regulated field converter for field weakening or economy applications, an advanced regulator with integrated DPI functionality, DC tachometer and encoder capability. Table of Contents Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page Standard Drives Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Catalog Number Explanation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Standard Drives Product Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 User Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Installation Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Parameter List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 PowerFlex DC Configured Drives . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Watts Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Reference Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 3 PowerFlex DC Technical Data Standard Drives Program Packaging and Mounting • IP20, Nema/UL Type Open - For conventional mounting inside or outside a control cabinet. Easy to Use Communication Tools The PowerFlex Digital DC drive provides common communication tools that are familiar and easy to use, including the LCD Human Interface Module (HIM) and PC-based configuration tools. • The LCD HIM provides: - Large and easy to read 7 line x 21 character, backlit display Alternate function keys for shortcuts to common tasks “Calculator-like” number pad for fast and easy data entry (Full Numeric version only) Control keys for local start, stop, speed, and direction Remote versions for panel mount applications • PC-based Configuration tools include: - DriveExplorer™ and DriveExplorer Lite (v5.02 or higher). A simple and flexible “On-line” tool for monitoring and configuring while connected to a drive. - DriveTools™ SP (v4.01 or higher is required with a PowerFlex DC drive specific software patch. The patch can be downloaded from http://www.ab.com/support/abdrives/webupdate/). A suite of software tools which provide an intuitive means for programming, troubleshooting and maintaining Allen-Bradley drives, including the PowerFlex DC Drive Start-Up Wizard. • Internal Communications allow you to integrate the drive into the manufacturing process. Status indicators for all internal communication options are visible on the cover for easy setup and monitoring of drive communications. You can easily manage information from “shop floor to top floor” and seamlessly integrate a complete system as you control, configure and collect data. 4 PowerFlex DC Technical Data Drive Features • Fast-acting Current Limit and Voltage Regulation result in maximum accel/decel without tripping. • High speed analog inputs improve drive response to torque or speed commands. • Programming flexibility allows parameters to be linked within the drive. • Field flashable firmware through DPI interface. • Flying Start delivers smooth and instantaneous connection into rotating loads, regardless of commanded direction, without the need for any speed feedback. • Single Phase Regulated Field supply (10, 14, & 20A) standard on all frames. • Integral Process PI Control can eliminate the need for a separate process loop controller. • Speed Regulation - Open Loop or Closed Loop - Armature Feedback provides a 2000:1 rpm speed range - DC Tachometer Feedback provides up to 0.1% speed regulation - Encoder Feedback provides up to 0.1% speed regulation for the tightest application requirements. • Torque Regulation - Open Loop or Closed Loop - Open Loop torque regulation provides ±5% regulation. - Encoder Feedback provides ±2% regulation and the ability to hold full load at zero speed. Unsurpassed Capability in Network Communications ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ RS485 DF1 Remote I/O PROFIBUS™ Interbus™ EtherNet/IP™ DeviceNet™ ControlNet™ PowerFlex drives are fully compatible with the wide variety of Allen-Bradley DPI™ communication adapters, offering the following benefits: Description (Unconnected Messaging) permits other network devices (e.g. PanelView™) to communicate directly to a drive without routing the communication through the network scanner. ✔ Adapter Routing - Plug PC into one drive and talk to all other Allen-Bradley drives on same network, without being routed through network scanner. ✔ ✔ ✔ ✔ Access to 100% of all parameters over the network. ✔ AutoBaud capability makes initial connections less problematic. Change of State significantly reduces network traffic by configuring control messages to be sent only upon customer defined states. Very flexible configuration for each node (Example: “reference must change by more than 5%”). Peer Control provides master-slave type control between drives, where one or more slave drives (consumers) can run based on the status of a master drive (producer), which can also significantly reduce network traffic. ADR (Automatic Device Replacement) saves significant time and effort when replacing a drive, by allowing the scanner to be configured to automatically detect a new drive and download the required parameter settings. ✔ ✔ ✔ ✔ Flexible Fault Configuration - Adapters can be programmed to take fault based actions as ramp to stop, coast-to-stop and hold last state, as well as send user configurable logic control and speed reference values. In addition, different actions can be taken based on whether the network experienced a serious problem (broken cable etc.) versus network idle condition (PLC set to “Program”). 5 PowerFlex DC Technical Data Catalog Number Explanation Position 1-3 4 5 6 7 8-10 11 12 13 14 15 16 20P 4 1 A D 4P1 R A 0 N N N a b c d e f g h i j k l a f1 g Drive 230V, 60 Hz Input Field Supply Code Type 20P PowerFlex DC Code b Motor Operation Hp Armature Frame Amps Field Amps Code A Type Three-Phase Regulated 7P0 1.5 7 A 10 9P0 2 9 A 10 012 3 12 A 10 020 5 20 A 10 029 7.5 29 A 10 038 10 38 A 10 h Packaging/Documentation F R Fixed Field w/Economy Single-Phase Regulated This option is currently not available. Code Type 2 Two Quadrant Operation (Non-Regen) 055 15 55 A 10 4 Four Quadrant Operation (Regen) 073 20 73 A 14 Code 093 25 93 A 14 0 110 30 110 A 14 c 146 40 146 B 20 N Yes No Input Type 180 50 180 B 20 Q No Yes This option is currently not available. Code Type 218 60 218 B 20 1 6 Pulse 265 75 265 B 20 12 Pulse 360 100 360 B 20 434 125 434 B 20 521 150 521 C 20 2 This option is currently not available. d Code Enclosure Rating Conform. Coat A IP20, NEMA/UL Type Open No Code Hp IP43, NEMA/UL Type 1 Filter No 4P1 2 4.1 A 10 6P0 3 6 A 10 G IP54, NEMA/UL Type 12 No 010 5 10 A 10 H IP54, NEMA/UL Type 12 Fan/Filter No 014 7.5 14 A 10 N IP00, NEMA/UL Type Open No 019 10 19 A 10 027 15 27 A 10 035 20 35 A 10 045 25 45 A 10 052 30 52 A 10 e 073 40 73 A 14 Input Voltage 086 50 86 A 14 14 B This option is currently not available. User Manual No No Yes Yes i HIM Code Operator Interface 0 Blank Cover Standard - For additional selections refer to User Installed Options. f2 Enclosure A Shipping Carton 460V, 60 Hz Input Armature Frame Amps j Field Amps I/O Options Code Control A‡ I/O Expansion Card (4 Additional 24V DC Digital Inputs & Outputs, 2 Analog Outputs) B‡ 115V AC Conversion Card (8 Digital Inputs & Outputs) C‡ I/O Expansion Card + 115V AC Conversion N‡ None (8 - 24V DC Digital Inputs & Outputs, 3 Analog Outputs and 2 Analog Inputs are Standard) ‡ Available only as a User Installed option. Code Voltage 100 60 100 A B 230V AC 129 75 129 A 14 k 400V AC 167 100 167 B 20 Communication Options C 460V AC 207 125 207 B 20 Code Description E D 600V AC 250 150 250 B 20 N None F 690V AC 330 200 330 B 20 412 250 412 B 20 495 300 495 C 20 667 400 667 C 20 This option is currently not available. Standard - for additional selections, refer to User Installed Options. l Cabinet Options 6 Code Type N None PowerFlex DC Technical Data Standard Drives Product Selection IP20, NEMA/UL Type Open (Position d = A) All drives are rated 150% overload for 60 seconds, 200% for three seconds. 230V AC, Three-Phase Drive Output Rating Normal Duty kW Normal Duty HP 1.2 1.5 1.5 2 2.2 3 3.7 5 5.5 7.5 7.5 10 11 15 15 20 18.5 25 22 30 30 40 37 50 45 60 56 75 75 100 93 125 112 150 Amps 7 9 12 20 29 38 55 73 93 110 146 180 218 265 360 434 521 Non-Regenerative Drives Cat. No. 20P21AB7P0RA0NNN 20P21AB9P0RA0NNN 20P21AB012RA0NNN 20P21AB020RA0NNN 20P21AB029RA0NNN 20P21AB038RA0NNN 20P21AB055RA0NNN 20P21AB073RA0NNN 20P21AB093RA0NNN 20P21AB110RA0NNN 20P21AB146RA0NNN 20P21AB180RA0NNN 20P21AB218RA0NNN 20P21AB265RA0NNN 20P21AB360RA0NNN 20P21AB434RA0NNN 20P21AB521RA0NNN Regenerative Drives Cat. No. 20P41AB7P0RA0NNN 20P41AB9P0RA0NNN 20P41AB012RA0NNN 20P41AB020RA0NNN 20P41AB029RA0NNN 20P41AB038RA0NNN 20P41AB055RA0NNN 20P41AB073RA0NNN 20P41AB093RA0NNN 20P41AB110RA0NNN 20P41AB146RA0NNN 20P41AB180RA0NNN 20P41AB218RA0NNN 20P41AB265RA0NNN 20P41AB360RA0NNN 20P41AB434RA0NNN 20P41AB521RA0NNN Frame Size A A A A A A A A A A B B B B B B C Amps 4.1 6 10 14 19 27 35 45 52 73 86 100 129 167 207 250 330 412 495 667 Non-Regenerative Drives Cat. No. 20P21AD4P1RA0NNN 20P21AD6P0RA0NNN 20P21AD010RA0NNN 20P21AD014RA0NNN 20P21AD019RA0NNN 20P21AD027RA0NNN 20P21AD035RA0NNN 20P21AD045RA0NNN 20P21AD052RA0NNN 20P21AD073RA0NNN 20P21AD086RA0NNN 20P21AD100RA0NNN 20P21AD129RA0NNN 20P21AD167RA0NNN 20P21AD207RA0NNN 20P21AD250RA0NNN 20P21AD330RA0NNN 20P21AD412RA0NNN 20P21AD495RA0NNN 20P21AD667RA0NNN Regenerative Drives Cat. No. 20P41AD4P1RA0NNN 20P41AD6P0RA0NNN 20P41AD010RA0NNN 20P41AD014RA0NNN 20P41AD019RA0NNN 20P41AD027RA0NNN 20P41AD035RA0NNN 20P41AD045RA0NNN 20P41AD052RA0NNN 20P41AD073RA0NNN 20P41AD086RA0NNN 20P41AD100RA0NNN 20P41AD129RA0NNN 20P41AD167RA0NNN 20P41AD207RA0NNN 20P41AD250RA0NNN 20P41AD330RA0NNN 20P41AD412RA0NNN 20P41AD495RA0NNN 20P41AD667RA0NNN Frame Size A A A A A A A A A A A A A B B B B B C C 460V AC, Three-Phase Drive Output Rating Normal Duty kW Normal Duty HP 1.5 2 2.2 3 3.7 5 5.5 7.5 7.5 10 11 15 15 20 18.5 25 22 30 30 40 37 50 45 60 56 75 75 100 93 125 112 150 149 200 187 250 224 300 298 400 7 PowerFlex DC Technical Data Factory Installed Options Each PowerFlex DC drive includes one encoder and DC analog tachometer input. No other factory installed options are available at this time. User Installed Options Human Interface and Wireless Interface Modules No HIM (Blank Plate) 20-HIM-A0 LCD Display, Full Numeric Keypad 20-HIM-A3 LCD Display, Programmer Only 20-HIM-A5 Remote (Panel Mount) LCD Display, Full Numeric Keypad 20-HIM-C3S Remote (Panel Mount) LCD Display, Programmer Only 20-HIM-C5S Remote (Panel Mount) Wireless Interface Module 20-WIM-N4S Handheld/Local (Drive Mount) Remote (Panel Mount) IP66, NEMA/UL Type 4x/12 Wireless Interface Module 20-WIM-N1 Human Interface Module Accessories Description Bezel Kit for LCD HIMs, NEMA/UL Type 1 Cat. No. ‡ 20-HIM-B1 ♣ Cat. No. Cat. No. No HIM (Blank Plate) 20-HIM-A0 – LCD Display, Full Numeric Keypad 20-HIM-A3 20-HIM-C3S ‡ 0.33 Meters (1.1 Feet) 1202-H03 LCD Display, Programmer Only 20-HIM-A5 20-HIM-C5S ‡ 1 Meter (3.3 Feet) 1202-H10 Wireless Interface Module 20-WIM-N1 3 Meter (9.8 Feet) 1202-H30 9 Meter (29.5 Feet) 1202-H90 Description 20-WIM-N4S For indoor use only. ‡ Includes a 1202-C30 interface cable (3 meters) for connection to drive. PowerFlex HIM Interface Cable, 1 m (39 in) 20-HIM-H10 Cable Kit (Male-Female) DPI/SCANport™ One to Two Port Splitter Cable 1203-S03 ‡ Includes a 1202-C30 interface cable (3 meters) for connection to drive. ♣ Required only when HIM is used as handheld or remote. Required in addition to 20-HIM-H10 for distances up to a total maximum of 10 Meters (32.8 Feet). I/O Option Kit Description 8 Cat. No. I/O Expansion board 20P-S5V62 115V ac to 24V dc 8 Channel I/O Converter Board 20P-S520L PowerFlex DC Technical Data User Installed Options, Continued Communication Option Kits PC Programming Software Description ® Cat. No. MS/TP RS485 Communication Adapter Description 20-COMM-B DriveTools™ SP Software ControlNet™ Communication Adapter (Coax) 20-COMM-C DriveExplorer™ Software (Lite/Full) Pocket DriveExplorer™ Software BACnet DeviceNet™ Communication Adapter 20-COMM-D EtherNet/IP™ Communication