Troubleshooting Appendix B Indicator Behavior Probable Error Probable Cause Recommended Action All indicators off No input power or power supply error No line power Verify proper line voltage and connections to the controller. Power supply overloaded This problem can occur intermittently if power supply is overloaded when output loading and temperature varies. Hardware faulted Processor hardware error Cycle power. Contact your local Allen-Bradley representative if the error persists. Loose wiring Verify connections to the controller. Power and FAULT indicators on solid Power on with solid indicator and FAULT indicator flashing Application fault Hardware/software major fault detected For error codes and status information, refer to the Connected Components Workbench online Help Power on with solid indicator and FAULT indicator flashing Operating system fault Firmware upgrade unsuccessful See Flash Upgrade Your Micro800 Firmware on page 121. Error codes This section lists possible error codes for your controller, as well as recommended actions for recovery. If an error persists after performing the recommended action, contact your local Rockwell Automation technical support representative. For contact information, go to http://support.rockwellautomation.com/MySupport.asp Rockwell Automation Publication 2080-UM005A-EN-E - December 2013 113