Download User Manual
Transcript
Installation Device installation in a heating system – Pressure maintenance with diaphragm-type "MAG" expansion tank 1 2 3 4 6 5 ≥ 500 0 °C ≤ t ≤ 70 °C V EC 15 WC 15 20 psv 000172_001_R001 1 2 3 Heating system Pressure expansion tank For optional equipment and accessories, see chapter 4.6 "Optional equipment and accessories" on page 14 4 5 6 Device "DC" degassing line (gas-rich water) "DC" degassing line (degassed water) Proceed as follows: • Connect the "DC" degassing lines in the "V" main volume flow of the facility system. • The device requires two "DC" degassing lines to the facility system. – One degassing line for the gas-rich water from the facility system – One degassing line for the degassed water back to the facility system • Install the degassing lines near the "EC" expansion line. – You ensure stable pressure conditions. • Install the device near the "MAG" diaphragm expansion tank. – You ensure pressure monitoring of the diaphragm expansion tank. – Set the "Magcontrol" operating mode at the device controller. Note! • Ensure the integration with the "V“ main flow volume. in particular in switching variants with hydraulic switching points and return admixtures. – For switching and make-up variants, see chapter 6.4 "Switching and make-up variants" on page 23 . Vacuum spray degassing — 03.11.2014 English — 21