Adapter 20-COMM-E HVAC Communication Adapter 20-COMM-H Interbus™ Communication Adapter 20-COMM-I PROFIBUS™ DP Communication Adapter 20-COMM-P ControlNet™ Communication Adapter (Fiber) 20-COMM-Q Remote I/O Communication Adapter 20-COMM-R RS485 DF1 Communication Adapter 20-COMM-S External Communications Kit Power Supply 20-XCOMMAC-PS1 DPI External Communications Kit 20-XCOMMDC-BASE External DPI I/O Option Board 20-XCOMMIO-OPT1 Compact I/O to DPI/SCANport Module 1769-SM1 Serial Null Modem Adapter 1203-SNM Smart Self-powered Serial Converter (RS232) includes 1203-SFC and 1202-C10 Cables 1203-SSS Universal Serial Bus™ (USB) Converter includes 2m USB, 20-HIM-H10 & 22-HIM-H10 Cables 1203-USB See publication 9303-PL002… for ordering/pricing information. Set-up wizards are available for use with DriveTools SP and DriveExplorer (Lite/Full) only. DriveExplorer Lite is available for free download at: http://www.ab.com/drives/driveexplorer/free_download.html For use only with External DPI Communications Kits 20-XCOMM-DCBASE. Only ModBus RTU can be used with Vector Control. Isolation Transformers Isolation Transformers are available for installations that have specific types of AC supply configurations or require drive protection due to AC line disturbances. Drive output Rating kW (HP) 1.2 - 2.2 (1.5 - 3) 3.7 (5) 5.5 (7.5) 7.5 (10) 11 (15) 15 (20) 18.5 (25) 22 (30) 30 (40) 37 (50) 45 (60) 56 (75) 75 (100) 93 (125) 112 (150) 145 (200) 187 (250) 224 (300) 298 (400) 373 (500) 448 (600) 522 (700) 597 (800) Transformer Output Rating kVA 5 7.5 11 14 20 27 34 40 51 63 75 93 118 145 175 220 275 330 440 550 660 770 880 230V AC Three Phase Primary Voltage 230V AC Secondary 460V AC Secondary Catalog Number Catalog Number 1321-3TW005-AA 1321-3TW005-AB 1321-3TW007-AA 1321-3TW007-AB 1321-3TW011-AA 1321-3TW011-AB 1321-3TW014-AA 1321-3TW014-AB 1321-3TW020-AA 1321-3TW020-AB 1321-3TW027-AA 1321-3TW027-AB 1321-3TW034-AA 1321-3TW034-AB 1321-3TW040-AA 1321-3TW040-AB 1321-3TW051-AA 1321-3TW051-AB 1321-3TH063-AA 1321-3TH063-AB 1321-3TH075-AA 1321-3TH075-AB 1321-3TH093-AA 1321-3TH093-AB 1321-3TH118-AA 1321-3TH118-AB 1321-3TH145-AA 1321-3TH145-AB 1321-3TH175-AA 1321-3TH175-AB 1321-3TH220-AA 1321-3TH220-AB 1321-3TH275-AA 1321-3TH275-AB 1321-3TH330-AA 1321-3TH330-AB — 1321-3TH440-AB — 1321-3TH550-AB — 1321-3TH660-AB 1321-3TH770-AB 1321-3TH880-AB 460V AC Three Phase Primary Voltage 230V AC Secondary 460V AC Secondary Catalog Number Catalog Number 1321-3TW005-BA 1321-3TW005-BB 1321-3TW007-BA 1321-3TW007-BB 1321-3TW011-BA 1321-3TW011-BB 1321-3TW014-BA 1321-3TW014-BB 1321-3TW020-BA 1321-3TW020-BB 1321-3TW027-BA 1321-3TW027-BB 1321-3TW034-BA 1321-3TW034-BB 1321-3TW040-BA 1321-3TW040-BB 1321-3TW051-BA 1321-3TW051-BB 1321-3TH063-BA 1321-3TH063-BB 1321-3TH075-BA 1321-3TH075-BB 1321-3TH093-BA 1321-3TH093-BB 1321-3TH118-BA 1321-3TH118-BB 1321-3TH145-BA 1321-3TH145-BB 1321-3TH175-BA 1321-3TH175-BB 1321-3TH220-BA 1321-3TH220-BB 1321-3TH275-BA 1321-3TH275-BB 1321-3TH330-BA 1321-3TH330-BB — 1321-3TH440-BB — 1321-3TH550-BB — 1321-3TH660-BB — 1321-3TH770-BB — 1321-3TH880-BB 9 PowerFlex DC Technical Data AC Input Line Reactors and Contactors If a DC Contactor is used, an AC Input contactor is not needed. 230V AC Input, Regenerative Drives Drive Cat. No. 20P-41AB7P0 20P-41AB9P0 20P-41AB012 20P-41AB020 20P-41AB029 20P-41AB038 20P-41AB055 20P-41AB073 20P-41AB093 20P-41AB110 20P-41AB146 20P-41AB180 20P-41AB218 20P-41AB265 20P-41AB360 20P-41AB434 20P-41AB521 AC Line DC Amps Amps 7 5.7 9 7.4 12 9.8 20 16 29 24 38 31 55 45 73 60 93 76 110 90 146 119 180 147 218 178 265 217 360 294 434 355 521 426 HP 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 IP00 (Open Style) Line Reactor Cat No. 1321-3R8-A 1321-3R12-A 1321-3R18-A 1321-3R18-A 1321-3R55-A 1321-3R55-A 1321-3R55-A 1321-3R80-A 1321-3R100-A 1321-3R100-A 1321-3R160-A 1321-3R160-A 1321-3RB250-A 1321-3RB250-A 1321-3RB320-A 1321-3RB400-A 1321-3R500-A Line Reactor kW (HP) .75 (1) 1.49 (2) 0.75-3.7 (1-5) 0.75-3.7 (1-5) 5.5-11 (7.5-15) 5.5-11 (7.5-15) 5.5-11 (7.5-15) 15 (20) 18.5-22 (25-30) 18.5-22 (25-30) 30-37 (40-50) 30-37 (40-50) 45-56 (60-75) 45-56 (60-75) 75 (100) 93 (125) 112 (150) AC Input Contactor Cat. No. 100-C12D10 100-C12D10 100-C12D10 100-C23D10 100-C30D10 100-C37D10 100-C60D10 100-C60D10 100-C85D10 100-D110D11 100-D140D11 100-D180D11 100-D180D11 100-D250ED11 100-D300ED11 100-D420ED11 100-D630ED11 Line Reactor kW (HP) .75 (1) 1.49 (2) 0.75-3.7 (1-5) 0.75-3.7 (1-5) 5.5-11 (7.5-15) 5.5-11 (7.5-15) 5.5-11 (7.5-15) 15 (20) 18.5-22 (25-30) 18.5-22 (25-30) 30-37 (40-50) 30-37 (40-50) 45-56 (60-75) 45-56 (60-75) 75 (100) 93 (125) 112 (150) AC Input Contactor Cat. No. 100-C12D10 100-C12D10 100-C12D10 100-C23D10 100-C30D10 100-C37D10 100-C60D10 100-C60D10 100-C85D10 100-D110D11 100-D140D11 100-D180D11 100-D180D11 100-D250ED11 100-D300ED11 100-D420ED11 100-D630ED11 230V AC Input, Non-Regenerative Drives Drive Cat. No. 20P-21AB7P0 20P-21AB9P0 20P-21AB012 20P-21AB020 20P-21AB029 20P-21AB038 20P-21AB055 20P-21AB073 20P-21AB093 20P-21AB110 20P-21AB146 20P-21AB180 20P-21AB218 20P-21AB265 20P-21AB360 20P-21AB434 20P-21AB521 10 DC Amps 7 9 12 20 29 38 55 73 93 110 146 180 218 265 360 434 521 AC Line Amps 5.7 7.4 9.8 16 24 31 45 60 76 90 119 147 178 217 294 355 426 HP 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 IP00 (Open Style) Line Reactor Cat No. 1321-3R8-A 1321-3R12-A 1321-3R18-A 1321-3R18-A 1321-3R55-A 1321-3R55-A 1321-3R55-A 1321-3R80-A 1321-3R100-A 1321-3R100-A 1321-3R160-A 1321-3R160-A 1321-3RB250-A 1321-3RB250-A 1321-3RB320-A 1321-3RB400-A 1321-3R500-A PowerFlex DC Technical Data 460V AC Input, Regenerative Drives Drive Cat. No. 20P-41AD4P1 20P-41AD6P0 20P-41AD010 20P-41AD014 20P-41AD019 20P-41AD027 20P-41AD035 20P-41AD045 20P-41AD052 20P-41AD073 20P-41AD086 20P-41AD100 20P-41AD129 20P-41AD167 20P-41AD207 20P-41AD250 20P-41AD330 20P-41AD412 20P-41AD495 20P-41AD667 DC Amps 4.1 6 10 14 19 27 35 45 52 73 86 100 129 167 207 250 330 412 495 667 AC Line Amps 3.3 4.9 8.2 11.4 15.5 22.1 28.6 36.8 42.5 59.6 70.3 81.7 105.4 136.4 169.1 204.3 269.6 336.6 404.4 544.9 HP 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 400 IP00 (Open Style) Line Reactor Cat No. 1321-3R4-A 1321-3R8-A 1321-3R18-B 1321-3R18-B 1321-3R18-B 1321-3R55-B 1321-3R55-B 1321-3R55-B 1321-3R55-B 1321-3R80-B 1321-3R100-B 1321-3R100-B 1321-3R160-B 1321-3R160-B 1321-3RB250-B 1321-3RB250-B 1321-3RB320-B 1321-3RB400-B 1321-3R500-B 1321-3R600-B Line Reactor kW (HP) .55 (.75) .75 (1) 1.5-7.5 (2-10) 1.5-7.5 (2-10) 1.5-7.5 (2-10) 11-22 (15-30) 11-22 (15-30) 11-22 (15-30) 11-22 (15-30) 30 (40) 37-45 (50-60) 37-45 (50-60) 56-75 (75-100) 56-75 (75-100) 93-112 (125-150) 93-112 (125-150) 149 (200) 186.4 (250) 223.7 (300) 298.3 (400) AC Input Contactor Cat. No. 100-C12D10 100-C12D10 100-C12D10 100-C12D10 100-C23D10 100-C23D10 100-C30D10 100-C37D10 100-C43D10 100-C60D10 100-C85D10 100-C85D10 100-D110D11 100-D140D11 100-D180D11 100-D210ED11 100-D300ED11 100-D420ED11 100-D420ED11 100-D630ED11 Line Reactor kW (HP) .55 (.75) .75 (1) 1.5-7.5 (2-10) 1.5-7.5 (2-10) 1.5-7.5 (2-10) 11-22 (15-30) 11-22 (15-30) 11-22 (15-30) 11-22 (15-30) 30 (40) 37-45 (50-60) 37-45 (50-60) 56-75 (75-100) 56-75 (75-100) 93-112 (125-150) 93-112 (125-150) 149 (200) 186.4 (250) 223.7 (300) 298.3 (400) AC Input Contactor Cat. No. 100-C12D10 100-C12D10 100-C12D10 100-C12D10 100-C23D10 100-C23D10 100-C30D10 100-C37D10 100-C43D10 100-C60D10 100-C85D10 100-C85D10 100-D110D11 100-D140D11 100-D180D11 100-D210ED11 100-D300ED11 100-D420ED11 100-D420ED11 100-D630ED11 460V AC Input, Non-Regenerative Drives Drive Cat. No. 20P-21AD4P1 20P-21AD6P0 20P-21AD010 20P-21AD014 20P-21AD019 20P-21AD027 20P-21AD035 20P-21AD045 20P-21AD052 20P-21AD073 20P-21AD086 20P-21AD100 20P-21AD129 20P-21AD167 20P-21AD207 20P-21AD250 20P-21AD330 20P-21AD412 20P-21AD495 20P-21AD667 DC Amps 4.1 6 10 14 19 27 35 45 52 73 86 100 129 167 207 250 330 412 495 667 AC Line Amps 3.3 4.9 8.2 11.4 15.5 22.1 28.6 36.8 42.5 59.6 70.3 81.7 105.4 136.4 169.1 204.3 269.6 336.6 404.4 544.9 HP 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 400 IP00 (Open Style) Line Reactor Cat No. 1321-3R4-A 1321-3R8-A 1321-3R18-B 1321-3R18-B 1321-3R18-B 1321-3R55-B 1321-3R55-B 1321-3R55-B 1321-3R55-B 1321-3R80-B 1321-3R100-B 1321-3R100-B 1321-3R160-B 1321-3R160-B 1321-3RB250-B 1321-3RB250-B 1321-3RB320-B 1321-3RB400-B 1321-3R500-B 1321-3R600-B 11 PowerFlex DC Technical Data DC Contactors and Dynamic Brake Resistor Kits 230V AC Input, Regenerative Drives DC Drive Cat. No. Amps 20P-41AB7P0 7 20P-41AB9P0 9 20P-41AB012 12 20P-41AB020 20 20P-41AB029 29 20P-41AB038 38 20P-41AB055 55 20P-41AB073 73 20P-41AB093 93 20P-41AB110 110 20P-41AB146 146 20P-41AB180 180 20P-41AB218 218 20P-41AB265 265 20P-41AB360 360 20P-41AB434 434 20P-41AB521 521 (1) (2) (3) (4) (5) (6) (7) AC Line Amps 5.7 7.4 9.8 16 24 31 45 60 76 90 119 147 178 217 294 355 426 HP 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 Dynamic Brake Resistor Kit Cat. No. 1370-DBL62 1370-DBL63 1370-DBL64 1370-DBL65 1370-DBL66 1370-DBL67 1370-DBL68 1370-DBL69 1370-DBL70 1370-DBL71 1370-DBL72 1370-DBL73 1370-DBL74 1370-DBL75 1370-DBL76 (1) (2) Armature Voltage (Volts) 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 DB Resistor Size (ohms) 20 20 15 8.6 6 5 3.5 2.6 2 2 0.7 0.5 0.5 2 1.4 0.5 0.322 DB Resistor Size (Watts) 420 420 420 420 345 330 385 385 330 330 280 365 365 330 290 1458 6221 Brake Amps Required 12.00 12.00 16.00 27.91 40.00 48.00 68.57 92.31 120.00 120.00 342.86 480.00 480.00 120.00 171.43 651 781 DC Loop Contactor Cat. No.(3) 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC110 1370-DC110 1370-DC110 1370-DC180 1370-DC180 1370-DC280 1370-DC280 DC Contactor Crimp Lugs Cat. No.(6) 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG56 1370-LG92 1370-LG92 1370-LG110 1370-LG160 1370-LG180 1370-LG228 1370-LG268 (4) (7) (5) (7) (5) (7) Qty 4-CUTLER-HAMMER_G3AP50 Two in series, two in parallel. Must be sourced separately from drive. HUBBELL_Y139W322GB - Must be sourced separately from drive. Coil voltage = 115V AC, 50/60Hz. ABB_EHDB360C-1L-22 - ABB Contactor for drives with a dynamic brake. Must be sourcing separately from drive. ABB_EHDB520C2P-1L - ABB Contactor for drives with no Dynamic Brake. ABB_EHDB520C-1L - ABB Contactor for drives with Dynamic Brake. Must be sourced separately from drive. See the “DC Contactor Crimp Lug Kit Specifications” in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001…, for more information. Wire and Lug size dependant on Cabinet dims and local codes. Parallel solutions available. 230V AC Input, Non-Regenerative Drives DC Drive Cat. No. Amps 20P-21AB7P0 7 20P-21AB9P0 9 20P-21AB012 12 20P-21AB020 20 20P-21AB029 29 20P-21AB038 38 20P-21AB055 55 20P-21AB073 73 20P-21AB093 93 20P-21AB110 110 20P-21AB146 146 20P-21AB180 180 20P-21AB218 218 20P-21AB265 265 20P-21AB360 360 20P-21AB434 434 20P-21AB521 521 (1) (2) (3) (4) (5) (6) (7) AC Line Amps 5.7 7.4 9.8 16 24 31 45 60 76 90 119 147 178 217 294 355 426 HP 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 Dynamic Brake Resistor Kit Cat. No. 1370-DBL62 1370-DBL63 1370-DBL64 1370-DBL65 1370-DBL66 1370-DBL67 1370-DBL68 1370-DBL69 1370-DBL70 1370-DBL71 1370-DBL72 1370-DBL73 1370-DBL74 1370-DBL75 1370-DBL76 (1) (2) Armature Voltage (Volts) 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 DB Resistor Size (ohms) 20 20 15 8.6 6 5 3.5 2.6 2 2 0.7 0.5 0.5 2 1.4 0.5 0.322 DB Resistor Size (Watts) 420 420 420 420 345 330 385 385 330 330 280 365 365 330 290 1458 6221 Brake Amps Required 12.00 12.00 16.00 27.91 40.00 48.00 68.57 92.31 120.00 120.00 342.86 480.00 480.00 120.00 171.43 – – DC Loop Contactor Cat. No.(3) 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC110 1370-DC110 1370-DC110 1370-DC180 1370-DC180 1370-DC280 1370-DC280 DC Contactor Crimp Lugs Cat. No.