Download FAULT CODES - du
Transcript
FAULT CODES INSUFFICIENT WATER FLOW RATE Fault Code: 001 Description The flow switch FSE is detecting a low water flow rate in the evaporator heat exchanger for more than 3 seconds Action F Immediate shutdown of the whole unit. F A fault signal is shown on the display. F The remote fault signal is delayed by 6 minutes Reset The unit restarts automatically, 20 seconds after the flow switch detects a flow rate. Possible causes Problem with the pump control wiring. Problem with the flow switch wiring Dirty or clogged water filter. Wrong setting of the flow switch. CLIMATIC 50 user manual – chillers ranges Solving the problem Check the pump connections Check the flow switch connections Clean the water filter. Check the flow switch settings. CL50-CHILLERS/IOM/1004-E 28 28