Download Quick Start Guide

Transcript
50 — AC Drive Control (Continued)
Modbus
0300H
0301H
Groups
50.01
50.02
Parameter
Description
Range
Source of LOCAL/HAND 04
Frequency
Master Frequency determined
by RS-485 (Frequency
retained)
05
Master Frequency determined
by RS-485 (Frequency not
retained)
Master Frequency determined
by digital keypad on the drive.
Master Frequency determined
by 0 – 10V on terminal AI1.
Master Frequency determined
by 4 – 20 mA on terminal AI2.
Master Frequency determined
by -10 – 10V on terminal AI3.
Master Frequency determined
by RS-485 (Frequency
retained)
Master Frequency determined
by RS-485 (Frequency not
retained)
Operating commands
determined by the Digital
Keypad.
Operating commands
determined by the External
Control Terminals. Keypad
STOP key is enabled.
Operating commands
determined by the External
Control Terminals. Keypad
STOP key is not enabled.
Operating commands
determined by the RS-485
communication interface.
Keypad STOP key is enabled.
Operating commands
determined by the RS-485
communication interface.
Keypad STOP key is not
enabled.
Operating commands
determined by the Digital
Keypad.
Operating commands
determined by the External
Control Terminals. Keypad
STOP key is enabled.
Operating commands
determined by the External
Control Terminals. Keypad
STOP key is not enabled.
Operating commands
determined by the RS-485
communication interface.
Keypad STOP key is enabled.
Operating commands
determined by the RS-485
communication interface.
Keypad STOP key is not
enabled.
Disable
Source of REMOTE/
AUTO Frequency
00
01
02
03
04
05
0302H
50.03
Source of LOCAL/HAND 00
Operation Command
01
02
0302H
50.03
Source of LOCAL/HAND 03
Operation Command
04
0303H
50.04
Source of REMOTE/
AUTO Operation
Command
00
01
02
03
04
0304H
50.05
0305H
0306H
50.06
50.07
0307H
50.08
MN04000002E
Dual Frequency Input
Mode
Trim Reference
Keypad Frequency
Setting
Stop Method
00
01
50.01 + 50.02
02
50.01 – 50.02
03
50.02 trims 50.01 (Reference)
0.00 to 100.00%
50.00 to 400.00 Hz
00
01
02
03
STOP = Ramp, EF = Coast
STOP = Coast, EF = Coast
STOP = Ramp, EF = Ramp
STOP = Coast, EF = Ramp
10
Default
User
Settings
00
01
00
00
01
00
0.00
60.00
00
June 2006