(6) 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG56 1370-LG92 1370-LG92 1370-LG110 1370-LG160 1370-LG180 1370-LG228 1370-LG268 (4) (7) (5) (7) (5) (7) Qty 4-CUTLER-HAMMER_G3AP50 Two in series, two in parallel. Must be sourced separately from drive. HUBBELL_Y139W322GB - Must be sourced separately from drive. Coil voltage = 115V AC, 50/60Hz. ABB_EHDB360C-1L-22 - ABB Contactor for drives with a dynamic brake. Must be sourcing separately from drive. ABB_EHDB520C2P-1L - ABB Contactor for drives with no Dynamic Brake. ABB_EHDB520C-1L - ABB Contactor for drives with Dynamic Brake. Must be sourced separately from drive. See the “DC Contactor Crimp Lug Kit Specifications” in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001…, for more information. Wire and Lug size dependant on Cabinet dims and local codes. Parallel solutions available. 12 PowerFlex DC Technical Data 460V AC Input, Regenerative Drives DC Drive Cat. No. Amps 20P-41AD4P1 4.1 20P-41AD6P0 6 20P-41AD010 10 20P-41AD014 14 20P-41AD019 19 20P-41AD027 27 20P-41AD035 35 20P-41AD045 45 20P-41AD052 52 20P-41AD073 73 20P-41AD086 86 20P-41AD100 100 20P-41AD129 129 20P-41AD167 167 20P-41AD207 207 20P-41AD250 250 20P-41AD330 330 20P-41AD412 412 20P-41AD495 495 20P-41AD667 667 (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) AC Line Amps 3.3 4.9 8.2 11.4 15.5 22.1 28.6 36.8 42.5 59.6 70.3 81.7 105.4 136.4 169.1 204.3 269.6 336.6 404.4 544.9 HP 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 400 Dynamic Brake Resistor Kit Cat. No. 1370-DBH63 1370-DBH64 1370-DBH65 1370-DBH66 1370-DBH67 1370-DBH68 1370-DBH69 1370-DBH70 1370-DBH71 1370-DBH72 1370-DBH73 1370-DBH74 1370-DBH75 1370-DBH76 1370-DBH77 1370-DBH78 1370-DBH79 (1) (2) (3) Armature Voltage (Volts) 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 DB Resistor Size (ohms) 81 62 45 27 20 12 5 4.5 3.5 2.6 2 2 1 0.7 0.7 0.5 0.7 0.808 0.595 0.542 DB Resistor Size (Watts) 255 245 245 350 420 405 330 330 385 345 345 345 270 280 280 365 280 7292 6069 6439 Brake Amps Required 6.17 8.06 11.11 18.52 25.00 41.67 100.00 111.11 142.86 192.31 250.00 250.00 500.00 714.29 714.29 1000.00 714.29 – – – DC Loop Contactor Cat. No.(4) 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC110 1370-DC110 1370-DC110 1370-DC180 1370-DC180 1370-DC280 1370-DC280 DC Contactor Crimp Lugs Cat. No.(9) 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG52 1370-LG52 1370-LG92 1370-LG92 1370-LG110 1370-LG140 1370-LG180 1370-LG228 1370-LG268 (5) (10) (6) (10) (7) (10) (8) (10) HUBBELL_Y95W808GB - Must be sourced separately from drive. HUBBELL_Y101W595GB - Must be sourced separately from drive. HUBBELL_Y109W542GB - Must be sourced separately from drive. Coil voltage = 115V AC, 50/60Hz. ABB_EHDB360C-1L-22 - ABB Contactor for drives with a dynamic brake. Must be sourcing separately from drive. ABB_EHDB520C2P-1L - ABB contactor for drives with no dynamic brake. ABB_EHDB520C-1L - ABB contactor for drives with a dynamic brake. Must be sourced separately from drive. ABB_EHDB650C2P-1L - ABB contactor for drives with no dynamic brake. ABB_EHDB650C-1L - ABB contactor for drives with a dynamic brake. Must be sourced separately from drive. ABB_EHDB800C2P-1L - ABB contactor for drives with no dynamic brake. ABB_EHDB800C-1L - ABB contactor for drives with a dynamic brake. Must be sourced separately from drive. See the “DC Contactor Crimp Lug Kit Specifications” in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001…, for more information. Wire and Lug size dependant on Cabinet dims and local codes. Parallel solutions available. 460V AC Input, Non-Regenerative Drives Drive Cat. No. 20P-21AD4P1 20P-21AD6P0 20P-21AD010 20P-21AD014 20P-21AD019 20P-21AD027 20P-21AD035 20P-21AD045 20P-21AD052 20P-21AD073 20P-21AD086 20P-21AD100 20P-21AD129 20P-21AD167 20P-21AD207 20P-21AD250 20P-21AD330 20P-21AD412 20P-21AD495 20P-21AD667 (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) DC Amps 4.1 6 10 14 19 27 35 45 52 73 86 100 129 167 207 250 330 412 495 667 AC Line Amps 3.3 4.9 8.2 11.4 15.5 22.1 28.6 36.8 42.5 59.6 70.3 81.7 105.4 136.4 169.1 204.3 269.6 336.6 404.4 544.9 HP 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 400 Dynamic Brake Resistor Kit Cat. No. 1370-DBH63 1370-DBH64 1370-DBH65 1370-DBH66 1370-DBH67 1370-DBH68 1370-DBH69 1370-DBH70 1370-DBH71 1370-DBH72 1370-DBH73 1370-DBH74 1370-DBH75 1370-DBH76 1370-DBH77 1370-DBH78 1370-DBH79 (1) (2) (3) Armature Voltage (Volts) 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 DB Resistor Size (ohms) 81 62 45 27 20 12 5 4.5 3.5 2.6 2 2 1 0.7 0.7 0.5 0.7 0.808 0.595 0.542 DB Resistor Size (Watts) 255 245 245 350 420 405 330 330 385 345 345 345 270 280 280 365 280 7292 6069 6439 Brake Amps Required 6.17 8.06 11.11 18.52 25.00 41.67 100.00 111.11 142.86 192.31 250.00 250.00 500.00 714.29 714.29 1000.00 714.29 – – – DC Loop Contactor Cat. No.(4) 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC110 1370-DC110 1370-DC110 1370-DC180 1370-DC180 1370-DC280 1370-DC280 DC Contactor Crimp Lugs Cat. No.(9) 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG52 1370-LG52 1370-LG92 1370-LG92 1370-LG110 1370-LG140 1370-LG180 1370-LG228 1370-LG268 (5) (10) (6) (10) (7) (10) (8) (10) HUBBELL_Y95W808GB - Must be sourced separately from drive. HUBBELL_Y101W595GB - Must be sourced separately from drive. HUBBELL_Y109W542GB - Must be sourced separately from drive. Coil voltage = 115V AC, 50/60Hz. ABB_EHDB360C-1L-22 - ABB Contactor for drives with a dynamic brake. Must be sourcing separately from drive. ABB_EHDB520C2P-1L - ABB contactor for drives with no dynamic brake. ABB_EHDB520C-1L - ABB contactor for drives with a dynamic brake. Must be sourced separately from drive. ABB_EHDB650C2P-1L - ABB contactor for drives with no dynamic brake. ABB_EHDB650C-1L - ABB contactor for drives with a dynamic brake. Must be sourced separately from drive. ABB_EHDB800C2P-1L - ABB contactor for drives with no dynamic brake. ABB_EHDB800C-1L - ABB contactor for drives with a dynamic brake. Must be sourced separately from drive. See the “DC Contactor Crimp Lug Kit Specifications” in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001…, for more information. Wire and Lug size dependant on Cabinet dims and local codes. Parallel solutions available. 13 PowerFlex DC Technical Data Installation Considerations The PowerFlex Digital DC drive has the following built in protective features to help simplify installation: • Ground fault protection during start up and running ensures reliable operation • Electronic motor overload protection increases motor life There are many other factors that must be considered for optimal performance in any given application. The block diagram below highlights the primary installation considerations. Input Fuses - See page -36 Input Power Conditioning - See page -9 LCD HIM - See page -8 DC Drive Accessories - See page -12 Motor Overload Protection - See page -28 Motor Recommendations - See the Allen-Bradley Variable Speed AC/DC Motors Catalog, publication RAPS-1348… 14 PowerFlex DC Technical Data Power Wiring AC Input Voltages PowerFlex DC drives are rated for the following AC input voltages: Armature Circuit Terminals U, V, W 230V ±10 %, 3Ph 400V ±10 %, 3Ph 440V ±10 %, 3Ph 460V ±10 %, 3Ph 480V ±10 %, 3Ph @ 50/60 Hz ±5 % (1) Field Circuit Terminals U1, V1 230V ±10 %, 1Ph 400V ±10 %, 1Ph 460V ±10 %, 1Ph @ 50/60 Hz ±5 % Control Circuit Terminals U2, V2 115V ±15 %, 1 Ph(1) or 230V ±15 %, 1Ph @ 50/60 Hz ±5 % For frame B and C drives only, a jumper must be placed between terminals SA-SB on the Switching Power Supply circuit board for the control circuits to work with 115V AC input. Refer to SA-SB Terminal Block Location on Frame B Drives on page 25 and SA-SB Terminal Block Location on Frame C Drives on page 26. DC Output Voltages The output voltages below take into account an AC input undervoltage within the stated tolerance limits and a voltage drop of 4% due to an AC input line reactor. It is the same as the rated armature voltage suggested for the connected motor. Armature Circuit AC Input Voltage (Terminals U, V, W) 230V ±10 %, 3Ph 400V ±10 %, 3Ph 440V ±10 %, 3Ph 460V ±10 %, 3Ph 480V ±10 %, 3Ph DC Output Armature Voltage (Terminals C & D) Two Quadrant Drive Four Quadrant Drive 260V 240V 470V 420V 530V 460V 560V 480V 580V 500V Field Circuit AC Input Voltage (Terminals U1 & V1) 230V ±15 %, 1Ph 400V ±15 %, 1Ph 460V ±10%, 1Ph (1) DC Output Field Voltage(1) (Terminals C1 & D1) Fixed Field Adjustable Field 200V 200V 310V 310V 360V 360V The max field voltage is equal to 0.85 x AC input line voltage 15 PowerFlex DC Technical Data Typical Power Wiring Diagrams The following diagram represents recommended power wiring configurations: Power Wiring with AC Input Contactor (1) 34 (on I/O TB4) FU1 (N.O. Relay) M1 AC Contactor 13 L1 L2 3 Phase AC line L3 FU8 C 19 (+24V - on I/O TB2) Aux 14 L1 T1 L2 T2 L3 T3 A1 A2 FU3 A1 U FU4 M V FU5 W PowerFlex DC Drive FU9 U2 460V 115V (2) A2 (2) FU2 D Control Board P/S V2 (3) 35 (3) 36 Control Power / Relay Terminal Block FU6 U1 FU7 V1 Field Power Terminal Block C1 F1 D1 F2 (1) Par 140 [Digital In8 Sel] set to 31 “Contactor” (2) Armature output fuses are required on four quadrant and are recommended on two quadrant Frame A and B drives. Fuses with Trip Indicator Switches are recommended for Inverting Fault protection when the motor will be Field Weakened and run above base speed. See Power Wiring with Armature Output Fuses and Inverting Fault Status on page 18. (3) Par 1391 [ContactorControl] = 1 “AC Cntctr” and Par 1392 [Relay Out 1 Sel] = 25 “Contactor”. Important: Terminal 35 and 36 are on the Control Power / Relay Terminal block, NOT the I/ O terminal blocks. See Relay Outputs on page 28. 16 PowerFlex DC Technical Data Power Wiring with DC Output Contactor (1) 34 (on I/O TB4) (N.O. Relay) M1 DC Contactor 13 19 (+24V on I/O TB2) FU3 L1 U L2 FU1 C FU4 D V FU5 3 Phase AC line L3 W FU8 Aux 14 L1 T1 L2 T2 A1 A2 (2) A1 PowerFlex DC Drive FU9 M A2 U2 460V 115V Control Board P/S FU2 (2) V2 (3) 35 (3) 36 Control Power / Relay Terminal Block FU6 U1 FU7 V1 Field Power Terminal Block C1 F1 D1 F2 (1) Par 140 [Digital In8 Sel] set to 31 “Contactor” (2) Armature output fuses are required on four quadrant and are recommended on two quadrant Frame A and B drives. Fuses with Trip Indicator Switches are recommended for Inverting Fault protection when the motor will be Field Weakened and run above base speed. See Power Wiring with Armature Output Fuses and Inverting Fault Status on page 18. (3) Par 1391 [ContactorControl] = 3 “DC Cntctr” and Par 1392 [Relay Out 1 Sel] = 25 “Contactor”. Important: Terminal 35 and 36 are on the Control Power / Relay Terminal block, NOT the I/O terminal blocks. See Relay Outputs on page 28. 17 PowerFlex DC Technical Data Power Wiring with DC Output Contactor and a Dynamic Brake (1) 34 (on I/O TB4) 19 (+24V on I/O TB2) FU3 L1 C U FU4 L2 (N.O. Relay) M1 DC Contactor Aux 13 14 D V W FU8 PowerFlex DC Drive FU9 115V (3) 75 A2 A1 L2 L1 13 A2 T2 T1 14 (2) A1 M A2 FU2 (3) 35 (3) A1 DB Resistor U2 36 T2 (N.C. Relay) DB Contactor Control Board P/S V2 460V L2 Aux L3 T1 FU1 FU5 3 Phase AC line L1 (2) Control Power / Relay Terminal Block (3) 76 FU6 U1 FU7 V1 Field Power Terminal Block C1 D1 F1 F2 (1) Par 140 [Digital In8 Sel] set to 31 “Contactor” (2) Armature output fuses are required on four quadrant and are recommended on two quadrant Frame A and B drives. Fuses with Trip Indicator Switches are recommended for Inverting Fault protection when the motor will be Field Weakened and run above base speed. See Power Wiring with Armature Output Fuses and Inverting Fault Status on page 18. (3) Par 1391 [ContactorControl] = 4 “DC Cntctr+DB”, Par 1392 [Relay Out 1 Sel] = 25 “Contactor”, and Par 629 [Relay Out 2 Sel] = 24 “ContactorDB”. Important: Terminal 35, 36, 75 and 76 are on the Control Power / Relay Terminal block, NOT the I/O terminal blocks. See Relay Outputs on page 28. Power Wiring with Armature Output Fuses and Inverting Fault Status (1) FU1 C A1 M PowerFlex DC Drive (1) A2 FU2 D (2) 33 (on I/O TB4) (1) Armature output fuses are required on four quadrant and are recommended on two quadrant Frame A and B drives. Fuses with Trip 19 (+24V on I/O TB2) Indicator Switches are recommended for Inverting Fault protection when the motor will be Field Weakened and run above base speed. (2) Par 139 [Digital In7 Sel] set to 64 “Invert Flt”. 18 PowerFlex DC Technical Data Armature Power Terminal Connections Terminal U V W C D Description Three-phase AC input power to the armature converter. Output power from the armature to the motor. Frame A Armature Terminal Block Locations Bottom View Loosen the two screws that secure the power terminal cover to the drive chassis and remove the terminal cover in order to connect the armature power wiring. Front View Note: Front view of drive shown with bottom protective and power terminal covers removed. PE ! U C V D W ATTENTION: Do not operate the drive with the power terminal cover removed. Operating the drive with the power terminal cover removed may result in a hazardous condition that could cause personal injury and/or equipment damage. 19 PowerFlex DC Technical Data Frame B Armature Terminal Block Locations PE U C V D W Frame C Armature Terminal Block Locations Front View PE U C V Bottom View 20 D W PowerFlex DC Technical Data Armature Power Terminal and Ground (PE) Wire Sizes Frame Drive Current Rating Code(1) 230V 460V A 7P0 4P1 9P0 6P0 012 010 020 014 – 019 029 027 038 035 055 045 – 052 073 073 093 086 110 – – 100 – 129 B 146 167 180 – 218 207 265 250 – 330 360 412 434 – C 521 495 – 667 (1) Terminals Terminal Bolt Size (mm) Wire Size and Type Tightening Torque (N•m / lbs•in) U, V, W, C, D, PE 5 6 / 53 U, V, W, C, D, PE Terminal Block 12 / 106 U, V, W, C, D PE U, V, W, C, D PE U, V, W, C, D PE U, V, W C, D PE U, V, W C, D PE U, V, W C, D PE U, V, W C, D PE U, V, W C, D PE U, V, W C, D PE 10 8 10 See “Cable and Wiring 8 Recommendations in the PowerFlex Digital 10 DC Drive User 8 Manual, publication 20P-UM001… 10 50 / 442.5 25 / 221 50 / 442.5 25 / 221 50 / 442.5 25 / 221 50 / 442.5 8 25 / 221 10 50 / 442.5 8 25 / 221 10 50 / 442.5 8 25 / 221 10 50 / 442.5 8 25 / 221 10 50 / 442.5 8 25 / 221 10 50 / 442.5 8 25 / 221 See the Catalog Number Explanation on page 6, positions 8-10 for corresponding drive HP rating, armature amp rating and field amp rating. 21 PowerFlex DC Technical Data Field Converter Connections Field Converter Terminal Designations Terminal U1 V1 C1 D1 Description Single-phase AC line input power to the field circuit. DC output power to the motor field. Frame A Field Circuit Terminal Block Location Bottom View of Drive U1 V1 C1 D1 Frame B Field Circuit Terminal Block Location U1 V1 C1 D 1 Top View of Drive 22 PowerFlex DC Technical Data Frame C Field Circuit Terminal Block Location Front View of Drive D1 C1 U1 V1 Field Converter Wire Sizes Frame All Drive w/Current Code(1) 230V 460V Terminals All All U1, V1, C1, D1 Wire Size and Type (2) (AWG/kcmils) 0.2 - 4.0 / 24 - 10 Tightening Torque (N•m / lbs•in) 0.5 - 0.8 / 4.4 - 7.1 (1) See the Catalog Number Explanation on page 6, positions 8-10 for corresponding drive HP rating, armature amp rating and field amp rating. (2) See “Cable and Wiring Recommendations in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001… Control Circuit Input Power The control circuit must be powered by an external 230V AC or 115V AC single phase power supply. For frame B and C drives only, a jumper is required between terminals SA and SB for 115V AC control input power. Refer to SA-SB Terminal Block Location on Frame B Drives on page 25 and SA-SB Terminal Block Location on Frame C Drives on page 26 for terminal block locations.) Control Circuit Terminal Designations Terminal U2 V2 Description Single-phase AC power for the control circuits. 23 PowerFlex DC Technical Data Frame A Control Circuit Terminal Block Location U2 Frame B Control Circuit Terminal Block Location U2 24 V2 V2 PowerFlex DC Technical Data Frame C Control Circuit Terminal Block Location U2 V2 Control Circuit Wire Sizes Drive w/Current Code(1) Frame 230V All All 460V All Terminals U2, V2 Wire Size and Type(2) Multi-core Flexible Wire Wire Size Size (mm2) (mm2) 0.14 - 1.5 0.14 - 2.5 AWG 26 - 14 Tightening Torque (N•m / lbs•in) 0.5 / 4.4 (1) See the Catalog Number Explanation on page 6, positions 8-10 for corresponding drive HP rating, armature amp rating and field amp rating. (2) See “Cable and Wiring Recommendations in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001… SA-SB Terminal Block Location on Frame B Drives SA-SB terminals Top of drive Front of drive 25 PowerFlex DC Technical Data SA-SB Terminal Block Location on Frame C Drives Switching Power Supply board (located on the back of the Control EMI shield) SA-SB terminals Front of drive shown with top protective cover removed. 26 Control EMI Shield (Shown in the open position) Control EMI shield PowerFlex DC Technical Data Frame C Heatsink Cooling Fans and Armature Fuse Signal Terminals Frame C drives require an external power supply for the heatsink cooling fans and include internal armature circuit protection fuses (drives rated 521A @ 230V AC and 495A and 667A @ 460V AC input only). The terminals for the internal armature circuit protection fuses can be connected to an external device to provide indication that the fuses have opened. Heatsink Fans and Fuses Terminal Designations Terminal U3 V3 81 82 Description Single-phase AC input power to cooling fans Maximum Voltage 240V AC Maximum Current 1A Internal armature fuse intervention signal 250V AC 1A AC112 Frame C Heatsink Cooling Fan and Internal Fuse Signal Terminal Block Locations 81 82 U3 V3 27 PowerFlex DC Technical Data Relay Outputs Terminals 35 and 36 and 75 and 76 are N.O. relay outputs. The relay output between terminals 35 and 36 is configured with parameter 1392 [Relay Out 1 Sel]. The relay output between terminals 75 and 76 is configured with parameter 629 [Relay Out 2 Sel]. Refer to “Using Contactors” in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001…, for more information. Thermistors and Thermal Switches To detect motor overheating and protect the motor from overloading, an external, user-supplied thermistor (PTC) or thermal switch must be connected to terminals 78 and 79. The drive’s response to a motor over temperature fault is configured in parameter 365 [OverTemp Flt Cfg]. If a temperature sensor is not used, a 1k ohm resistor must be connected between terminals 78 and 79 (installed at the factory). The instructions for installing a thermal sensor are detailed below. Thermistors (PTC) PTC thermistors fitted in the motor can be connected directly to the drive via terminals 78 and 79. In this case the 1k ohm resistor is not required between terminals 78 and 79. Thermal Switches (Klixon®) in the Motor Windings “Klixon” type temperature-dependent contacts can disconnect the drive from the motor via an external control or can be configured as an external fault using a digital input on drive. They can also be connected to terminals 78 and 79 in order to indicate a drive “Motor Over Temp” fault (F16), though this is not recommended due to the noise sensitivity of the current threshold circuitry. If a thermal switch is used a 1k ohm resistor must be placed in series between the switch and one of the terminals. Contact Relay and Thermistor Terminal Designations Terminal 35 36 75 76 78 79 28 Description Normally open contact. Configured with parameter 1392 [Relay Out 1 Sel] - set to 25 “Contactor” by default. Normally open contact. Configured with parameter 629 [Relay Out 2 Sel] set to 5 “Ready” by default. Motor thermistor connections (PTC) PowerFlex DC Technical Data Frame A Contact Relay and Thermistor Terminal Block Locations Note: Terminals 78 and 79 shown with 1k ohm resistor in place of temperature sensor. 78 79 35 36 75 76 Frame B Contact Relay and Thermistor Terminal Block Locations 78 79 35 36 75 76 29 PowerFlex DC Technical Data Frame C Contact Relay and Thermistor Terminal Block Locations 35 36 75 76 78 79 Recommended Signal Wire Size for Relay Outputs and Thermistor/Thermal Switch Terminals Signal Type Relay Outputs Thermistor and Thermal Switches (1) Terminals 35 & 36, 75 & 76 78 & 79 Wire Type and Size(1) Flexible multi-core (mm2) (mm2) 0.140 - 1.500 0.140 - 1.500 AWG 26-14 Tightening Torque N•m (lb•in) 0.5 (4.4) See “Cable and Wiring Recommendations in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001… 30 PowerFlex DC Technical Data I/O Signal and Control Wiring Eight (8) digital inputs, four (4) digital outputs, three (3) analog inputs, and two (2) analog outputs are available on the standard I/O terminal blocks provided with the drive. One digital input (1-8) must be configured for “Enable”. Additional digital and analog I/O is available when using the optional I/O Expansion circuit board. Refer to Appendix F “Optional Analog and Digital I/O Expansion Circuit Board”, in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001…, for more information. Also, you can use the optional 115V AC Converter circuit board to convert 115V AC digital input signals to 24V DC digital inputs signals to interface with the digital inputs on the standard I/O terminal blocks. Refer to Appendix G - “Optional 115V AC to 24V DC I/O Converter Circuit Board” in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001…, for more information. All I/O terminal blocks are located on the control board. I/O Terminal Block Locations Terminal Block 3 Terminal Block 4 Terminal Block 1 Terminal Block 2 I/O Terminal Block 1 Designations 1 (1) 2 3 4 5 6 7 8 9 No. 1 2 3 4 5 6 Signal Analog Input 1 (+) Analog Input 1 (–) Analog Input 2 (+) Analog Input 2 (–) Analog Input 3 (+) Analog Input 3 (–) 7 8 9 10 +10V Pot Reference –10V Pot Reference Pot Common PE ground 10 Description Isolated (1), bipolar, differential, ±10V / 0-20mA, or 4-20mA. Important: 0-20mA or 4-20mA operation requires that switch S9, S10, and S11 on the Control board be in the “Off” position. Drive damage may occur if the switch is not in the correct position based on the type of input signal. Refer to “DIP Switch and Jumper Settings” in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001… Max ±10V, Max 0.25mA. 2-5k ohm load. Max ±10V, Max 10mA. Factory Default 1 “Speed Ref A” Related Parameter 70 [Anlg In1 Sel] 0 “Off” 75 [Anlg In2 Sel] 0 “Off” 80 [Anlg In3 Sel] – – For (+) and (–) 10V pot references. PE ground to drive chassis. – – – – Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity. 31 PowerFlex DC Technical Data I/O Terminal Block 2 Designations 11 12 13 14 15 16 17 18 19 20 No. 11 12 13 14 15 16 17 18 19 Signal Internal 0V Digital Input 1 Digital Input 2 Digital Input 3 Digital Input 4 Digital Input Common(2) Not Used 24V Supply Common +24V DC Supply Description Max Volt. +30V, Max Cur. 15V/3.2mA, 24V/5mA, and 30V/6.4mA. Common for the internal power supply. Drive supplied control input power. Factory Default – 2 “Stop/CF” 3 “Start” 11 “Jog” 1 “Enable”(1) – – – – Related Parameter – 133 [Digital In1 Sel] 134 [Digital In2 Sel] 135 [Digital In3 Sel] 136 [Digital In4 Sel] – – – – – – Max. +20-30V, 200mA(3) 20 (1) (2) (3) PE ground PE ground to drive chassis. A digital input (1-8) must be configured for “Enable”. When using the internal +24V DC supply (terminal 19) for digital inputs 1-4, you must connect the digital input common (terminal 16) to the +24V supply common (terminal 18). The total current draw is the sum of encoder power, digital outputs and any other loads connected to terminal 19. I/O Terminal Block 3 Designations 21 22 23 24 25 26 27 28 29 30 No. 21 22 23 24 25 26 27 28 29 30 Signal Analog Output 1 (+) Analog Output 1 (–) Analog Output 2 (+) Analog Output 2 (–) Digital Output Common Digital Output 1 Digital Output 2 Digital Output 3 Digital Output 4 +24VDC Description Max. ±10V, Max. 5 mA. Max. +30V, Max 50mA Drive supplied power for Digital Outputs. Max. +30V, Max. 80mA. Factory Default 12 “Motor Speed” Related Parameter 66 [Anlg Out1 Sel] 13 “Motor Curr” 67 [Anlg Out2 Sel] – 5 “Ready” 9 “Fault” 2 “Spd Thresh” 4 “CurrentLimit” – – 145 [Digital Out1 Sel] 146 [Digital Out2 Sel] 147 [Digital Out3 Sel] 148 [Digital Out4 Sel] – I/O Terminal Block 4 Designations 31 32 33 34 35 36 37 38 39 No. 31 32 33 34 35 Signal Digital Input 5 Digital Input 6 Digital Input 7 Digital Input 8 Digital Input Common 3640 Not Used 40 Description Max Volt. +30V, Max Cur. 15V/3.2mA, 24V/5mA, and 30V/6.4mA. Important: When using the internal +24V DC supply (terminal 19) for digital inputs 5-8, you must connect the digital input common (terminal 35) to the +24V supply common (terminal 18). Recommended Signal Wire Size for Analog I/O and Digital I/O Signal Type Analog and Digital I/O (1) Terminal Block (Terminals) TB1 - 4 (1 - 40) Wire Type and Size(1) Flexible multi-core (mm2) (mm2) 0.140 - 1.500 0.140 - 1.500 AWG 26-16 Tightening Torque N•m (lb•in) 0.4 (3.5) See “Cable and Wiring Recommendations in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001… 32 Factory Default 17 “Speed Sel 1” 18 “Speed Sel 2” 19 “Speed Sel 3” 31 “Contactor” – Related Parameter 137 [Digital In5 Sel] 138 [Digital In6 Sel] 139 [Digital In7 Sel] 140 [Digital In8 Sel] – – – PowerFlex DC Technical Data Digital Encoder Terminal Block The encoder connection cables should always be connected directly to the terminals on the encoder terminal block. The encoder cable must be made up of twisted pairs with the shield connected to the shield ground on the drive side. Do not connect the shield to ground on the motor side. In some cases (i.e., cable lengths that exceed 100 meters), it may be necessary to ground the shield of each twisted pair on the power supply. Refer to Appendix A of the PowerFlex Digital DC Drive User Manual, publication 20P-UM001…, for Digital Encoder specifications. Digital Encoder Terminal Designations A+ A- B+ B- Z+ ZCO M +V No. A+ AB+ BZ+ ZCOM +V Description Encoder A Encoder A (NOT) Encoder B Encoder B (NOT) Encoder Z Encoder Z (NOT) +5/12-15V (1) DC Return +5/12-15V (1) DC Power Single channel or quadrature A input Dual channel quadrature B input Pulse, marker or registration input (2) Internal power common Internal power source 200 mA (1) Selectable via switch S21 on the Control board. Refer to “DIP Switch and Jumper Settings” in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001…, for more information. (2) Selectable via switch S20 on the Control board. Refer to “DIP Switch and Jumper Settings” in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001…, for more information. Digital Encoder Terminal Block Location Digital Encoder terminal block 33 PowerFlex DC Technical Data Sample Encoder Wiring I/O Connection Example Encoder Power – (1) +5/12-15V DC Internal Drive Power (200 mA) Internal (drive) +5/12-15V DC, +V 200mA COM Common ZZ+ to Shield (1) BB+ AA+ Encoder Power –External Power Source +V BB+ + ZZ+ Common COM to Shield (1) External Power Supply AA+ Encoder Signal –SingleEnded, Dual Channel +V to Power Supply Common COM Z- Z NOT Z Z+ B- B NOT B B+ A- A NOT A A+ to Shield (1) Encoder Signal –Differential, Dual Channel +V COM Z- Z NOT Z+ Z B- B NOT B+ B A- A NOT A+ A to Shield (1) (1) 34 Shield connection is on the drive Control EMI Shield. Refer to Digital Encoder Terminal Block Location on page 33. PowerFlex DC Technical Data DC Analog Tachometer Terminal Block ATTENTION: The Drive can overspeed if DIP switch S4 is set incorrectly, or the tachometer is wired incorrectly. Failure to observe this precaution could result in damage to, or destruction of, the equipment. ! DC Analog Tachometer Terminal Designations − (1) A B C + No. – A B C + Signal Negative input (Not Used) Description – Positive input Clockwise rotation = positive Counterclockwise rotation = negative 22.7 / 45.4 / 90.7 / 181.6 / 302.9V(1) max voltage 8 mA max. current Maximum voltage depends on the configuration of DIP switch S4. Refer to the PowerFlex® Digital DC Drive User Manual, publication 20P-UM001… for information on jumper settings. Analog Tachometer Terminal Block Location Analog Tachometer terminal block Recommended Signal Wire Size for DC Analog Tachometer Signal Type DC Analog Tach (1) Terminal Block (Terminals) M3 (+ and –) Wire Type and Size(1) Flexible multi-core (mm2) (mm2) 0.140 - 1.500 0.140 - 1.500 AWG 26-16 Tightening Torque N-m (lb.-in.) 0.4 (3.5) See “Cable and Wiring Recommendations in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001… 35 PowerFlex DC Technical Data Circuit Protection The tables on the following pages provide drive ratings and the recommended fuses for protecting the armature and field circuits. Externally mounted fuses (as indicated in the figures below) must be sourced separately when installing the drive. Internally mounted fuses are provided with the drive. Frame A and B Fuse Designations FS1 = Externally mounted fuses for the armature converter on the AC input side. FS1 U V C FS2 = Externally mounted fuses for the armature circuit on the DC side. W U1 FS3 D C1 FS3 = Internally mounted fuses for the field circuit on the AC input side. V1 D1 FS2 M AC Input Line Fuses - 230V AC Input Frame A and B (Regenerative and Non-Regenerative Drives) Frame Drive Current Rating Code A 7P0 9P0 012 020 029 038 055 073 093 110 B 146 180 218 265 360 434 36 Fuse Code FS1 (See Frame A and B Fuse Designations above) Bussmann DC Amps 7 9 12 20 29 38 55 73 93 110 146 180 218 265 360 434 AC Line Amps 5.7 7.4 9.8 16 24 31 45 60 76 90 119 147 178 217 294 355 Ferrule FWP Type FWP-10A14F FWP-15A14F FWP-20A14F FWP-25A14F FWP-40A22F FWP-63A22F FWP-80A22F Ferrule Fuse North American Block FWP Type CH143D FWP-10B FWP-15B FWP-20B FWP-25B CH223D FWP-40B FWP-60B FWP-80B FWP-100A FWP-150A FWP-175A FWP-250A FWP-300A FWP-350A FWP-400A FWP-600A FWP-600A Ferraz Shawmut (Gould Shawmut) North American Fuse Block ST14 ST38-72612 Ferrule A70QS Type A70QS10-14F A70QS16-14F A70QS20-14F A70QS25-14F A70QS40-22F A70QS63-22F A70QS80-22F North American A70P / A70QS Type A70P10-4 A70P15-4 A70P20-4 A70QS25-4 A70QS40-4 A70QS60-4 A70QS80-4 A70QS100-4K A70QS150-4K A70QS175-4K A70QS250-4 A70QS300-4 A70QS350-4 A70QS400-4 A70QS600-4K A70QS600-4 PowerFlex DC Technical Data Recommended AC Input Line Fuses - 460V AC Input Frame A and B (Regenerative and Non-Regenerative Drives) Frame Drive Current Rating Code A 4P1 6P0 010 014 019 027 035 045 052 073 086 100 129 B 167 207 250 330 412 Fuse Code FS1 (See Frame A and B Fuse Designations on page 36) Bussmann DC Amps 4.1 6 10 14 19 37 35 45 52 73 86 100 129 167 207 250 330 412 AC Line Amps 3.3 4.9 8.2 11.4 15.5 22.1 28.6 36.8 42.5 59.6 70.3 81.7 105.4 136.4 169.1 204.3 269.6 336.6 Ferrule FWP Type FWP-10A14F FWP-10A14F FWP-20A14F FWP-25A14F FWP-25A14F FWP-40A22F FWP-63A22F FWP-80A22F FWP-80A22F Ferrule Fuse North American Block FWP Type CH143D FWP-10B FWP-10B FWP-20B FWP-25B FWP-25B CH223D FWP-40B FWP-60B FWP-80B FWP-80B FWP-100A FWP-150A FWP-175A FWP-175A FWP-300A FWP-350A FWP-400A FWP-600A FWP-600A Ferraz Shawmut (Gould Shawmut) North American Fuse Block Ferrule A70QS Type A70QS10-14F A70QS10-14F A70QS20-14F A70QS25-14F A70QS25-14F A70QS40-22F A70QS63-22F A70QS80-22F A70QS80-22F ST14 ST38-72612 North American A70P / A70QS Type A70P10-4 A70P10-4 A70P25-4 A70P25-4 A70P25-4 A70QS40-4 A70QS60-4 A70QS80-4 A70QS80-4 A70QS100-4K A70QS150-4K A70QS175-4K A70QS175-4K A70QS300-4 A70QS350-4 A70QS400-4 A70QS600-4K A70QS600-4 Recommended Armature DC Output Fuses - 230V AC Input Frame A and B (Regenerative Drives Only) Frame Drive Current Rating Code A 7P0 9P0 012 020 029 038 055 073 093 110 B 146 180 218 265 360 434 (1) Fuse Code FS2(1) (See Frame A and B Fuse Designations on page 36) Bussmann DC Amps 7 9 12 20 29 38 55 73 93 110 146 180 218 265 360 434 AC Line Amps 5.7 7.4 9.8 16 24 31 45 60 76 90 119 147 178 217 294 355 Ferrule FWP Type FWP-15A14F FWP-20A14F FWP-25A14F FWP-40A14F FWP-63A22F FWP-80A22F Ferrule Fuse North American Block FWP Type CH142D FWP-15B FWP-20B FWP-25B FWP-40B CH222D FWP-60B FWP-80B FWP-125A FWP-150A FWP-200A FWP-225A FWP-300A FWP-350A FWP-450A FWP-600A FWP-700A FWP-900A Ferraz Shawmut (Gould Shawmut) North American Fuse Block ST14 ST38-72612 Ferrule A70QS Type A70QS16-14F A70QS20-14F A70QS25-14F A70QS40-14F A70QS63-22F A70QS80-22F North American A70P / A70QS Type A70P15-4 A70P20-4 A70P25-4 A70QS40-4 A70QS60-4 A70QS80-4 A70QS125-4K A70QS150-4K A70QS200-4K A70QS250-4 A70QS300-4 A70QS350-4 A70QS450-4 A70QS600-4K A70QS700-4 A70P900-4 Required on four quadrant drives only, highly recommended on two quadrant drives. 37 PowerFlex DC Technical Data Recommended Armature DC Output Fuses - 460V AC Input Frame A and B (Regenerative Drives Only) Frame Drive Current Rating Code A 4P1 6P0 010 014 019 027 035 045 052 073 086 100 129 B 167 207 250 330 412 (1) Fuse Code FS2(1) (See Frame A and B Fuse Designations on page 36) Bussmann DC Amps 4.1 6 10 14 19 37 35 45 52 73 86 100 129 167 207 250 330 412 AC Line Amps 3.3 4.9 8.2 11.4 15.5 22.1 28.6 36.8 42.5 59.6 70.3 81.7 105.4 136.4 169.1 204.3 269.6 336.6 Ferrule FWP Type FWP-10A14F FWP-15A14F FWP-20A14F FWP-30A14F FWP-40A14F FWP-63A22F FWP-80A22F FWP-100A22F FWP-100A22F Ferrule Fuse North American Block FWP Type CH142D FWP-10B FWP-15B FWP-20B FWP-30B FWP-40B CH222D FWP-60B FWP-70B FWP-90B FWP-100B FWP-150A FWP-175A FWP-200A FWP-250A FWP-350A FWP-400A FWP-500A FWP-700A FWP-800A Ferraz Shawmut (Gould Shawmut) North American Fuse Block Ferrule A70QS Type A70QS10-14F A70QS16-14F A70QS20-14F A70QS32-14F A70QS40-14F A70QS63-22F A70QS80-22F ST14 ST38-72612 North American A70P / A70QS Type A70P10-4 A70P15-4 A70P20-4 A70P30-4 A70QS40-4 A70QS60-4 A70QS70-4 A70QS90-4 A70QS100-4 A70QS150-4K A70QS175-4K A70QS200-4K A70QS250-4 A70QS350-4 A70QS400-4 A70QS500-4K A70QS700-4 A70QS800-4 Required on four quadrant drives only, highly recommended on two quadrant drives. Frame Recommended Field Circuit Fuses - 230V AC Input Frame A and B (Regenerative and Non-Regenerative Drives) A B (1) 38 Drive Current Rating Code 7P0 9P0 012 020 029 038 055 073 093 110 146 180 218 265 360 434 Field Amps 10 Type 6 x 32 mm Fuse Code FS3(1) (See Frame A and B Fuse Designations on page 36 and Frame A Field AC Input Line Fuses Location on page 39 and Frame B Field AC Input Line Fuses Location on page 40 for location.) Ferraz Shawmut Bussmann (Gould Shawmut) SIBA FWH-016A6F E085449 70 125 40.16 10 x 38 mm FWC-25A10F 14 20 Internal fuses - provided with the drive. A60Q25-2 60 033 05.25 PowerFlex DC Technical Data Frame Recommended Field Circuit Fuses - 460V AC Input Frame A and B (Regenerative and Non-Regenerative Drives) A B (1) Drive Current Rating Code 4P1 6P0 010 014 019 027 035 045 052 073 086 100 129 167 207 250 330 412 Field Amps 10 Type 6 x 32 mm Fuse Code FS3(1) (See Frame A and B Fuse Designations on page 36 and Frame A Field AC Input Line Fuses Location on page 39 and Frame B Field AC Input Line Fuses Location on page 40 for location.) Ferraz Shawmut Bussmann (Gould Shawmut) SIBA FWH-016A6F E085449 70 125 40.16 10 x 38 mm FWC-25A10F 14 20 A60Q25-2 60 033 05.25 Internal fuses - provided with the drive. Frame A Field AC Input Line Fuses Location Bottom View of Drive without Fan Bottom View of Drive with Fan Field circuit fuses 39 PowerFlex DC Technical Data Frame B Field AC Input Line Fuses Location Top View of Drive Field circuit fuses 40 PowerFlex DC Technical Data Frame C Fuse Designations All fuses for AC input to the armature and field circuit protection are internally mounted and provided with frame C PowerFlex DC drives with 230V AC input and a current rating of 521A and 460V AC input and a current rating of 495A and 667A. FS4 = Internally mounted fuses for the armature converter on the AC input side. U FS4 V C W U1 FS3 D C1 V1 D1 FS3 = Internally mounted fuses for the field circuit on the AC input side. M Recommended Field Circuit Fuses - 230V AC Input Frame C (Regenerative and Non-Regenerative Drives) Drive Current Rating Code 521 Field Amps 20 Type 10 x 38 mm Fuse Code FS3 (See Frame C Fuse Designations on page 41 and Frame C Field Circuit Fuse Location below for location.) Bussmann Ferraz Shawmut (Gould Shawmut) SIBA FWC-25A10F A60Q25-2 60 033 05.25 Recommended Field Circuit Fuses -460V AC Input Frame C (Regenerative and Non-Regenerative Drives) Drive Current Rating Code 495 667 Field Amps 20 Type 10 x 38 mm Fuse Code FS3 (See Frame C Fuse Designations on page 41 and Frame C Field Circuit Fuse Location below for location.) Bussmann Ferraz Shawmut (Gould Shawmut) SIBA FWC-25A10F A60Q25-2 60 033 05.25 A60Q25-8 Frame C Field Circuit Fuse Location Field AC input fuses are located on the Control EMI shield, which holds the Control board. 41 PowerFlex DC Technical Data Recommended Leg Fuses - 230V AC Input Frame C (Regenerative Drives Only) Drive Current Rating DC Code Amps 521 521 AC Line Amps 426 Fuse Code FS4 (See Frame C Fuse Designations on page 41 and Frame C Regenerative Drive - Leg Fuse Location below for location) Bussmann Ferraz Shawmut (Gould Shawmut) SIBA Square Body - Flush End Contact 170M5464 + switch 170H0069 6,9 URD 32 TTF 800 + switch MS3-V1-5BS 20 671 32.800 + switch 2800104 Recommended Leg Fuses - 460V AC Input Frame C (Regenerative Drives Only) Drive Current Rating Code 495 667 DC Amps 495 667 AC Line Amps 404.4 544.9 Fuse Code FS4 (See Frame C Fuse Designations on page 41 and Frame C Regenerative Drive - Leg Fuse Location below for location) Bussmann Ferraz Shawmut (Gould Shawmut) SIBA Square Body - Flush End Contact 170M5462 + switch 170H0069 6,9 URD 32 TTF 630 + switch MS3-V1-5BS 20 671 32.630 + switch 2800104 170M5464 + switch 170H0069 6,9 URD 32 TTF 800 + switch MS3-V1-5BS 20 671 32.800 + switch 2800104 Frame C Regenerative Drive - Leg Fuse Location Leg fuses and switches are located on the bus bars behind the Control EMI shield, which holds the Control board. Note: Drive shown with front covers removed and Control EMI shield lowered. 42 PowerFlex DC Technical Data Recommended AC Input Line Fuses - 230V AC Input Frame C (Non-Regenerative Drives Only) Drive Current Rating DC Code Amps 521 521 AC Line Amps 426 Fuse Code FS4 (See Frame C Fuse Designations on page 41 and Frame C Regenerative Drive - Leg Fuse Location below for location) Bussmann Ferraz Shawmut (Gould Shawmut) SIBA Square Body - Flush End Contact 170M5466 + switch 170H0069 6,9 URD 32 TTF 1000 + switch MS3-V1-5BS 20 671 32.1000 + switch 2800104 Recommended AC Input Line Fuses - 460V AC Input Frame C (Non-Regenerative Drives Only) Drive Current Rating Code 495 667 DC Amps 495 667 AC Line Amps 404.4 544.9 Fuse Code FS4 (See Frame C Fuse Designations on page 41 and Frame C Regenerative Drive - Leg Fuse Location below for location) Bussmann Ferraz Shawmut (Gould Shawmut) SIBA Square Body - Flush End Contact 170M5464 + switch 170H0069 6,9 URD 32 TTF 800 + switch MS3-V1-5BS 20 671 32.800 + switch 2800104 170M5466 + switch 170H0069 6,9 URD 32 TTF 1000 + switch MS3-V1-5BS 20 671 32.1000 + switch 2800104 Frame C Non-Regenerative Drive - AC Input Line Fuse Location AC Input fuses and switches are located on the bus bars behind the Control EMI shield, which holds the Control board. Note: Drive shown with front covers removed and Control EMI shield lowered. 43 PowerFlex DC Technical Data Control Power Circuit Protection Fuses The following fuses are used to protect the Switching Power Supply circuit and the MOVs on the Pulse Transformer circuit board (frame B drives only) or Transient Noise Filter circuit board (frame C drives only). Frame A B and C Mounted on Switching Power Supply circuit board Switching Power Supply circuit board B C Pulse Transformer circuit board Transient Noise Filter circuit board Designation F1 F1 F2 F1/F2/F3 F11/F21/F31 Fuse 1A, 250V slow, 5x20mm 3.15A, 250V slow, 5x20mm 2.5A, 250V fast, 5x20mm 16A, 500V fast, 6x32mm 25A, 500V fast, 6x32mm Frame A Switching Power Supply Fuse Location Top View of Drive Switching Power Supply fuse Frame B Switching Power Supply Fuse Location Top View of Drive F1 = 3.15A fuse 44 F2 = 2.5A fuse PowerFlex DC Technical Data Frame C Switching Power Supply Fuse Location F1 = 3.15A fuse F2 = 2.5A fuse Fuses are located on the Switching Power Supply circuit board (SW-2) on the back of the Control EMI shield, which holds the Control board. 45 PowerFlex DC Technical Data Mounting Operating Conditions and Temperatures PowerFlex DC drives are designed to operate at 0° to 50° C surrounding air temperature without derating. The drive must be mounted in a clean, dry location. Contaminants such as oils, corrosive vapors and abrasive debris must be kept out of the enclosure. NEMA/UL Type Open, IP20 enclosures are intended for indoor use primarily to provide a degree of protection against contact with enclosed equipment. These enclosures offer no protection against airborne contaminants. Minimum Mounting Clearances Minimum clearance requirements (indicated in Drive Enclosure Minimum Mounting Clearances on page 46) are intended to be from drive to drive. Other objects can occupy this space; however, reduced airflow may cause protection circuits to fault the drive. The drive must be mounted in a vertical orientation as shown below and must not be mounted at an angle greater than 30° from vertical. In addition, inlet air temperature must not exceed the product specification. Drive Enclosure Minimum Mounting Clearances 150 mm (6.0 in.) 150 mm (6.0 in.) PORT MOD NET A NET B PORT MOD NET A STS NET B STS 10 mm (0.4 in.) 10 mm (0.4 in.) 150 mm (6.0 in.) 10 mm (0.4 in.) 50 mm (2.0 in.) Important: Verify that all mounting screws are properly tightened before and after operation. 46 Airflow through the drive must not be impeded. PowerFlex DC Technical Data Approximate Dimensions Frame A Dimensions A mm (in.) 267 (10.5) B mm (in.) 359 (14.0) C mm (in.) 287 (11.3) A1 mm (in.) 250 (9.8) A B1 mm (in.) 275 (10.8) C PORT MOD NET A NET B STS B1 B A1 Frame A Weights Drive w/ND Rating Code 230V 460V 7P0 4P1 9P0 6P0 012 010 020 014 – 019 029 027 038 035 055 045 – 052 073 073 093 086 110 – – 100 – 129 Weight Drive kg (lbs.) 8.4 (19.5) Drive & Packaging kg (lbs.) 10.5 (23.1) 8.8 (19.4) 11 (24.3) 10.8 (23.8) 13 (28.7) 47 PowerFlex DC Technical Data Frame B Dimensions A mm (in.) 311 (12.2) A1 mm (in.) 275 (10.8) A2 mm (in.) 16.5 (0.65) B mm (in.) 388 (15.3) B1 mm (in.) 375 (14.8) A A1 C PORT MOD NET A NET B STS B1 B A2 Frame B Weights Drive w/ND Rating Code 230V 460V 146 167 180 – 218 207 265 250 360 330 434 412 48 C mm (in.) 350 (13.8) Weight Drive kg (lbs.) 25.5 (56.2) Drive & Packaging kg (lbs.) 27.5 (60.6) 29.5 (65.0) 32 (70.5) 31.5 (69.4) 34 (75) PowerFlex DC Technical Data Frame C Dimensions A mm (in.) 521 (20.5) A1 mm (in.) 499 (19.7) B mm (in.) 511 (20.1) B1 mm (in.) 400 (15.7) B2 mm (in.) 200 (7.9) A1 B3 mm (in.) 55 (2.2) B4 mm (in.) 56 (2.2) C mm (in.) 416 (16.4) C B4 PORT MOD NET A NET B B1 STS B B2 B3 A Frame C Weights Drive w/ND Rating Code 230V 460V – 495 521 667 Weight Drive kg (lbs.) 61 (134.5) 65 (143.3) Drive & Packaging kg (lbs.) 74 (163.1) 81 (178.6) 49 PowerFlex DC Technical Data Parameter List The LCD HIM displays parameters in a File–Group–Parameter or Numbered List view order. To switch display mode, access the Main Menu, press ALT, then Sel (View) while the cursor is on the Parameter menu selection. In addition, using Par 211 [Param Access Lvl], you have the option to display the most commonly used parameters (Basic Parameter view) or all parameters (Advanced Parameter View). File–Group–Parameter Order This simplifies programming by grouping parameters that are used for similar functions. The parameters are organized into files. Each file is divided into groups, and each parameter is an element in a group. By default, the LCD HIM displays parameters by File–Group–Parameter view. Numbered List View All parameters are in numerical order. Advanced Parameter View Parameter 211 [Param Access Lvl] set to option 1 “Advanced”. Refer to the PowerFlex Digital DC Drive User Manual, publication 20P-UM001…, for a list of “Basic” view parameters in File-Group-Parameter order. File Monitor Group Speed Meters Monito r Current Meters Drive Data 50 Parameters [Speed Ref A] [Speed Ref A Pct] [Speed Ref B] [Speed Ref B Pct] [Speed Ref Out] [Spd Ref Out Pct] [Ramp In] [Spd Reg Out Pct] [Current Reg In] [Arm Current] [Arm Current Pct] [FaultCode] [AC Line Voltage] [AC Line Freq] 44 47 48 49 385 384 110 236 41 200 199 57 466 588 [Ramp In Pct] [Ramp Out] [Ramp Out Pct] [Speed Draw Out] [Spd Draw Out Pct] [Speed Reg In] [Speed Reg In Pct] [Field Current] [Fld Current Pct] [Cur Lim Pos Out] [Cur Lim Neg Out] [Output Voltage] [Output Power] [Drive Type] 111 113 114 1018 1019 118 117 351 234 10 11 233 1052 300 [Spd Feedback] [Spd Feedback Pct] [Actual Speed] [Encoder Speed] [Tachometer Speed] 122 121 924 420 1408 [Filt TorqCur Pct] [Field Ref Pct] 928 500 [Drive Size] [Elapsed Lifetime] [Software Version] 465 235 331 PowerFlex DC Technical Data File Motor Control Group Motor Data Parameters [Max Ref Speed] [Max Feedback Spd] ol [Rated Motor Volt] [Field Reg Enable] Field Config [Field Economy En] [Field Econ Delay] [Field Mode Sel] [Max Fld Curr Pct] [Min Fld Curr Pct] [Current Limit] Torq Attributes [Current Lim Pos] [Current Lim Neg] [Torque Ref] [Trim Torque] Speed Feedback [Fdbk Device Type] [Anlg Tach Gain] [Anlg Tach Zero] [Spd Fdbk Control] [SpdReg FB Bypass] [Autotune Cur Lim] Autotune [CurrReg Autotune] [Arm Resistance] [Arm Inductance] [Spd Reg Autotune] [TstGen Output] Test Generator [TstGen Frequency] [Minimum Speed] Speed Command Limits [Min Speed Fwd] Speed Comm and Discrete Speeds [Jog Speed] [Jog Off Delay] [Preset Speed 1] [Preset Speed 2] [Trim Ramp] Speed [Trim Ramp Pct] References Motor Contr Speed Regulator [Speed Reg En] [Arm Volt Kp] [Arm Volt Ki] [Spd Reg Kp] [Spd Reg Ki] [Arm Volt Kp Base] [Arm Volt Ki Base] [Spd Reg Kp Base] [Spd Reg Ki Base] [Spd Reg Kp Outpt] [Spd Reg Ki Outpt] [Speed Thresh Pos] [Speed Ramp En] Dynamic Control Ramp Rates [Ramp Type Select] Dynam ic Con trol [Accel Time 1] [Decel Time 1] [Accel Time 2] [Decel Time 2] [MOP Accel Time] [Enable Droop Load Limits [Droop Percent] [Droop Filter] [Fast Stop Time] Stop Modes [Spd 0 Trip Delay] [Start At Powerup] Restart Modes Adaptv Regulator [Adaptive Spd En] [Adaptive Reg Typ] [Adaptive Ref] [Adaptive Spd 1] [Adaptive Spd 2] 45 162 175 497 499 1407 469 467 468 7 8 9 39 40 414 562 563 457 458 1048 452 453 454 1027 58 59 1 5 266 1409 154 155 42 378 [Nom Mtr Arm Amps] [Nom Mtr Fld Amps] [Drv Fld Brdg Cur] [Fld Weaken Ratio] [Fld Reg Kp] [Fld Reg Ki] [Force Min Field] [Out Volt Level] [Fld Reg Kp Base] [Torque Reduction] [Zero Torque] [TrqTpr_Enable] [TrqTpr_Lim0] [TrqTpr_Lim1] [Spd Fdbk Error] [Act Spd Filter] [Encoder PPR] [Encoder Out Sel] [Encoder Err Chk] [Speed Tune Dir] [Speed Tune Kp] [Speed Tune Ki] [Spd Tune Inertia] [SpdTune Friction] [TstGen Amplitude] 179 280 374 456 91 92 498 921 97 342 353 750 751 752 455 923 169 1021 652 1029 1032 1033 1030 1031 60 [Drive Type Sel] 201 [Fld Reg Ki Base] [Set Fld Curve] [Reset Fld Curve] [Fld Const 40 Pct] [Fld Const 70 Pct] [Fld Const 90 Pct] [TrqTpr_Lim2] [TrqTpr_Lim3] [TrqTpr_Lim4] [TrqTpr_Spd] [Filt Torq Cur] [Z Channel Enable] [Z Capture Pos En] [Z Captured Pos] 98 919 920 916 917 918 753 754 755 756 926 911 912 913 [I Reg Error] [Inertia C Filter] [Torque Const] [Inertia] [Friction] [TstGen Offset] 587 1012 1013 1014 1015 61 [Min Speed Rev] [Maximum Speed] [Preset Speed 3] [Preset Speed 4] [Preset Speed 5] [Preset Speed 6] [Trim Speed] [Trim Speed Pct] 6 2 156 157 158 159 43 379 [Max Speed Fwd] [Max Speed Rev] [Preset Speed 7] [TB Manual Ref] 3 4 160 267 [Speed Ratio] 1017 242 493 494 87 88 495 496 93 94 99 100 101 245 18 660 662 24 32 22 699 696 697 38 627 1344 181 182 183 184 185 [Speed Thresh Neg] [Threshold Delay] [At Speed Error] [At Speed Delay] [Ref Zero Level] [Speed Zero Level] [Speed Zero Delay] [Spd Zero I En] [Spd Ref Zero En] [Spd Zero P En] [Spd Zero P Gain] [Lock Speed Integ] [MOP Decel Time] [Jog Ramp Time] [S Curve Time] [S Curve Accel 1] [S Curve Decel 1] [S Curve Accel 2] [S Curve Decel 2] [Droop Limit] [Load Comp] [Torq Red CurLim] [Closing Speed] [Opening Delay] [Powerup Delay] [Adaptive Joint 1] [Adaptive Joint 2] [Adaptive P Gain1] [Adaptive I Gain1] [Adaptive P Gain2] 102 103 104 105 106 107 108 123 124 125 126 348 30 1410 19 665 666 667 668 700 698 13 1262 1263 1345 186 187 188 189 190 [Flying Start En] [Spd Fdbk Filter] [Spd Up Gain Pct] [Speed Up Base] [Speed Up Filter] [SpdReg Kp Bypass] [SpdReg Ki Bypass] [SpdFuncSelect] [InertiaCompAct] [InertiaCompVar] 388 444 445 446 447 459 460 1016 1191 1192 [Ramp Delay] [Zero Ramp Output] [Zero Ramp Input] [Freeze Ramp] [Acc Dec Filter] 20 344 345 373 1212 [Torq Limit Type] 715 [Ramp In Zero En] [Actuator Delay] 1265 1266 [Adaptive I Gain2] [Adaptive P Gain3] [Adaptive I Gain3] 191 192 193 51 PowerFlex DC Technical Data File Applications Applic atio 52 ns Group PI Control Parameters [Enable PI] [PI Steady Thrsh] [PI Integral Gain] [PI Prop Gain PID] [PI Output] [Enable PD] PD Control [PD Output PID] [PD Deriv Gain 1] [Enable PID] PID Control [Real FF PID] [PID Steady Delay] [PI Init Intgl Gn] [PID Clamp] [Feed Fwd PID] [PID Error] [Scale1 Input] Scale Blocks [Scale1 Output] [Scale1 Mul] [Scale1 Div] [Scale1 In Max] [Scale1 In Min] [Scale1 In Off] [Scale1 Out Off] [Scale1 In Abs] [Scale2 Input] [Scale2 Output] [Scale2 Mul] [Scale2 Div] [Scale2 In Max] [Scale2 In Min] [Scale2 In Off] [Scale2 Out Off] [Scale2 In Abs] [Diameter Calc] Diameter Calc [DncrPosSpd] [Max Deviation] [Gear Box Ratio] [Dancer Constant] [Minimum Diameter] [Diameter Calc St] [Max Diameter] [Roll Diameter] Winder Functions [Variable J Comp] [Constant J Comp] [Materl Width Pct] [Static Friction] [Dynamic Friction] [Taper Enable] [Initial Diameter] [Final Diameter] [Tension Reduct] [Tension Ref] [Tension Scale] [Time AccDec Min] [Int Acc Calc En] [Line Accel Pct] [Line Decel Pct] 769 695 764 765 771 770 421 766 1258 418 731 734 757 758 759 484 485 486 487 488 489 490 491 492 553 554 555 556 557 558 559 560 561 794 795 796 797 798 799 800 1153 1154 1171 1172 1173 1174 1175 1176 1177 1178 1179 1180 1181 1182 1183 1184 1185 [PI Central v1] [PI Central v2] [PI Central v3] [PI Central v sel] [PI Central vs0] [PD Deriv Filter] [PD Prop Gain 1] [PD Prop Gain 2] [PID Setpoint 0] [PID Setpoint 1] [PID Setpoint Sel] [PID Feedback] [PID Output Sign] [PID Output Scale] [PID Output] [Scale3 Input] [Scale3 Output] [Scale3 Mul] [Scale3 Div] [Scale3 In Max] [Scale3 In Min] [Scale3 In Off] [Scale3 Out Off] [Scale3 In Abs] [Scale4 Input] [Scale4 Output] [Scale4 Mul] [Scale4 Div] [Scale4 In Max] [Scale4 In Min] [Scale4 In Off] [Scale4 Out Off] [Scale4 In Abs] [Line Spd Thresh] [Line Spd Gain] [Diameter Reset] [Diam Threshold] [Diameter Reached] [Line Speed Pct] [Diam Calc Dis] [Diameter Filter] [Base Omega] [Line FastStp Pct] [Winder Type] [Torq Current Pct] [Act Ten Ref Pct] [Speed Match] [Spd Match Acc] [Spd Match Dec] [Offs Accel Time] [W Offset] [Spd Match Gain] [Winder Side] [W Gain] [Spd Match Compl] [Line Spd Source] [Close Loop Comp] 776 777 778 779 780 767 768 788 760 761 762 763 772 773 774 1218 1219 1220 1221 1222 1223 1224 1225 1226 1227 1228 1229 1230 1231 1232 1233 1234 1235 1155 1156 1157 1158 1159 1160 1161 1162 1163 1186 1187 1193 1194 1195 1196 1197 1198 1199 1200 1201 1202 1203 1204 1208 [PI Central vs1] [PI integr freeze] [PI Upper Limit] [PI Lower Limit] [PI Init Prop Gn] [PD Deriv Gain 2] [PD Prop Gain 3] [PD Deriv Gain 3] [PID Target] [PID Source] [PID Source Gain] [PID Accel Time] [PID Decel Time] [PID Error Gain] 781 783 784 785 793 789 790 791 782 786 787 1046 1047 1254 [Scale5 Input] [Scale5 Output] [Scale5 Mul] [Scale5 Div] [Scale5 In Max] [Scale5 In Min] [Scale5 In Off] [Scale5 Out Off] [Scale5 In Abs] [Scale6 Input] [Scale6 Output] [Scale6 Mul] [Scale6 Div] [Scale6 In Max] [Scale6 In Min] [Scale6 In Off] [Scale6 Out Off] [Scale6 In Abs] [Diam Preset 0] [Diam Preset 1] [Diam Preset 2] [Diam Preset 3] [Diam Preset Sel] [Diam Inc Dec En] [Diam init filter [Diam stdy delay] 1236 1237 1238 1239 1240 1241 1242 1243 1244 1245 1246 1247 1248 1249 1250 1251 1252 1253 1164 1165 1166 1167 1168 1205 1206 1207 [Torque Winder En] [W Target] [Actual Comp] [Closed Loop En] [Speed Demand En] [Spd match torque] [W Reference] [Jog TW Speed] [Jog TW Enable] [Ref Spd Source] [Ref Speed Gain] [Ref Line Speed] [Static F Zero] 1209 1210 1213 1214 1215 1216 1217 1255 1256 1284 1285 1286 1287 PowerFlex DC Technical Data File Utility Group Parameters Reference Config [Direction Mode] [Save HIM Ref] [Param Access Lvl] Drive Memory [Drive Status 1] Diagnostics [Drive Status 2] [Last Stop Source] [Start Inhibits] [Drive Logic Rslt] [At Speed] [At Zero Speed] [CurrLimit Active] [Spd Limit Active] [Speed Threshold] [Clear Fault Que] Faults [Fault Clear] [Fault Clr Mode] [Status1 at Fault] [Status2 at Fault] [Fault Arm Amps] [Fault Speed] [Fault Field Amps] [Fault Voltage] [Fault 1 Code] [Drive Alarm 1] Alarms [OverVolt Flt Cfg] [Aux Inp Flt Cfg] [UsrDsplyMult0] User Defined [UsrDsplyDiv0] [UsrValMult1] [UsrValDiv1] [UserDefined0] [UserDefined1] [UserDefined2] [UserDefined3] [UserDefined4] [UserDefined5] [UserDefined6] [UserDefined7] [UserDefined8] [UserDefined9] [UserDefined10] [UserDefined11] [UserDefined12] [UserDefined13] [DPI Baud Rate] Communications Comm Control [DPI Port Sel] Comm unicat ion Masks & Owners [Logic Mask] [Start Mask] [Jog Mask] [Direction Mask] [Reference Mask] [Accel Mask] [Fault Clr Mask] [Data In A1] Datalinks [Data In A2] [Data In B1] [Data In B2] [Data In C1] [Data In C2] [Logic Mask] Security [Logic Mask Act] Utility 1322 209 211 381 382 1402 1403 1328 394 395 349 372 393 263 1347 1348 1349 1350 1371 1372 1373 1374 1351 1380 203 354 50 51 53 54 503 504 505 506 507 508 509 510 511 512 513 514 515 516 589 590 591 592 593 594 595 596 597 610 611 612 613 614 615 591 1376 [Man Ref Preload] [Save MOP Ref] [Reset Defaults] [Torque Positive] [Torque Negative] [MOP Inc Active] [MOP Dec Active] [Spd Select 0] [Spd Select 1] [Spd Select 2] [Ramp Select 0] [Ramp Select 1] [Encoder State] [Fault 2 Code] [Fault 3 Code] [Fault 4 Code] [Fault 5 Code] [Fault 6 Code] [Fault 7 Code] [Fault 8 Code] [Fault 9 Code] [Fault 10 Code] [Fault 1 Time] [OverTemp Flt Cfg] [FldLoss Flt Cfg] [Spd Loss Flt Cfg] [UserDefined14] [UserDefined15] [UsrDefBitWrdA] [UsrDefBitWrdA0] [UsrDefBitWrdA1] [UsrDefBitWrdA2] [UsrDefBitWrdA3] [UsrDefBitWrdA4] [UsrDefBitWrdA5] [UsrDefBitWrdA6] [UsrDefBitWrdA7] [UsrDefBitWrdA8] [UsrDefBitWrdA9] [UsrDefBitWrdA10] [UsrDefBitWrdA11] [UsrDefBitWrdA12] [UsrDefBitWrdA13] [UsrDefBitWrdA14] [DPI Fdbk Select] 210 249 258 346 347 396 397 400 401 402 403 404 651 1352 1353 1354 1355 1356 1357 1358 1359 1360 1361 365 473 478 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532 533 534 1321 [MOP Select] 1375 [Accel Status] [Decel Status] [Fast Stop Status] [TestPoint Sel] [TestPoint Data] [TaskLoad 32 ms] [TaskLoad 1 ms] [TaskLoad 2 ms] [TaskLoad 8 ms] 1188 1189 1190 1381 1382 1383 1384 1385 1386 [Fault 2 Time] [Fault 3 Time] [Fault 4 Time] [Fault 5 Time] [Fault 6 Time] [Fault 7 Time] [Fault 8 Time] [Fault 9 Time] [Fault 10 Time] 1362 1363 1364 1365 1366 1367 1368 1369 1370 [UnderVolt Thresh] [OverCurrent Thr] 481 584 [UsrDefBitWrdA15] [UsrDefBitWrdB] [UsrDefBitWrdB0] [UsrDefBitWrdB1] [UsrDefBitWrdB2] [UsrDefBitWrdB3] [UsrDefBitWrdB4] [UsrDefBitWrdB5] [UsrDefBitWrdB6] [UsrDefBitWrdB7] [UsrDefBitWrdB8] [UsrDefBitWrdB9] [UsrDefBitWrdB10] [UsrDefBitWrdB11] [UsrDefBitWrdB12] [UsrDefBitWrdB13] [UsrDefBitWrdB14] [UsrDefBitWrdB15] [DPI Port Value] 535 536 537 538 539 540 541 542 543 544 545 546 547 548 549 550 551 552 1343 [MOP Mask] [Local Mask] [Decel Mask] [Stop Owner] [Start Owner] [Jog Owner] [Direction Owner] [Data In D1] [Data In D2] [Data Out A1] [Data Out A2] [Data Out B1] [Data Out B2] [Write Mask Act] [Write Mask Cfg] 598 599 631 600 601 602 603 616 617 618 619 620 621 1377 1378 [Reference Owner] [Accel Owner] [Fault Clr Owner] [MOP Owner] [Local Owner] [Decel Owner] 604 605 606 607 608 609 [Data Out C1] [Data Out C1] [Data Out D1] [Data Out D2] [Data In Val Sel] [Data In SelData] [Port Mask Act] 622 623 624 625 1319 1320 1379 53 PowerFlex DC Technical Data File Input / Output Group Analog Inputs Inputs / Outpu ts Analog Outputs Digital Inputs Digital Outputs DPI Inputs 54 Parameters [Anlg In1 Sel] [Anlg In1 Config] [Anlg In1 Scale] [Anlg1 Tune Scale] [Anlg In1 Offset] [Anlg In1 Tune] [Anlg In1 Filter] [Anlg In2 Sel] [Anlg In2 Config] [Anlg In2 Scale] [Anlg Out1 Sel] [Anlg Out2 Sel] [Anlg Out3 Sel] [ContactorControl] [Dig In Status] [Digital In1 Sel] [Digital In2 Sel] [Digital In3 Sel] [Digital In4 Sel] [Digital In5 Sel] [Digital In6 Sel] [Digital In7 Sel] [Digital In8 Sel] [Digital In9 Sel] [Digital In10 Sel] [Digital In11 Sel] [Dig Out Status] [Digital Out1 Sel] [Digital Out2 Sel] [Digital Out3 Sel] [Digital Out4 Sel] [Digital Out5 Sel] [Digital Out6 Sel] [DPI P1 Select] [DPI P2 Select] 70 71 72 73 74 259 792 75 76 77 66 67 68 1391 564 133 134 135 136 137 138 139 140 141 142 143 581 145 146 147 148 149 150 1323 1324 [Anlg2 Tune Scale] [Anlg In2 Offset] [Anlg In2 Tune] [Anlg In3 Sel] [Anlg In3 Config] [Anlg In3 Scale] [Anlg3 Tune Scale] [Anlg In3 Offset] [Anlg In3 Tune] [Anlg In1 Target] [Anlg Out4 Sel] [Analog Out1 Scale] [Analog Out2 Scale] [Digital In12 Sel] [Inversion In 1] [Inversion In 2] [Inversion In 3] [Inversion In 4] [Inversion In 5] [Inversion In 6] [Inversion In 7] [Inversion In 8] [Inversion In 9] [Inversion In 10] [Inversion In 11] [Inversion In 12] [Digital Out7 Sel] [Digital Out8 Sel] [Relay Out 1 Sel] [Relay Out 2 Sel] [Inversion Out 1] [Inversion Out 2] [Inversion Out 3] [DPI P3 Select] [DPI P4 Select] 78 79 260 80 81 82 83 84 261 295 69 62 63 144 1276 1277 1278 1279 1280 1281 1282 1283 1387 1388 1389 1390 151 152 1392 629 1267 1268 1269 1325 1326 [Anlg In2 Target] [Anlg In3 Target] [Anlg In1 Cmp] [Anlg In1 Cmp Err] [Anlg In1 Cmp Dly] [Anlg In1 Cmp Eq] [Analog In1 Value] [Analog In2 Value] [Analog In3 Value] 296 297 1042 1043 1044 1045 1404 1405 1406 [Analog Out3 Scale] 64 [Analog Out4 Scale] 65 [Dig In Term 1] [Dig In Term 2] [Dig In Term 3] [Dig In Term 4] [Dig In Term 5] [Dig In Term 6] [Dig In Term 7] [Dig In Term 8] [Dig In Term 9] [Dig In Term 10] [Dig In Term 11] [Dig In Term 12] 565 566 567 568 569 570 571 572 573 574 575 576 [Inversion Out 4] [Inversion Out 5] [Inversion Out 6] [Inversion Out 7] [Inversion Out 8] [Inversion Relay1] [Inversion Relay2] [DPI P5 Select] 1270 1271 1272 1273 1274 1393 1275 1327 PowerFlex DC Technical Data PowerFlex DC Configured Drives Overview The PowerFlex DC Configured Drives allow users to create drive packages based on their specific needs. This program enhances stand-alone drive functionality through additional control, power and packaging options, which are ideal for Original Equipment Manufacturers (OEM) and end users with special installation needs. This program consists of: • Standard Configured Drives • Engineer To Order Configured Drives Standard Configured Drives The Standard Configured Drives Program allows users to create drive packages based on their specific needs. A complete drive package may be specified by assembling a single catalog number string that includes a base drive and all required options. Packaging is available for 230 and 460V AC requirements in IP20, NEMA/ UL Type 1 MCC style enclosures or rigid-panel mounted for installation in an existing enclosure. The program consists of a fully defined catalog string identified within this publication. Focused on higher volume, repeat business, the standard designs provide consistent manufacturing and minimizes customer resources by reducing engineering, manufacturing and installation time. Typical delivery is 6…8 weeks from order entry and can be ordered through the order entry system. Engineer To Order Configured Drives (ETO) The Engineer To Order Configured Drives Program offers users the ability to create drive packages beyond the Standard Configured Drives offering. Options may or may not be defined within this publication. Products can be ordered by contacting your Global Drives Systems representative at the central office location or one of the Local Drive Solution Centers. Our engineering experts will assist in defining the specific requirements of your application. The Standard Configured Drive designs may be modified to meet the design criteria or a complete custom package can be designed for any application. The typical lead time of an ETO order is 8…12 weeks based on the lead time and availability of unique components of the design. Benefits • Simplified installation and start-up by use of common options assembled at the factory. • Drive functionality exceeds options offered with a standard drive. • Multiple packaging options specific to customer needs. • Pre-engineered options for easy order entry, consistent manufacturing, high quality and reduced delivery time. • Selectable configurations to meet application requirements. 55 PowerFlex DC Technical Data Features • Standard PowerFlex DC Digital drives and drive-related options. • 6 pulse and 12 pulse. • Enclosure options: IP20 MCC, IP42 Filter, IP00 (mounted on a panel), either conformal coated circuit boards or without. • Pre-engineered options. • Custom/engineered solutions. • UL panel recognition from the factory for pre-engineered options. Factory Installed Options Enclosure Options The PowerFlex Configured DC drives can be ordered in a IP20, NEMA/UL Type 1 MCC style enclosure or a IP43, NEMA/UL Type 1 with Fan & Filter MCC style enclosure. For both of these enclosures the drive, incoming disconnect and any specified operator devices will be mounted and wired in the cabinet or on the door as required. If a cabinet mounted input line reactor is specified, it will be mounted in the cabinet for drives ratings of 200 Hp or less. The drive may also be ordered on a rigid panel for installation in a users existing cabinet. For these designs the drive and all panel mounted parts will be mounted and wired. The incoming disconnect, operator devices and input line reactor will be shipped loose for customer mounting and wiring per local codes. All MCC cabinets are 2286 mm H x 635 mm D (90 in. H x 25 in. D) with the width determined by the size of the drive and the options requested. The standard width enclosures are 508, 635, 889 mm (20, 25 and 35 in.) wide. The rigid panel mount designs are shipped on a 1981 mm H x 508 mm W or 813 mm W (78 in. H x 20 in. W or 32 in. W) panel to fit a standard 610 mm W X 914 mm W (24 in. W or 36 in. W) enclosure. Human Interface Module (HIM) Options The PowerFlex Configured DC drives can be ordered with a variety of HIM modules to meet the needs of each drive. The HIM’s are installed on the door of the enclosures or shipped loose on the Open Panel designs. All designs have the door mounted bezel and interconnect cable to the drive. HIM’s can be installed or updated in the field. No HIM (Blank Plate) Catalog Code: 0 56 LCD Display, Full Numeric Keypad Catalog Code: C LCD Display, Programmer Only Catalog Code: E PowerFlex DC Technical Data I/O Options The PowerFlex Configured DC drive has built-in configurable digital and analog I/O. The digital I/O is 24V DC and the analog I/O can be configured for voltage or current operation. Additional 24V DC and analog I/O can be added or an I/O conversion card can be added to accommodate 115V AC digital I/O. I/O Options Control Code I/O Expansion Card (4 Additional 24V dc Digital Inputs & Outputs, 2 Analog Outputs) A 115V ac Conversion Card (8 Digital Inputs & Outputs) B 8 - 24V - dc Digital Inputs & Outputs, 3 Analog Outputs and 2 Analog Inputs N Communication Options The PowerFlex Configured DC drives are fully compatible with Allen-Bradley drive’s wide variety of DPI communication adapters, offering the following options. Description Catalog No. ControlNet™ Communication Adapter (Coax) C DeviceNet™ Communication Adapter D EtherNet/IP™ Communication Adapter E Interbus™ Communication Adapter I LonWorks™ Communication Adapter L PROFIBUS™ DP Communication Adapter P ControlNet™ Communication Adapter (Fiber) Q Remote I/O Communication Adapter R None N Cabinet Options The Configured Drive enclosure can be equipped with a variety of standard user option. These options are predefined as described below. Other options can be ordered through the ETO program. Description None Catalog No. N Start and Stop PB’s 1 Local/Remote SS 2 E-Stop PB 3 Jog 4 Blower Motor Starter 5 Options 1 & 2 A Options 1 & 3 B Options 1 & 4 C Options 1 - 3 D Options 1 - 4 E Options 1 - 5 F Options A & 4 G Options A & 5 H Options B & 4 J Options B & 5 K 57 PowerFlex DC Technical Data Certifications The PowerFlex DC Drive is a UL/cUL certified product. The Configured Drive enclosure can also be built to UL/cUL certification and to CSA certification. Description Code None (Drive unit is UL/cUL N UL/cUL 1 CSA Inspection & certification 2 Please contact your local distributor or sales office for product availability. Configured Drives offers Quick Ship and PreEngineered Programs. Configured Drive Enclosure Dimensions Frame 1 Frame 2 150 mm (5.91 in.) JOG 150 mm (5.91 in.) START JOG START LOCAL-REMOTE STOP SPEED EMERG STOP PORT PORT MOD MOD NET A NET A NET B NET B STS STS LOCAL-REMOTE STOP SPEED EMERG STOP 1986 mm (78.25 in.) 1986 mm (78.25 in.) 150 mm (5.91 in.) 150 mm (5.91 in.) 508 mm (20.0 in.) 58 635 mm (25.0 in.) PowerFlex DC Technical Data Configured Drive Enclosure Dimensions, Continued Frame 3 150 mm (5.91 in.) JOG START LOCAL-REMOTE STOP SPEED EMERG STOP PORT MOD NET A NET B STS 1986 mm (78.25 in.) 150 mm (5.91 in.) 889 mm (35.0 in.) 59 PowerFlex DC Technical Data Specifications Category Agency Certification Specification According to file E59272 for the series of the approved devices. The drive is also designed to meet the following specifications: NFPA 70 - US National Electrical Code Category Drive Type Protection Environment(1) (1) 60 Specification Full Wave Regen, 6 Pulse, Regulated Field Supply Heat Sink Thermistor: Monitored by microprocessor overtemp trip Drive Overcurrent Trip Software Overcurrent Trip: 200% of rated current (typical) Hardware Overcurrent Trip: 220-300% of rated current (dependent on drive rating) Line transients: Up to 2000 volts peak per IEC 6100-4-5 Control Logic Noise Immunity: Showering arc transients up to 1500V peak Power Ride-Thru: 15 milliseconds at full load Logic Control Ride-Thru: 0.5 seconds minimum, 2 seconds typical Ground Fault Trip: Phase-to-ground on drive output Short Circuit Trip: Phase-to-phase on drive output Altitude: 1000 m (3300 ft) max. without derating. De-rate output power by 1.2% for every 100 meters (328ft) above 1000 meters (3300ft). Maximum Surrounding Air Temperature IP20, NEMA Type Open: 0 to 50 degrees C (32 to 122 degrees F), typical. Storage Temp. (all const.): –25 to 55 degrees C (–13 to 131 degrees F) Atmosphere: Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere. Relative Humidity: Operating: 5 to 85% non-condensing Storage: 5 - 95% non-condensing Shock: 15G peak for 11ms duration (±1.0 ms) Vibration: 0.152 mm (0.006 in.) displacement, 1G peak PowerFlex DC drives must be installed in a Pollution Degree 2 environment. PowerFlex DC Technical Data Category Drive Type Electrical Control Specification Full Wave Regen, 6 Pulse, Regulated Field Supply Input Voltages: 230 to 480V AC +/- 10%, 3 Phase Input Frequency: 50/60 Hz +/- 5% Armature Output Voltage: Two Quadrant Drives Four Quadrant Drives 260V DC @ 230V AC 240V DC @ 230V AC 470V DC @ 400V AC 420V DC @ 400V AC 530V DC @ 440V AC 460V DC @ 440V AC 560V DC @ 460V AC 480V DC @ 460V AC 580V DC @ 480V AC 500V DC @ 480V AC Output Horsepower (Cont.) 1.5 to 150 HP @ 230V AC 2 to 400 HP @ 460V AC Output Current: 4.1 to 667A Overload Capability: 100% rated continuous current 150% rated current for one minute then fault 200% rated current for three seconds then fault Field Output Voltage 200V DC @ 230V AC 310V DC @ 400V AC 360V DC @ 460V AC Maximum field output voltage is 0.85 x AC input line voltage. Controller Current Overload: 150% rated current for one minute 200% rated current for three seconds Max. Short Circuit Ratings: 100,000 A, with the following exceptions: • 230V AC input, 521 A, two quadrant drives are short circuit rated at 10,000 A • 460V AC input, 495 A and 667 A, two quadrant drives are short circuit rated at 18,000 A Speed Regulation:* All operating modes: Max. speed: 8000 rpm Digital reference resolution: 0.25 rpm Analog reference resolution: ≥ 0.25 rpm with Digital Incremental Encoder Speed feedback resolution 0.5 rpm Operating range better than 1000:1 rpm, bi-directional Performance Accuracy ±0.02% typical 170 rad/sec bandwidth with DC Analog Tachometer Speed feedback resolution better than 2000:1 rpm Operating range better than 1000:1 rpm, bi-directional Performance accuracy ±0.1% 170 rad/sec bandwidth *Subject to motor specs, current loop tuning. Torque Regulation Feedback Devices Encoder DC Analog Tachometer Current feedback resolution better than 2000:1 rpm Performance accuracy: 1.0% typical 500 rad/sec bandwidth Type: Incremental, dual channel, two channel optional (with jumper), differential (recommended) or single-ended Input Voltage: Configurable for +2.5V - 5.2V (switch S21 in ENC_5 position) or +5.4V - 15.2V (switch S21 in ENC_12 position) Input Current: 4.5 mA / 6.8 - 10.9 mA each channel Quadrature: 90° ± 27° @ 25° C Duty cycle: 50% ± 10% Source/Sink capable Pulses Per Revolution: 600 to 9999 Maximum Frequency: 150 kHz Maximum Cable Length: Shielded, 150m (0.75 mm2), 125m (0.5 mm2), 55m (0.22 mm2) Input Voltage: 22.7, 45.4, 90.7, 181.6, & 302.9V max. Input Current: 8 mA full scale Maximum Cable Length: Shielded, depends on the installation, typical 150m. 61 PowerFlex DC Technical Data Category Inputs Specification Analog Inputs Digital Inputs Outputs Analog Outputs Digital Outputs Relay Outputs Three configurable, isolated, differential ±10V, 0-10V, 0-20mA or 4-20mA. Eight standard configurable, four additional configurable with the I/O Expansion circuit board. Max Voltage +30V DC input, 200mA (total current draw is the sum of encoder power, digital outputs and any other loads connected to terminal 19) Two standard configurable, two additional configurable with the I/O Expansion circuit board. Sampling rate 2 ms. ± 10V, 5mA, bipolar (current is not bipolar) Four standard configurable, four additional configurable with the I/O Expansion circuit board. + 30V, 50mA Two configurable, N.O. contacts Max. 250V AC, 1A AC1 Watts Loss Watts loss data shown below is based on the rated current of the drive. Frame Important: For drives with 230V input, rated 150 hp / 521 amps, the cooling fans must be powered by an external 230V 50/60 Hz power supply at terminals U3 & V3. A B C (1) 62 Drive Current Rating Code(1) @ 230V @ 460V 7P0 4P1 9P0 6P0 012 010 020 014 – 019 029 027 038 035 055 045 – 052 073 073 093 086 110 – – 100 – 129 146 167 180 – 218 207 265 250 – 330 360 412 434 – 521 495 – 667 Total Watts Loss (W) 131 Fans Voltage (V) – 186 254 – – Internal power supply Rated Current (A) – Air Capacity (m3/h) – – 80 408 476 160 160 553 160 781 320 939 1038 1248 1693 320 320 320 680 2143 2590 230 230 0.75 0.75 1050 1050 Refer to Catalog Number Explanation on page 6, positions 8-10 for corresponding drive HP rating, armature amp rating and field amp rating. PowerFlex DC Technical Data Reference Materials For additional PowerFlex DC data and general drive information, refer to the following publications: Title PowerFlex Digital DC Drive User Manual A Global Reference Guide for Reading Schematic Diagrams Guarding Against Electrostatic Damage Preventive Maintenance of Industrial Control and Drive System Equipment Safety Guidelines for the Application, Installation and Maintenance of Solid State Control Publication Available Online at . . . 20P-UM001… 100-2.10 8000-4.5.2 www.rockwellautomation.com/literature DRIVES-TD001… SGI-1.1 For other information, contact Allen-Bradley Drives Technical Support: Title Allen-Bradley Drives Technical Support Online at . . . www.ab.com/support/abdrives 63 www.rockwellautomation.com Power, Control and Information Solutions Headquarters Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA,Tel: (1) 414.382.2000, Fax: (1) 414.382.4444 Europe/Middle East/Africa: Rockwell Automation, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium,Tel: (32) 2 663 0600, Fax: (32) 2 663 0640 Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong,Tel: (852) 2887 4788, Fax: (852) 2508 1846 Publication 20P-TD001C-EN-P - August, 2008 Supersedes 20P-TD001B-EN-P - October 2007 Copyright © 2008 Rockwell Automation, Inc. All rights reserved. Printed in USA.